[2026-08-08 04:11:04.863 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753102, value:-127.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:04.864 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:04.865 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:04.881 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:04.904 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:04.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:04.939 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:04.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:04.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5849.800000 = p_th_old_:5859.700000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:04.939 UTC] [V] OFSCtrl CHG 21 batt_w:-12772.988173 = old:-12696.857173 +  kp:0.550000 * e:-137.700000 + ki:0.000000 * sume:9377782.900239 + kd:0.040000 * (e:-137.700000 - e1:-127.800000)
[2026-08-08 04:11:04.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:12772.988173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:04.940 UTC] [V] OFSCtrl CHG 29 q:-128.000000, mod(round):0.000000
[2026-08-08 04:11:04.940 UTC] [D] OFSCtrl battery ctrl val:-25.500000
[2026-08-08 04:11:04.940 UTC] [V] 485ChCtl <C3> battery limit on [-128.000000,] request.
[2026-08-08 04:11:04.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:04.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:04.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-128] set rate[-25.600000] value100[500] value-100[-500]
[2026-08-08 04:11:04.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff80]
[2026-08-08 04:11:05.003 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:05.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.039 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:05.049 UTC] [V] CIStDb UpdateStatusData. [SELECT no, on_time, off_time FROM contact_input_status WHERE no BETWEEN '1' AND '9' ORDER BY no ASC ]
[2026-08-08 04:11:05.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301784 UPRstat:0
[2026-08-08 04:11:05.091 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:05.091 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:05.091 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:05.091 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:05.092 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:05.104 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:05.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.139 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:05.204 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:05.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:05.303 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:05.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:05.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:05.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:05.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:05.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:05.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:05.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:05.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.438 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.538 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:05.738 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301786 UPRstat:0
[2026-08-08 04:11:05.739 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:05.739 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040407f202231bba]
[2026-08-08 04:11:05.739 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:05.740 UTC] [V] OFSCtrl Rcv set flux_of_solar:203.400000
[2026-08-08 04:11:05.740 UTC] [V] 485DevCtl <C1:01> [01][401006][2034.000000][1][W/m2]
[2026-08-08 04:11:05.740 UTC] [V] SummDat SetVrmValue dev_id:1 val:203400.000000 sc:3
[2026-08-08 04:11:05.740 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2034.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:05.741 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.741 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.742 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:05.742 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:05.742 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:05.753 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:05.755 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:05.760 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:05.761 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:05.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:05.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:05.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:05.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:05.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:05.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:05.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:05.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.839 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:05.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:05.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:05.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5839.900000 = p_th_old_:5849.800000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:05.940 UTC] [V] OFSCtrl CHG 21 batt_w:-12732.876673 = old:-12772.988173 +  kp:0.550000 * e:58.650000 + ki:0.000000 * sume:9377841.550239 + kd:0.040000 * (e:58.650000 - e1:-137.700000)
[2026-08-08 04:11:05.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:12732.876673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:05.940 UTC] [V] OFSCtrl CHG 29 q:-128.000000, mod(round):1.000000
[2026-08-08 04:11:05.940 UTC] [D] OFSCtrl battery ctrl val:-25.500000
[2026-08-08 04:11:05.940 UTC] [V] 485ChCtl <C3> battery limit on [-127.000000,] request.
[2026-08-08 04:11:05.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:05.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:05.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-127] set rate[-25.400000] value100[500] value-100[-500]
[2026-08-08 04:11:05.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff81]
[2026-08-08 04:11:06.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.038 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301785 UPRstat:0
[2026-08-08 04:11:06.103 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:06.105 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:06.106 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:06.107 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:06.111 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:06.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.200 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301785 UPRstat:0
[2026-08-08 04:11:06.200 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:06.202 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [040328000062440000631c00005716000000510000025a000102ba00000296ffff4931fffffe2d00121684dc53]
[2026-08-08 04:11:06.202 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:06.203 UTC] [V] OFSCtrl Rcv set p_co:6620.000000, p_co_old:6660.000000
[2026-08-08 04:11:06.203 UTC] [V] 485DevCtl <C1:04> [01][601260][662.000000][2][kW]
[2026-08-08 04:11:06.203 UTC] [V] SummDat SetVrmValue dev_id:4 val:6620.000000 sc:3
[2026-08-08 04:11:06.204 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:662.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:06.204 UTC] [V] 485DevCtl <C1:04> [01][603260][1185412.000000][1][kWh]
[2026-08-08 04:11:06.204 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185412.000000 sc:1
[2026-08-08 04:11:06.204 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185412.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:06.205 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:06.205 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:06.205 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:06.205 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:06.205 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:06.205 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6620.000000
[2026-08-08 04:11:06.205 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:203.400000 < rad_th:80.000000
[2026-08-08 04:11:06.206 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301823:6620.000000
[2026-08-08 04:11:06.206 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:06.206 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:06.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.238 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:06.244 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:06.244 UTC] [D] OFSCtrl pv-pcs ctrl val:20.618458 old:20.118458
[2026-08-08 04:11:06.244 UTC] [V] OCHisDB set rate:21 t_rate:249 cnt:13
[2026-08-08 04:11:06.244 UTC] [V] 485ChCtl <C2> pv-pcs limit on [20.618458] request.
[2026-08-08 04:11:06.245 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:06.245 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:06.254 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:06.304 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:06.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:06.320 UTC] [D] VarInf update ofs_rate:20.618458
[2026-08-08 04:11:06.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:06.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:06.321 UTC] [D] VarInf update ofs_rate:20.618458
[2026-08-08 04:11:06.321 UTC] [D] VarInf Limit setRate[206.184570] rate[20.618458] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:06.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:20.618458 set_rate206
[2026-08-08 04:11:06.321 UTC] [D] VarInf Limit rt[2] int_set_rate[206] server_rate[20.618458] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:06.324 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00ce063b]
[2026-08-08 04:11:06.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.404 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:06.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.504 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017911, monitor_cnt:123, bc_elapsed:11, min:10, max:40
[2026-08-08 04:11:06.505 UTC] [V] 485DevCtl <C1:03> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:06.505 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:06.505 UTC] [V] 485ChCtl <C1> send request:omron03
[2026-08-08 04:11:06.506 UTC] [D] 485AcReq <C1:03> PutOStream [2][08000303002000084424]
[2026-08-08 04:11:06.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.538 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.619 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:06.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:06 val:6620.000000
[2026-08-08 04:11:06.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:06' , 6620.000000 , 0  )
[2026-08-08 04:11:06.721 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:06.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:06.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.839 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:06.869 UTC] [V] 485DevCtl <C1:03> AnalyzeResponseData proc restart cnt:301780 UPRstat:0
[2026-08-08 04:11:06.870 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:06.870 UTC] [D] 485DevCtl <C1:03> RcvDat status[2] len[21] [0303100000000038226e14000000000006843bc39f]
[2026-08-08 04:11:06.870 UTC] [D] 485DevCtl <C1:03> ResCnd OperationId [2] IsNormal[1] 
[2026-08-08 04:11:06.871 UTC] [V] StructInfo Add 941780.500000 = 0.000000+941780.500000+0.000000
[2026-08-08 04:11:06.872 UTC] [V] 485DevCtl <C1:03> [01][603202][94178050.000000][2][kWh]
[2026-08-08 04:11:06.874 UTC] [V] SummDat SetVrmValue dev_id:3 val:94178050.000000 sc:2
[2026-08-08 04:11:06.880 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:603202, value:94178050.000000, scaleFactor:2, devId:3
[2026-08-08 04:11:06.880 UTC] [V] 485DevCtl <C1:03> [01][604202][94178050.000000][2][kWh]
[2026-08-08 04:11:06.880 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:604202, value:94178050.000000, scaleFactor:2, devId:3
[2026-08-08 04:11:06.881 UTC] [V] StructInfo Add 427.067000 = 0.000000+427.067000+0.000000
[2026-08-08 04:11:06.881 UTC] [V] 485DevCtl <C1:03> [01][613202][42706.700000][2][kWh]
[2026-08-08 04:11:06.881 UTC] [V] SummDat SetVrmValue dev_id:3 val:42706.700000 sc:2
[2026-08-08 04:11:06.907 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:613202, value:42706.700000, scaleFactor:2, devId:3
[2026-08-08 04:11:06.911 UTC] [V] 485DevCtl <C1:03> device_type:Grid-Meter
[2026-08-08 04:11:06.924 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:06.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:06.939 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:06.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:06.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5830.000000 = p_th_old_:5839.900000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:06.940 UTC] [V] OFSCtrl CHG 21 batt_w:-12909.272673 = old:-12732.876673 +  kp:0.550000 * e:-295.000000 + ki:0.000000 * sume:9377546.550239 + kd:0.040000 * (e:-295.000000 - e1:58.650000)
[2026-08-08 04:11:06.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:12909.272673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:06.941 UTC] [V] OFSCtrl CHG 29 q:-130.000000, mod(round):1.000000
[2026-08-08 04:11:06.941 UTC] [D] OFSCtrl battery ctrl val:-25.800000
[2026-08-08 04:11:06.941 UTC] [V] 485ChCtl <C3> battery limit on [-129.000000,] request.
[2026-08-08 04:11:06.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:07.004 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017916, monitor_cnt:128, bc_elapsed:16, min:10, max:40
[2026-08-08 04:11:07.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.039 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:07.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:07.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-129] set rate[-25.800000] value100[500] value-100[-500]
[2026-08-08 04:11:07.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff7f]
[2026-08-08 04:11:07.104 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017917, monitor_cnt:129, bc_elapsed:17, min:10, max:40
[2026-08-08 04:11:07.105 UTC] [V] 485DevCtl <C1:05> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:07.105 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:07.105 UTC] [V] 485ChCtl <C1> send request:omron04
[2026-08-08 04:11:07.107 UTC] [D] 485AcReq <C1:05> PutOStream [1][0800050300030014b441]
[2026-08-08 04:11:07.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.138 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:07.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301786 UPRstat:0
[2026-08-08 04:11:07.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:07.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:07.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:07.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:07.203 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:07.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.239 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:07.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.338 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:07.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.438 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:07.504 UTC] [V] 485DevCtl <C1:05> AnalyzeResponseData proc restart cnt:301779 UPRstat:0
[2026-08-08 04:11:07.505 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:07.506 UTC] [D] 485DevCtl <C1:05> RcvDat status[2] len[45] [0503280000e0d60000e7690000dae700000061000002580002fe9d000007aaffff4e57fffffe3a001382b99b37]
[2026-08-08 04:11:07.506 UTC] [D] 485DevCtl <C1:05> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:07.507 UTC] [V] OFSCtrl Rcv set p_pv:19620.000000
[2026-08-08 04:11:07.508 UTC] [V] 485DevCtl <C1:05> [01][601259][1962.000000][2][kW]
[2026-08-08 04:11:07.508 UTC] [V] SummDat SetVrmValue dev_id:5 val:19620.000000 sc:3
[2026-08-08 04:11:07.515 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:601259, value:1962.000000, scaleFactor:2, devId:5
[2026-08-08 04:11:07.519 UTC] [V] 485DevCtl <C1:05> [01][603259][1278649.000000][1][kWh]
[2026-08-08 04:11:07.520 UTC] [V] SummDat SetVrmValue dev_id:5 val:1278649.000000 sc:1
[2026-08-08 04:11:07.527 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:603259, value:1278649.000000, scaleFactor:1, devId:5
[2026-08-08 04:11:07.531 UTC] [V] 485DevCtl <C1:05> device_type:PV-Meter
[2026-08-08 04:11:07.537 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:07.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.539 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:07.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017922, monitor_cnt:134, bc_elapsed:22, min:10, max:40
[2026-08-08 04:11:07.604 UTC] [V] 485DevCtl <C1:06> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:07.604 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:07.605 UTC] [V] 485ChCtl <C1> send request:omron06
[2026-08-08 04:11:07.606 UTC] [D] 485AcReq <C1:06> PutOStream [1][08000603000000144472]
[2026-08-08 04:11:07.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1183->1183] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.639 UTC] [V] OFSCtrl angif value:1183 power_val_:6331.250000
[2026-08-08 04:11:07.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:07.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.739 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:07.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1183->1183] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.838 UTC] [V] OFSCtrl angif value:1183 power_val_:6331.250000
[2026-08-08 04:11:07.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1183->1183] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:07.938 UTC] [V] OFSCtrl angif value:1183 power_val_:6331.250000
[2026-08-08 04:11:07.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:07.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5820.100000 = p_th_old_:5830.000000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:07.939 UTC] [V] OFSCtrl CHG 21 batt_w:-13199.051173 = old:-12909.272673 +  kp:0.550000 * e:-511.150000 + ki:0.000000 * sume:9377035.400239 + kd:0.040000 * (e:-511.150000 - e1:-295.000000)
[2026-08-08 04:11:07.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13199.051173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:07.940 UTC] [V] OFSCtrl CHG 29 q:-132.000000, mod(round):0.000000
[2026-08-08 04:11:07.940 UTC] [D] OFSCtrl battery ctrl val:-26.400000
[2026-08-08 04:11:07.940 UTC] [V] 485ChCtl <C3> battery limit on [-132.000000,] request.
[2026-08-08 04:11:07.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:07.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:07.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-132] set rate[-26.400000] value100[500] value-100[-500]
[2026-08-08 04:11:07.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff7c]
[2026-08-08 04:11:08.004 UTC] [V] 485DevCtl <C1:06> AnalyzeResponseData proc restart cnt:301780 UPRstat:0
[2026-08-08 04:11:08.004 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:08.006 UTC] [D] 485DevCtl <C1:06> RcvDat status[2] len[45] [060328000007f4000008060000080700008ed400008fb000009186ffffff9c00000259fffe01fdfffffae70848]
[2026-08-08 04:11:08.006 UTC] [D] 485DevCtl <C1:06> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:08.006 UTC] [V] OFSCtrl Rcv set p_batt:-13050.000000
[2026-08-08 04:11:08.009 UTC] [V] 485DevCtl <C1:06> [01][601237][-1305.000000][2][kW]
[2026-08-08 04:11:08.009 UTC] [V] SummDat SetVrmValue dev_id:6 val:-13050.000000 sc:3
[2026-08-08 04:11:08.009 UTC] [V] OCMgr SetMeterValue PhId:0106, branchNo:01, valueId:601237, value:-1305.000000, scaleFactor:2, devId:6
[2026-08-08 04:11:08.010 UTC] [V] 485DevCtl <C1:06> device_type:Batt-Meter
[2026-08-08 04:11:08.010 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:08.022 UTC] [D] 485ChCtl <C1> monitoring dev All Send
[2026-08-08 04:11:08.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1183->1183] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.039 UTC] [V] OFSCtrl angif value:1183 power_val_:6331.250000
[2026-08-08 04:11:08.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301787 UPRstat:0
[2026-08-08 04:11:08.089 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:08.090 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:08.090 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:08.090 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:08.090 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:08.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1183->1183] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.139 UTC] [V] OFSCtrl angif value:1183 power_val_:6331.250000
[2026-08-08 04:11:08.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.238 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:08.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.338 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:08.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.439 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:08.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.539 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:08.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.639 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:08.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:08.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.738 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:08.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.838 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:08.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:08.939 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:08.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:08.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5810.200000 = p_th_old_:5820.100000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:08.940 UTC] [V] OFSCtrl CHG 21 batt_w:-13242.649673 = old:-13199.051173 +  kp:0.550000 * e:-108.550000 + ki:0.000000 * sume:9376926.850239 + kd:0.040000 * (e:-108.550000 - e1:-511.150000)
[2026-08-08 04:11:08.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13242.649673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:08.941 UTC] [V] OFSCtrl CHG 29 q:-133.000000, mod(round):1.000000
[2026-08-08 04:11:08.941 UTC] [D] OFSCtrl battery ctrl val:-26.500000
[2026-08-08 04:11:08.941 UTC] [V] 485ChCtl <C3> battery limit on [-132.000000,] request.
[2026-08-08 04:11:08.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:09.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.039 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:09.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-132] set rate[-26.400000] value100[500] value-100[-500]
[2026-08-08 04:11:09.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff7c]
[2026-08-08 04:11:09.121 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017937, monitor_cnt:50, bc_elapsed:3017937, min:10, max:40
[2026-08-08 04:11:09.121 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:09.122 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:09.123 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:09.124 UTC] [D] 485AcReq <C2:01> PutOStream [1][08000104138a0024d57f]
[2026-08-08 04:11:09.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.139 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301788 UPRstat:0
[2026-08-08 04:11:09.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:09.201 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:09.201 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:09.201 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:09.202 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:09.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.338 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.438 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.527 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:09.536 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[77] [01044801b1fc9f000017260000019927a6000019aa001a198c001a19ae001827cf000010b810c010d9008a0089008affffffffffffffffffffffff273600000670000003db0258267a82001f6b]
[2026-08-08 04:11:09.537 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:09.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.539 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.544 UTC] [V] 485DevCtl <C2:01> [01][115202][433.000000][1][kWh]
[2026-08-08 04:11:09.545 UTC] [V] SummDat SetVrmValue dev_id:7 val:433.000000 sc:1
[2026-08-08 04:11:09.550 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:115202, value:433.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.555 UTC] [V] 485DevCtl <C2:01> [01][113202][64671.000000][0][kWh]
[2026-08-08 04:11:09.557 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671.000000 sc:0
[2026-08-08 04:11:09.561 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:113202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:09.561 UTC] [V] 485DevCtl <C2:01> [01][121005][409.000000][1][℃]
[2026-08-08 04:11:09.561 UTC] [V] SummDat SetVrmValue dev_id:7 val:40900.000000 sc:3
[2026-08-08 04:11:09.561 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121005, value:409.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.569 UTC] [V] 485DevCtl <C2:01> [01][101100][6570.000000][1][V]
[2026-08-08 04:11:09.570 UTC] [V] SummDat SetVrmValue dev_id:7 val:657000.000000 sc:3
[2026-08-08 04:11:09.572 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101100, value:6570.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.575 UTC] [V] 485DevCtl <C2:01> [01][101101][26.000000][1][A]
[2026-08-08 04:11:09.576 UTC] [V] SummDat SetVrmValue dev_id:7 val:2600.000000 sc:3
[2026-08-08 04:11:09.579 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101101, value:26.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.581 UTC] [V] 485DevCtl <C2:01> [02][101100][6540.000000][1][V]
[2026-08-08 04:11:09.583 UTC] [V] SummDat SetVrmValue dev_id:7 val:654000.000000 sc:3
[2026-08-08 04:11:09.587 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101100, value:6540.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.591 UTC] [V] 485DevCtl <C2:01> [02][101101][26.000000][1][A]
[2026-08-08 04:11:09.592 UTC] [V] SummDat SetVrmValue dev_id:7 val:2600.000000 sc:3
[2026-08-08 04:11:09.597 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101101, value:26.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.601 UTC] [V] 485DevCtl <C2:01> [03][101100][6574.000000][1][V]
[2026-08-08 04:11:09.603 UTC] [V] SummDat SetVrmValue dev_id:7 val:657400.000000 sc:3
[2026-08-08 04:11:09.608 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101100, value:6574.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.608 UTC] [V] 485DevCtl <C2:01> [03][101101][24.000000][1][A]
[2026-08-08 04:11:09.609 UTC] [V] SummDat SetVrmValue dev_id:7 val:2400.000000 sc:3
[2026-08-08 04:11:09.609 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101101, value:24.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.609 UTC] [V] 485DevCtl <C2:01> [01][101102][10191.000000][0][W]
[2026-08-08 04:11:09.609 UTC] [V] SummDat SetVrmValue dev_id:7 val:10191000.000000 sc:3
[2026-08-08 04:11:09.610 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101102, value:10191.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:09.610 UTC] [V] 485DevCtl <C2:01> [01][111200][4280.000000][1][V]
[2026-08-08 04:11:09.610 UTC] [V] SummDat SetVrmValue dev_id:7 val:428000.000000 sc:3
[2026-08-08 04:11:09.610 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111200, value:4280.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.610 UTC] [V] 485DevCtl <C2:01> [02][111200][4288.000000][1][V]
[2026-08-08 04:11:09.610 UTC] [V] SummDat SetVrmValue dev_id:7 val:428800.000000 sc:3
[2026-08-08 04:11:09.611 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111200, value:4288.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.611 UTC] [V] 485DevCtl <C2:01> [03][111200][4313.000000][1][V]
[2026-08-08 04:11:09.611 UTC] [V] SummDat SetVrmValue dev_id:7 val:431300.000000 sc:3
[2026-08-08 04:11:09.611 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111200, value:4313.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.611 UTC] [V] 485DevCtl <C2:01> [01][111201][138.000000][1][A]
[2026-08-08 04:11:09.612 UTC] [V] SummDat SetVrmValue dev_id:7 val:13800.000000 sc:3
[2026-08-08 04:11:09.630 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111201, value:138.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.634 UTC] [V] 485DevCtl <C2:01> [02][111201][137.000000][1][A]
[2026-08-08 04:11:09.636 UTC] [V] SummDat SetVrmValue dev_id:7 val:13700.000000 sc:3
[2026-08-08 04:11:09.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.639 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.641 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017942, monitor_cnt:50, bc_elapsed:3017942, min:10, max:40
[2026-08-08 04:11:09.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:09.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:09.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:09.642 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:09.643 UTC] [D] 485AcReq <C3:01> PutOStream [2][0c0000010000000601042751005e]
[2026-08-08 04:11:09.649 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111201, value:137.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.657 UTC] [V] 485DevCtl <C2:01> [03][111201][138.000000][1][A]
[2026-08-08 04:11:09.659 UTC] [V] SummDat SetVrmValue dev_id:7 val:13800.000000 sc:3
[2026-08-08 04:11:09.660 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111201, value:138.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.660 UTC] [V] 485DevCtl <C2:01> [01][111202][10038.000000][0][W]
[2026-08-08 04:11:09.660 UTC] [V] SummDat SetVrmValue dev_id:7 val:10038000.000000 sc:3
[2026-08-08 04:11:09.660 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111202, value:10038.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:09.677 UTC] [V] 485DevCtl <C2:01> [01][111203][1648.000000][0][var]
[2026-08-08 04:11:09.678 UTC] [V] SummDat SetVrmValue dev_id:7 val:1648000.000000 sc:3
[2026-08-08 04:11:09.680 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111203, value:1648.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:09.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:09.693 UTC] [V] 485DevCtl <C2:01> [01][121007][987.000000][3][]
[2026-08-08 04:11:09.698 UTC] [V] SummDat SetVrmValue dev_id:7 val:987.000000 sc:3
[2026-08-08 04:11:09.699 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121007, value:987.000000, scaleFactor:3, devId:7
[2026-08-08 04:11:09.699 UTC] [V] 485DevCtl <C2:01> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:09.699 UTC] [V] SummDat SetVrmValue dev_id:7 val:60000.000000 sc:3
[2026-08-08 04:11:09.700 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:09.721 UTC] [V] 485DevCtl <C2:01> [01][114202][64671.000000][0][kWh]
[2026-08-08 04:11:09.721 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671000.000000 sc:3
[2026-08-08 04:11:09.721 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:114202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:09.722 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:09.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.738 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.741 UTC] [V] 485DevCtl <C2:01> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:09.741 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:09.820 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017944, monitor_cnt:57, bc_elapsed:3017944, min:10, max:40
[2026-08-08 04:11:09.821 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:09.821 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:09.822 UTC] [D] 485AcReq <C2:02> PutOStream [1][08000204138a0024d54c]
[2026-08-08 04:11:09.830 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301789 UPRstat:0
[2026-08-08 04:11:09.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.838 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.858 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[197] [0001000000bf0104bc0000ffffffffffff016400000000001000000000000000000000000000000000000000ae0032009a0000000100010001ffffffffffffffffffffffffffffffffffffffff000100000001000000010000ffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffff000101f40000ff7dffff0000000003e89ddc00009126000002210000001b0000]
[2026-08-08 04:11:09.867 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [2] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:09.867 UTC] [V] 485DevCtl <C3:01> [02][753049][0.000000][0][]
[2026-08-08 04:11:09.867 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:09.868 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:02, valueId:753049, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.868 UTC] [V] 485DevCtl <C3:01> [01][753040][16.000000][0][]
[2026-08-08 04:11:09.868 UTC] [V] SummDat SetVrmValue dev_id:9 val:16.000000 sc:0
[2026-08-08 04:11:09.868 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753040, value:16.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.869 UTC] [V] 485DevCtl <C3:01> [01][753053][0.000000][0][]
[2026-08-08 04:11:09.869 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:09.878 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.881 UTC] [V] 485DevCtl <C3:01> [02][753053][0.000000][0][]
[2026-08-08 04:11:09.883 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:09.893 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:02, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.904 UTC] [V] 485DevCtl <C3:01> [03][753053][0.000000][0][]
[2026-08-08 04:11:09.904 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:09.905 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:03, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.905 UTC] [V] 485DevCtl <C3:01> [04][753053][0.000000][0][]
[2026-08-08 04:11:09.905 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:09.905 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:04, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.906 UTC] [V] 485DevCtl <C3:01> [01][716202][500.000000][1][kW]
[2026-08-08 04:11:09.906 UTC] [V] SummDat SetVrmValue dev_id:9 val:50000.000000 sc:3
[2026-08-08 04:11:09.906 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:716202, value:500.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:09.915 UTC] [V] 485DevCtl <C3:01> [01][711102][-131.000000][1][kW]
[2026-08-08 04:11:09.918 UTC] [V] SummDat SetVrmValue dev_id:9 val:-13100.000000 sc:3
[2026-08-08 04:11:09.926 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:711102, value:-131.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:09.937 UTC] [V] 485DevCtl <C3:01> [01][703102][40412.000000][0][kWh]
[2026-08-08 04:11:09.937 UTC] [V] SummDat SetVrmValue dev_id:9 val:40412.000000 sc:0
[2026-08-08 04:11:09.937 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:703102, value:40412.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.938 UTC] [V] 485DevCtl <C3:01> [01][713102][37158.000000][0][kWh]
[2026-08-08 04:11:09.938 UTC] [V] SummDat SetVrmValue dev_id:9 val:37158.000000 sc:0
[2026-08-08 04:11:09.938 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:713102, value:37158.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:09.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:09.939 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:09.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:09.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5800.300000 = p_th_old_:5810.200000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:09.940 UTC] [V] OFSCtrl CHG 21 batt_w:-13308.193173 = old:-13242.649673 +  kp:0.550000 * e:-118.450000 + ki:0.000000 * sume:9376808.400239 + kd:0.040000 * (e:-118.450000 - e1:-108.550000)
[2026-08-08 04:11:09.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13308.193173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:09.940 UTC] [V] OFSCtrl CHG 29 q:-134.000000, mod(round):1.000000
[2026-08-08 04:11:09.940 UTC] [D] OFSCtrl battery ctrl val:-26.600000
[2026-08-08 04:11:09.940 UTC] [V] 485ChCtl <C3> battery limit on [-133.000000,] request.
[2026-08-08 04:11:09.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:09.938 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:09.963 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:09.965 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:10.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.038 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:10.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:10.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-133] set rate[-26.600000] value100[500] value-100[-500]
[2026-08-08 04:11:10.044 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff7b]
[2026-08-08 04:11:10.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.138 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:10.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301789 UPRstat:0
[2026-08-08 04:11:10.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:10.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:10.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:10.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:10.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:10.233 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:10.236 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[77] [02044801ae0229000117190000019528d600001a23000e18aa00241a1900102828000010c210be10e7008e008d008effffffffffffffffffffffff278e0000067d000003db0258267a82005185]
[2026-08-08 04:11:10.236 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:10.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:10.236 UTC] [V] 485DevCtl <C2:02> [01][115202][430.000000][1][kWh]
[2026-08-08 04:11:10.241 UTC] [V] SummDat SetVrmValue dev_id:8 val:430.000000 sc:1
[2026-08-08 04:11:10.244 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:115202, value:430.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.249 UTC] [V] 485DevCtl <C2:02> [01][113202][66089.000000][0][kWh]
[2026-08-08 04:11:10.250 UTC] [V] SummDat SetVrmValue dev_id:8 val:66089.000000 sc:0
[2026-08-08 04:11:10.254 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:113202, value:66089.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:10.257 UTC] [V] 485DevCtl <C2:02> [01][121005][405.000000][1][℃]
[2026-08-08 04:11:10.257 UTC] [V] SummDat SetVrmValue dev_id:8 val:40500.000000 sc:3
[2026-08-08 04:11:10.257 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121005, value:405.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.261 UTC] [V] 485DevCtl <C2:02> [01][101100][6691.000000][1][V]
[2026-08-08 04:11:10.263 UTC] [V] SummDat SetVrmValue dev_id:8 val:669100.000000 sc:3
[2026-08-08 04:11:10.266 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101100, value:6691.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.271 UTC] [V] 485DevCtl <C2:02> [01][101101][14.000000][1][A]
[2026-08-08 04:11:10.273 UTC] [V] SummDat SetVrmValue dev_id:8 val:1400.000000 sc:3
[2026-08-08 04:11:10.278 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101101, value:14.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.282 UTC] [V] 485DevCtl <C2:02> [02][101100][6314.000000][1][V]
[2026-08-08 04:11:10.282 UTC] [V] SummDat SetVrmValue dev_id:8 val:631400.000000 sc:3
[2026-08-08 04:11:10.282 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101100, value:6314.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.283 UTC] [V] 485DevCtl <C2:02> [02][101101][36.000000][1][A]
[2026-08-08 04:11:10.283 UTC] [V] SummDat SetVrmValue dev_id:8 val:3600.000000 sc:3
[2026-08-08 04:11:10.283 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101101, value:36.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.283 UTC] [V] 485DevCtl <C2:02> [03][101100][6681.000000][1][V]
[2026-08-08 04:11:10.283 UTC] [V] SummDat SetVrmValue dev_id:8 val:668100.000000 sc:3
[2026-08-08 04:11:10.284 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101100, value:6681.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.284 UTC] [V] 485DevCtl <C2:02> [03][101101][16.000000][1][A]
[2026-08-08 04:11:10.284 UTC] [V] SummDat SetVrmValue dev_id:8 val:1600.000000 sc:3
[2026-08-08 04:11:10.284 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101101, value:16.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.284 UTC] [V] 485DevCtl <C2:02> [01][101102][10280.000000][0][W]
[2026-08-08 04:11:10.285 UTC] [V] SummDat SetVrmValue dev_id:8 val:10280000.000000 sc:3
[2026-08-08 04:11:10.285 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101102, value:10280.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:10.285 UTC] [V] 485DevCtl <C2:02> [01][111200][4290.000000][1][V]
[2026-08-08 04:11:10.285 UTC] [V] SummDat SetVrmValue dev_id:8 val:429000.000000 sc:3
[2026-08-08 04:11:10.304 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111200, value:4290.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.308 UTC] [V] 485DevCtl <C2:02> [02][111200][4286.000000][1][V]
[2026-08-08 04:11:10.310 UTC] [V] SummDat SetVrmValue dev_id:8 val:428600.000000 sc:3
[2026-08-08 04:11:10.316 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111200, value:4286.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.319 UTC] [V] 485DevCtl <C2:02> [03][111200][4327.000000][1][V]
[2026-08-08 04:11:10.321 UTC] [V] SummDat SetVrmValue dev_id:8 val:432700.000000 sc:3
[2026-08-08 04:11:10.325 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111200, value:4327.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.325 UTC] [V] 485DevCtl <C2:02> [01][111201][142.000000][1][A]
[2026-08-08 04:11:10.332 UTC] [V] SummDat SetVrmValue dev_id:8 val:14200.000000 sc:3
[2026-08-08 04:11:10.333 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111201, value:142.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.334 UTC] [V] 485DevCtl <C2:02> [02][111201][141.000000][1][A]
[2026-08-08 04:11:10.334 UTC] [V] SummDat SetVrmValue dev_id:8 val:14100.000000 sc:3
[2026-08-08 04:11:10.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.338 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:10.338 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111201, value:141.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.340 UTC] [V] 485DevCtl <C2:02> [03][111201][142.000000][1][A]
[2026-08-08 04:11:10.341 UTC] [V] SummDat SetVrmValue dev_id:8 val:14200.000000 sc:3
[2026-08-08 04:11:10.344 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111201, value:142.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.347 UTC] [V] 485DevCtl <C2:02> [01][111202][10126.000000][0][W]
[2026-08-08 04:11:10.348 UTC] [V] SummDat SetVrmValue dev_id:8 val:10126000.000000 sc:3
[2026-08-08 04:11:10.350 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111202, value:10126.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:10.352 UTC] [V] 485DevCtl <C2:02> [01][111203][1661.000000][0][var]
[2026-08-08 04:11:10.353 UTC] [V] SummDat SetVrmValue dev_id:8 val:1661000.000000 sc:3
[2026-08-08 04:11:10.355 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111203, value:1661.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:10.359 UTC] [V] 485DevCtl <C2:02> [01][121007][987.000000][3][]
[2026-08-08 04:11:10.361 UTC] [V] SummDat SetVrmValue dev_id:8 val:987.000000 sc:3
[2026-08-08 04:11:10.369 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121007, value:987.000000, scaleFactor:3, devId:8
[2026-08-08 04:11:10.376 UTC] [V] 485DevCtl <C2:02> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:10.386 UTC] [V] SummDat SetVrmValue dev_id:8 val:60000.000000 sc:3
[2026-08-08 04:11:10.391 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:10.397 UTC] [V] 485DevCtl <C2:02> [01][114202][66089.000000][0][kWh]
[2026-08-08 04:11:10.398 UTC] [V] SummDat SetVrmValue dev_id:8 val:66089000.000000 sc:3
[2026-08-08 04:11:10.399 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:114202, value:66089.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:10.400 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:10.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:10.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:10.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:10.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:10.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:10.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:10.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:10.419 UTC] [V] 485DevCtl <C2:02> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:10.424 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:10.432 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:10.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.438 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:10.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:10.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:10.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:10.737 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301791 UPRstat:0
[2026-08-08 04:11:10.738 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:10.738 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040408210223e957]
[2026-08-08 04:11:10.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:10.738 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:10.740 UTC] [V] OFSCtrl Rcv set flux_of_solar:208.100000
[2026-08-08 04:11:10.740 UTC] [V] 485DevCtl <C1:01> [01][401006][2081.000000][1][W/m2]
[2026-08-08 04:11:10.740 UTC] [V] SummDat SetVrmValue dev_id:1 val:208100.000000 sc:3
[2026-08-08 04:11:10.740 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2081.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:10.741 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:10.742 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:10.746 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:10.746 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:10.746 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:10.767 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:10.769 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:10.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:10.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:10.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:10.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:10.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:10.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:10.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:10.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.839 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:10.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:10.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:10.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:10.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5790.400000 = p_th_old_:5800.300000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:10.940 UTC] [V] OFSCtrl CHG 21 batt_w:-13298.056673 = old:-13308.193173 +  kp:0.550000 * e:9.150000 + ki:0.000000 * sume:9376817.550239 + kd:0.040000 * (e:9.150000 - e1:-118.450000)
[2026-08-08 04:11:10.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13298.056673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:10.940 UTC] [V] OFSCtrl CHG 29 q:-133.000000, mod(round):0.000000
[2026-08-08 04:11:10.940 UTC] [D] OFSCtrl battery ctrl val:-26.600000
[2026-08-08 04:11:10.941 UTC] [V] 485ChCtl <C3> battery limit on [-133.000000,] request.
[2026-08-08 04:11:10.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:11.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.038 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:11.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-133] set rate[-26.600000] value100[500] value-100[-500]
[2026-08-08 04:11:11.044 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff7b]
[2026-08-08 04:11:11.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.138 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301790 UPRstat:0
[2026-08-08 04:11:11.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:11.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:11.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:11.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:11.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:11.210 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301790 UPRstat:0
[2026-08-08 04:11:11.210 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:11.211 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [040328000061f8000062b7000056bf00000051000002580001014b00000292ffff4979fffffe2d001216847b95]
[2026-08-08 04:11:11.212 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:11.212 UTC] [V] OFSCtrl Rcv set p_co:6580.000000, p_co_old:6660.000000
[2026-08-08 04:11:11.213 UTC] [V] 485DevCtl <C1:04> [01][601260][658.000000][2][kW]
[2026-08-08 04:11:11.214 UTC] [V] SummDat SetVrmValue dev_id:4 val:6580.000000 sc:3
[2026-08-08 04:11:11.214 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:658.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:11.215 UTC] [V] 485DevCtl <C1:04> [01][603260][1185412.000000][1][kWh]
[2026-08-08 04:11:11.215 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185412.000000 sc:1
[2026-08-08 04:11:11.215 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185412.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:11.215 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:11.215 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:11.216 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:11.216 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:11.216 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:11.216 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6580.000000
[2026-08-08 04:11:11.233 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:208.100000 < rad_th:80.000000
[2026-08-08 04:11:11.237 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301828:6580.000000
[2026-08-08 04:11:11.237 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:11.238 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:11.238 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:11.238 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:11.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.250 UTC] [D] OFSCtrl pv-pcs ctrl val:21.118458 old:20.618458
[2026-08-08 04:11:11.252 UTC] [V] OCHisDB set rate:21 t_rate:270 cnt:14
[2026-08-08 04:11:11.253 UTC] [V] 485ChCtl <C2> pv-pcs limit on [21.118458] request.
[2026-08-08 04:11:11.253 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:11.254 UTC] [V] OFSCtrl Nod calc proc start.
[2026-08-08 04:11:11.271 UTC] [V] OFSCtrl ProcNodCountCalculation cur:301828 >= next:301878 diff:-50
[2026-08-08 04:11:11.272 UTC] [V] OFSCtrl ProcNodCountCalculation time not reached:-50
[2026-08-08 04:11:11.272 UTC] [V] OFSCtrl update p_co_old:6580.000000
[2026-08-08 04:11:11.272 UTC] [V] OFSCtrl Nod calc proc:
[2026-08-08 04:11:11.274 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:11.277 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:11.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:11.321 UTC] [D] VarInf update ofs_rate:21.118458
[2026-08-08 04:11:11.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:11.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:11.321 UTC] [D] VarInf update ofs_rate:21.118458
[2026-08-08 04:11:11.321 UTC] [D] VarInf Limit setRate[211.184570] rate[21.118458] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:11.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:21.118458 set_rate211
[2026-08-08 04:11:11.321 UTC] [D] VarInf Limit rt[2] int_set_rate[211] server_rate[21.118458] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:11.323 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00d3c632]
[2026-08-08 04:11:11.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.611 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:11.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.689 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:11 val:6580.000000
[2026-08-08 04:11:11.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:11' , 6580.000000 , 0  )
[2026-08-08 04:11:11.711 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:11.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.738 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:11.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.839 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:11.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:11.939 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:11.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:11.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5780.500000 = p_th_old_:5790.400000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:11.940 UTC] [V] OFSCtrl CHG 21 batt_w:-13461.115173 = old:-13298.056673 +  kp:0.550000 * e:-275.750000 + ki:0.000000 * sume:9376541.800239 + kd:0.040000 * (e:-275.750000 - e1:9.150000)
[2026-08-08 04:11:11.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13461.115173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:11.941 UTC] [V] OFSCtrl CHG 29 q:-135.000000, mod(round):0.000000
[2026-08-08 04:11:11.941 UTC] [D] OFSCtrl battery ctrl val:-26.900000
[2026-08-08 04:11:11.941 UTC] [V] 485ChCtl <C3> battery limit on [-135.000000,] request.
[2026-08-08 04:11:11.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:12.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.039 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:12.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:12.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-135] set rate[-27.000000] value100[500] value-100[-500]
[2026-08-08 04:11:12.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff79]
[2026-08-08 04:11:12.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.139 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:12.218 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301791 UPRstat:0
[2026-08-08 04:11:12.221 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:12.221 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:12.222 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:12.222 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:12.223 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:12.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.239 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:12.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1182->1182] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.338 UTC] [V] OFSCtrl angif value:1182 power_val_:6262.500000
[2026-08-08 04:11:12.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.438 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:12.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.539 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:12.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.639 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:12.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:12.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.739 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:12.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.839 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:12.941 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:12.941 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:12.941 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:12.941 UTC] [V] OFSCtrl CHG 20 p_th(t):5770.600000 = p_th_old_:5780.500000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:12.944 UTC] [V] OFSCtrl CHG 21 batt_w:-13659.181173 = old:-13461.115173 +  kp:0.550000 * e:-354.400000 + ki:0.000000 * sume:9376187.400239 + kd:0.040000 * (e:-354.400000 - e1:-275.750000)
[2026-08-08 04:11:12.944 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13659.181173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:12.945 UTC] [V] OFSCtrl CHG 29 q:-137.000000, mod(round):0.000000
[2026-08-08 04:11:12.946 UTC] [D] OFSCtrl battery ctrl val:-27.300000
[2026-08-08 04:11:12.947 UTC] [V] 485ChCtl <C3> battery limit on [-137.000000,] request.
[2026-08-08 04:11:12.948 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:13.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.039 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:13.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:13.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-137] set rate[-27.400000] value100[500] value-100[-500]
[2026-08-08 04:11:13.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff77]
[2026-08-08 04:11:13.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.139 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:13.208 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301792 UPRstat:0
[2026-08-08 04:11:13.209 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:13.210 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:13.210 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:13.211 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:13.211 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:13.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.238 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:13.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.338 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:13.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.439 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:13.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.539 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:13.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:13.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:13.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.739 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:13.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.838 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:13.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:13.938 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:13.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:13.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5760.700000 = p_th_old_:5770.600000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:13.939 UTC] [V] OFSCtrl CHG 21 batt_w:-13738.254673 = old:-13659.181173 +  kp:0.550000 * e:-158.050000 + ki:0.000000 * sume:9376029.350239 + kd:0.040000 * (e:-158.050000 - e1:-354.400000)
[2026-08-08 04:11:13.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13738.254673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:13.940 UTC] [V] OFSCtrl CHG 29 q:-138.000000, mod(round):1.000000
[2026-08-08 04:11:13.940 UTC] [D] OFSCtrl battery ctrl val:-27.500000
[2026-08-08 04:11:13.940 UTC] [V] 485ChCtl <C3> battery limit on [-137.000000,] request.
[2026-08-08 04:11:13.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:13.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-137] set rate[-27.400000] value100[500] value-100[-500]
[2026-08-08 04:11:13.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff77]
[2026-08-08 04:11:13.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:14.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.038 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301793 UPRstat:0
[2026-08-08 04:11:14.100 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:14.100 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:14.100 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:14.100 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:14.101 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:14.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.138 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.339 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.439 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.539 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:14.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:14.640 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017992, monitor_cnt:50, bc_elapsed:3017992, min:10, max:40
[2026-08-08 04:11:14.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:14.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:14.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :3
[2026-08-08 04:11:14.642 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:14.643 UTC] [D] 485AcReq <C3:01> PutOStream [3][0c00000100000006010435260018]
[2026-08-08 04:11:14.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:14.740 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.740 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.768 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301794 UPRstat:0
[2026-08-08 04:11:14.770 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[57] [0001000000330104301f3f00a4026203e81f3f026200010001ffff8000ffff013b013bffff008c008c00640064ffff821e81ce013601220045]
[2026-08-08 04:11:14.770 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [3] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:14.770 UTC] [V] 485DevCtl <C3:01> [01][721100][7999.000000][1][V]
[2026-08-08 04:11:14.770 UTC] [V] SummDat SetVrmValue dev_id:9 val:799900.000000 sc:3
[2026-08-08 04:11:14.771 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721100, value:7999.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:14.771 UTC] [V] 485DevCtl <C3:01> [01][721101][164.000000][1][A]
[2026-08-08 04:11:14.771 UTC] [V] SummDat SetVrmValue dev_id:9 val:16400.000000 sc:3
[2026-08-08 04:11:14.771 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721101, value:164.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:14.772 UTC] [V] OFSCtrl change set SOC(t):61.000000 drive cnt:1
[2026-08-08 04:11:14.792 UTC] [V] OFSCtrl Rcv set soc[0301]:61.000000
[2026-08-08 04:11:14.792 UTC] [V] 485DevCtl <C3:01> [01][721035][610.000000][1][%]
[2026-08-08 04:11:14.793 UTC] [V] SummDat SetVrmValue dev_id:9 val:61000.000000 sc:3
[2026-08-08 04:11:14.793 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721035, value:610.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:14.793 UTC] [V] 485DevCtl <C3:01> [01][721036][1000.000000][1][%]
[2026-08-08 04:11:14.793 UTC] [V] SummDat SetVrmValue dev_id:9 val:100000.000000 sc:3
[2026-08-08 04:11:14.794 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721036, value:1000.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:14.794 UTC] [V] 485DevCtl <C3:01> [01][721030][33310.000000][4][V]
[2026-08-08 04:11:14.794 UTC] [V] SummDat SetVrmValue dev_id:9 val:3331.000000 sc:3
[2026-08-08 04:11:14.794 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721030, value:33310.000000, scaleFactor:4, devId:9
[2026-08-08 04:11:14.795 UTC] [V] 485DevCtl <C3:01> [01][721031][33230.000000][4][V]
[2026-08-08 04:11:14.820 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017994, monitor_cnt:50, bc_elapsed:3017994, min:10, max:40
[2026-08-08 04:11:14.820 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:14.821 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:14.821 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:14.822 UTC] [D] 485AcReq <C2:01> PutOStream [2][0800010413d80002f574]
[2026-08-08 04:11:14.795 UTC] [V] SummDat SetVrmValue dev_id:9 val:3323.000000 sc:3
[2026-08-08 04:11:14.834 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721031, value:33230.000000, scaleFactor:4, devId:9
[2026-08-08 04:11:14.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.839 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.842 UTC] [V] 485DevCtl <C3:01> [01][721032][310.000000][1][℃]
[2026-08-08 04:11:14.842 UTC] [V] SummDat SetVrmValue dev_id:9 val:31000.000000 sc:3
[2026-08-08 04:11:14.843 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721032, value:310.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:14.843 UTC] [V] 485DevCtl <C3:01> [01][721033][290.000000][1][℃]
[2026-08-08 04:11:14.843 UTC] [V] SummDat SetVrmValue dev_id:9 val:29000.000000 sc:3
[2026-08-08 04:11:14.843 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721033, value:290.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:14.844 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:14.845 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:14.879 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:14.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:14.938 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:14.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:14.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5750.800000 = p_th_old_:5760.700000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:14.939 UTC] [V] OFSCtrl CHG 21 batt_w:-13831.023173 = old:-13738.254673 +  kp:0.550000 * e:-167.950000 + ki:0.000000 * sume:9375861.400239 + kd:0.040000 * (e:-167.950000 - e1:-158.050000)
[2026-08-08 04:11:14.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13831.023173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:14.939 UTC] [V] OFSCtrl CHG 29 q:-139.000000, mod(round):1.000000
[2026-08-08 04:11:14.940 UTC] [D] OFSCtrl battery ctrl val:-27.700000
[2026-08-08 04:11:14.940 UTC] [V] 485ChCtl <C3> battery limit on [-138.000000,] request.
[2026-08-08 04:11:14.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:14.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:14.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-138] set rate[-27.600000] value100[500] value-100[-500]
[2026-08-08 04:11:14.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff76]
[2026-08-08 04:11:15.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.039 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:15.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301794 UPRstat:0
[2026-08-08 04:11:15.100 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:15.100 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:15.101 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:15.101 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:15.101 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:15.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.139 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:15.147 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[9] [010404100000027e85]
[2026-08-08 04:11:15.147 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [2] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:15.148 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:15.148 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounter value0
[2026-08-08 04:11:15.148 UTC] [V] 485DevCtl <C2:01> ExecuteAction set start cnt:0
[2026-08-08 04:11:15.148 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:11:15.149 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:15.221 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3017998, monitor_cnt:54, bc_elapsed:3017998, min:10, max:40
[2026-08-08 04:11:15.221 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:15.221 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:15.222 UTC] [D] 485AcReq <C2:02> PutOStream [2][0800020413d80002f547]
[2026-08-08 04:11:15.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:15.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.338 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:15.386 UTC] [V] OC485DevMgr TargetPowerPolling 
[2026-08-08 04:11:15.387 UTC] [V] OC485DevMgr TargetPowerPolling Target power no ud current[20260808040000]now[20260808041115]next[20260808043000]
[2026-08-08 04:11:15.387 UTC] [V] OCMgr UpdateExtCurrentTarget call
[2026-08-08 04:11:15.387 UTC] [V] OCMgr UpdateExtSchedule call
[2026-08-08 04:11:15.387 UTC] [V] OCMgr UpdateExtSchedule file none. ext rate:-1, time:20200101000000
[2026-08-08 04:11:15.387 UTC] [V] OCMgr IsPvocdScheduleError 0
[2026-08-08 04:11:15.388 UTC] [V] OCMgr UpdateExtCurrentTarget check schedule:0, ext rate:-1
[2026-08-08 04:11:15.388 UTC] [V] OCMgr CalcOutputControlPower pow:99.000000, rate:100, cap:99.000000
[2026-08-08 04:11:15.388 UTC] [V] OCMgr IsPvocdScheduleError 0
[2026-08-08 04:11:15.388 UTC] [D] OCMgr UpdateExtCurrentTarget external none, in_pow:99.000000, 99.000000
[2026-08-08 04:11:15.389 UTC] [V] OCMgr CalcOutputControlRate rate:100, pow:99.000000, cap:99.000000, rate_out:99.000000
[2026-08-08 04:11:15.389 UTC] [V] OCMgr WriteExtSchedule dat:100,20260808133000
[2026-08-08 04:11:15.390 UTC] [V] FlUtil write csv file[/media/sdcard/solajithome/Log/modbus/ExecSchedulePath/ExecEmsSchedule.csv] result:1
[2026-08-08 04:11:15.390 UTC] [V] OCMgr now time:20260808040000, power_value:99.000000, rt:0
[2026-08-08 04:11:15.390 UTC] [V] OCMgr next time:20260808043000, power_value:99.000000, rt:0
[2026-08-08 04:11:15.391 UTC] [V] OCMgr GetCurrentTargetPower current target:99.000000
[2026-08-08 04:11:15.391 UTC] [V] OCMgr CalcOutputControlRate rate:100, pow:99.000000, cap:99.000000, rate_out:99.000000
[2026-08-08 04:11:15.391 UTC] [V] OCMgr IsPvocdCommunication 1
[2026-08-08 04:11:15.391 UTC] [V] OCMgr IsPvocdScheduleError 0
[2026-08-08 04:11:15.391 UTC] [V] OCMgr UpdateActiveMode mode:OFS conditions:output rate 100.
[2026-08-08 04:11:15.391 UTC] [V] LgMgr change mode OFS -> OFS
[2026-08-08 04:11:15.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:15.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:15.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:15.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:15.405 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:15.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:15.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:15.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.438 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:15.444 UTC] [I] ErrDatRSndMgr Send unsent err dat start.
[2026-08-08 04:11:15.448 UTC] [D] SLDatInf GetUnsentDataFromDateList select:SELECT time, errorLevel, physicalId, errorCode, errorDetail, sent, deviceName, deviceNumber FROM status_log WHERE time BETWEEN '2026-08-06 00:00:00' AND '2026-08-08 04:06:15' AND sent=0  ORDER BY time ASC 
[2026-08-08 04:11:15.476 UTC] [D] SLDatInf GetUnsentDataFromDateList select:SELECT time, errorLevel, physicalId, errorCode, errorDetail, sent, deviceName, deviceNumber FROM status_log WHERE time BETWEEN '2026-08-06 00:00:00' AND '2026-08-08 04:06:15' AND sent=0  ORDER BY time ASC 
[2026-08-08 04:11:15.509 UTC] [V] LMgr FlushLoggerLog
[2026-08-08 04:11:15.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:15.552 UTC] [I] Wdog command:/usr/bin/touch "/mnt/system/check/pvsl"
[2026-08-08 04:11:15.604 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[9] [020404100000024d85]
[2026-08-08 04:11:15.605 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [2] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:15.621 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:15.629 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounter value0
[2026-08-08 04:11:15.636 UTC] [V] 485DevCtl <C2:02> ExecuteAction set start cnt:0
[2026-08-08 04:11:15.636 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:11:15.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:15.646 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:15.647 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:15.691 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:15.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.738 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:15.741 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301796 UPRstat:0
[2026-08-08 04:11:15.742 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:15.743 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [010404081702230959]
[2026-08-08 04:11:15.744 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:15.744 UTC] [V] OFSCtrl Rcv set flux_of_solar:207.100000
[2026-08-08 04:11:15.744 UTC] [V] 485DevCtl <C1:01> [01][401006][2071.000000][1][W/m2]
[2026-08-08 04:11:15.744 UTC] [V] SummDat SetVrmValue dev_id:1 val:207100.000000 sc:3
[2026-08-08 04:11:15.745 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2071.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:15.745 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:15.745 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:15.746 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:15.746 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:15.746 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:15.759 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:15.769 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:15.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:15.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:15.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:15.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:15.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:15.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:15.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:15.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:15.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:15.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:15.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:15.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5740.900000 = p_th_old_:5750.800000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:15.940 UTC] [V] OFSCtrl CHG 21 batt_w:-13848.111673 = old:-13831.023173 +  kp:0.550000 * e:-40.350000 + ki:0.000000 * sume:9375821.050239 + kd:0.040000 * (e:-40.350000 - e1:-167.950000)
[2026-08-08 04:11:15.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13848.111673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:15.941 UTC] [V] OFSCtrl CHG 29 q:-139.000000, mod(round):1.000000
[2026-08-08 04:11:15.941 UTC] [D] OFSCtrl battery ctrl val:-27.700000
[2026-08-08 04:11:15.943 UTC] [V] 485ChCtl <C3> battery limit on [-138.000000,] request.
[2026-08-08 04:11:15.945 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:16.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.038 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:16.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-138] set rate[-27.600000] value100[500] value-100[-500]
[2026-08-08 04:11:16.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff76]
[2026-08-08 04:11:16.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301795 UPRstat:0
[2026-08-08 04:11:16.189 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:16.192 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:16.192 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:16.193 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:16.196 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:16.203 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301795 UPRstat:0
[2026-08-08 04:11:16.203 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:16.205 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [040328000061b0000062630000567300000051000002580000ffdb0000028effff4990fffffe2d0012168419e0]
[2026-08-08 04:11:16.205 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:16.205 UTC] [V] OFSCtrl Rcv set p_co:6540.000000, p_co_old:6580.000000
[2026-08-08 04:11:16.205 UTC] [V] 485DevCtl <C1:04> [01][601260][654.000000][2][kW]
[2026-08-08 04:11:16.205 UTC] [V] SummDat SetVrmValue dev_id:4 val:6540.000000 sc:3
[2026-08-08 04:11:16.206 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:654.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:16.206 UTC] [V] 485DevCtl <C1:04> [01][603260][1185412.000000][1][kWh]
[2026-08-08 04:11:16.213 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185412.000000 sc:1
[2026-08-08 04:11:16.217 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185412.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:16.222 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:16.223 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:16.226 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:16.230 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:16.232 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:16.235 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6540.000000
[2026-08-08 04:11:16.236 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:207.100000 < rad_th:80.000000
[2026-08-08 04:11:16.236 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301833:6540.000000
[2026-08-08 04:11:16.236 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:16.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.236 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:16.252 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:16.253 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:16.253 UTC] [D] OFSCtrl pv-pcs ctrl val:21.362231 old:21.118458
[2026-08-08 04:11:16.253 UTC] [V] OCHisDB set rate:21 t_rate:291 cnt:15
[2026-08-08 04:11:16.253 UTC] [V] 485ChCtl <C2> pv-pcs limit on [21.362231] request.
[2026-08-08 04:11:16.253 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:16.254 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:16.257 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:16.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:16.321 UTC] [D] VarInf update ofs_rate:21.362230
[2026-08-08 04:11:16.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:16.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:16.321 UTC] [D] VarInf update ofs_rate:21.362230
[2026-08-08 04:11:16.321 UTC] [D] VarInf Limit setRate[213.622299] rate[21.362230] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:16.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:21.362230 set_rate214
[2026-08-08 04:11:16.322 UTC] [D] VarInf Limit rt[2] int_set_rate[214] server_rate[21.362230] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:16.323 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00d60631]
[2026-08-08 04:11:16.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.338 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.615 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:16.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:16.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:16 val:6540.000000
[2026-08-08 04:11:16.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:16' , 6540.000000 , 0  )
[2026-08-08 04:11:16.711 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:16.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.739 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:16.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.838 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:16.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:16.938 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:16.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:16.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5731.000000 = p_th_old_:5740.900000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:16.940 UTC] [V] OFSCtrl CHG 21 batt_w:-13997.832673 = old:-13848.111673 +  kp:0.550000 * e:-256.500000 + ki:0.000000 * sume:9375564.550239 + kd:0.040000 * (e:-256.500000 - e1:-40.350000)
[2026-08-08 04:11:16.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:13997.832673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:16.940 UTC] [V] OFSCtrl CHG 29 q:-140.000000, mod(round):0.000000
[2026-08-08 04:11:16.940 UTC] [D] OFSCtrl battery ctrl val:-28.000000
[2026-08-08 04:11:16.941 UTC] [V] 485ChCtl <C3> battery limit on [-140.000000,] request.
[2026-08-08 04:11:16.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:17.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:17.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:17.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-140] set rate[-28.000000] value100[500] value-100[-500]
[2026-08-08 04:11:17.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff74]
[2026-08-08 04:11:17.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.139 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:17.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301796 UPRstat:0
[2026-08-08 04:11:17.189 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:17.190 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:17.191 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:17.191 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:17.191 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:17.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.239 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:17.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.339 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:17.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.438 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:17.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.538 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:17.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018022, monitor_cnt:100, bc_elapsed:22, min:10, max:40
[2026-08-08 04:11:17.604 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:17.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:17.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:17.704 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018023, monitor_cnt:101, bc_elapsed:23, min:10, max:40
[2026-08-08 04:11:17.704 UTC] [V] 485DevCtl <C1:02> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:17.704 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:17.705 UTC] [V] 485ChCtl <C1> send request:IMT01
[2026-08-08 04:11:17.706 UTC] [D] 485AcReq <C1:02> PutOStream [1][08000204000200019039]
[2026-08-08 04:11:17.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.739 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:17.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.839 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:17.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:17.939 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:17.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:17.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5721.100000 = p_th_old_:5731.000000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:17.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14104.186173 = old:-13997.832673 +  kp:0.550000 * e:-197.650000 + ki:0.000000 * sume:9375366.900239 + kd:0.040000 * (e:-197.650000 - e1:-256.500000)
[2026-08-08 04:11:17.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14104.186173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:17.941 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:17.941 UTC] [D] OFSCtrl battery ctrl val:-28.200000
[2026-08-08 04:11:17.942 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:17.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:18.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.040 UTC] [V] 485DevCtl <C1:02> AnalyzeResponseData proc restart cnt:301791 UPRstat:0
[2026-08-08 04:11:18.040 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:18.041 UTC] [D] 485DevCtl <C1:02> RcvDat status[2] len[7] [020402021cfd99]
[2026-08-08 04:11:18.041 UTC] [D] 485DevCtl <C1:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:18.041 UTC] [V] 485DevCtl <C1:02> [01][431005][290.000000][1][°C]
[2026-08-08 04:11:18.041 UTC] [V] SummDat SetVrmValue dev_id:2 val:29000.000000 sc:3
[2026-08-08 04:11:18.042 UTC] [V] OCMgr SetMeterValue PhId:0102, branchNo:01, valueId:431005, value:290.000000, scaleFactor:1, devId:2
[2026-08-08 04:11:18.042 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:18.043 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:18.045 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:18.048 UTC] [V] 485DevCtl <C1:02> device_type:
[2026-08-08 04:11:18.048 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:18.104 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018027, monitor_cnt:105, bc_elapsed:27, min:10, max:40
[2026-08-08 04:11:18.104 UTC] [V] 485DevCtl <C1:03> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:18.104 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:18.105 UTC] [V] 485ChCtl <C1> send request:omron03
[2026-08-08 04:11:18.106 UTC] [D] 485AcReq <C1:03> PutOStream [1][08000303000000144427]
[2026-08-08 04:11:18.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.138 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301797 UPRstat:0
[2026-08-08 04:11:18.202 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:18.203 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:18.204 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:18.204 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:18.207 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:18.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:18.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.339 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.439 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.494 UTC] [V] 485DevCtl <C1:03> AnalyzeResponseData proc restart cnt:301791 UPRstat:0
[2026-08-08 04:11:18.495 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:18.496 UTC] [D] 485DevCtl <C1:03> RcvDat status[2] len[45] [0303280000fc360000ff060000fe510000219f0000267500002d110000005e0000025800100b3a000029128f0d]
[2026-08-08 04:11:18.496 UTC] [D] 485DevCtl <C1:03> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:18.497 UTC] [V] 485DevCtl <C1:03> [01][301200][64566.000000][1][V]
[2026-08-08 04:11:18.497 UTC] [V] SummDat SetVrmValue dev_id:3 val:6456600.000000 sc:3
[2026-08-08 04:11:18.498 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301200, value:64566.000000, scaleFactor:1, devId:3
[2026-08-08 04:11:18.499 UTC] [V] 485DevCtl <C1:03> [01][301201][8607.000000][3][A]
[2026-08-08 04:11:18.499 UTC] [V] SummDat SetVrmValue dev_id:3 val:8607.000000 sc:3
[2026-08-08 04:11:18.499 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301201, value:8607.000000, scaleFactor:3, devId:3
[2026-08-08 04:11:18.500 UTC] [V] OFSCtrl Rcv set p_grid:105140.000000
[2026-08-08 04:11:18.500 UTC] [V] 485DevCtl <C1:03> [01][601202][10514.000000][2][kW]
[2026-08-08 04:11:18.500 UTC] [V] SummDat SetVrmValue dev_id:3 val:105140.000000 sc:3
[2026-08-08 04:11:18.500 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:601202, value:10514.000000, scaleFactor:2, devId:3
[2026-08-08 04:11:18.501 UTC] [V] 485DevCtl <C1:03> device_type:Grid-Meter
[2026-08-08 04:11:18.501 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:18.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.538 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018032, monitor_cnt:110, bc_elapsed:32, min:10, max:40
[2026-08-08 04:11:18.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.638 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:18.704 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018033, monitor_cnt:111, bc_elapsed:33, min:10, max:40
[2026-08-08 04:11:18.704 UTC] [V] 485DevCtl <C1:05> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:18.704 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:18.705 UTC] [V] 485ChCtl <C1> send request:omron04
[2026-08-08 04:11:18.706 UTC] [D] 485AcReq <C1:05> PutOStream [1][0800050300030014b441]
[2026-08-08 04:11:18.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.739 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.839 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:18.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:18.939 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:18.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:18.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5711.200000 = p_th_old_:5721.100000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:18.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14015.922173 = old:-14104.186173 +  kp:0.550000 * e:136.200000 + ki:0.000000 * sume:9375503.100239 + kd:0.040000 * (e:136.200000 - e1:-197.650000)
[2026-08-08 04:11:18.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14015.922173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:18.942 UTC] [V] OFSCtrl CHG 29 q:-141.000000, mod(round):1.000000
[2026-08-08 04:11:18.943 UTC] [D] OFSCtrl battery ctrl val:-28.000000
[2026-08-08 04:11:18.944 UTC] [V] 485ChCtl <C3> battery limit on [-140.000000,] request.
[2026-08-08 04:11:18.944 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:19.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.039 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:19.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:19.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-140] set rate[-28.000000] value100[500] value-100[-500]
[2026-08-08 04:11:19.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff74]
[2026-08-08 04:11:19.102 UTC] [V] 485DevCtl <C1:05> AnalyzeResponseData proc restart cnt:301791 UPRstat:0
[2026-08-08 04:11:19.102 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:19.104 UTC] [D] 485DevCtl <C1:05> RcvDat status[2] len[45] [0503280000eab30000f1cd0000e4f200000061000002580003235200000808ffff4f16fffffe3c001382b9df1d]
[2026-08-08 04:11:19.104 UTC] [D] 485DevCtl <C1:05> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:19.104 UTC] [V] OFSCtrl Rcv set p_pv:20560.000000
[2026-08-08 04:11:19.104 UTC] [V] 485DevCtl <C1:05> [01][601259][2056.000000][2][kW]
[2026-08-08 04:11:19.104 UTC] [V] SummDat SetVrmValue dev_id:5 val:20560.000000 sc:3
[2026-08-08 04:11:19.105 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:601259, value:2056.000000, scaleFactor:2, devId:5
[2026-08-08 04:11:19.110 UTC] [V] 485DevCtl <C1:05> [01][603259][1278649.000000][1][kWh]
[2026-08-08 04:11:19.113 UTC] [V] SummDat SetVrmValue dev_id:5 val:1278649.000000 sc:1
[2026-08-08 04:11:19.124 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:603259, value:1278649.000000, scaleFactor:1, devId:5
[2026-08-08 04:11:19.126 UTC] [V] 485DevCtl <C1:05> device_type:PV-Meter
[2026-08-08 04:11:19.127 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:19.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.138 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301798 UPRstat:0
[2026-08-08 04:11:19.189 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:19.190 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:19.190 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:19.191 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:19.191 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:19.204 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018038, monitor_cnt:116, bc_elapsed:38, min:10, max:40
[2026-08-08 04:11:19.204 UTC] [V] 485DevCtl <C1:06> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:19.204 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:19.205 UTC] [V] 485ChCtl <C1> send request:omron06
[2026-08-08 04:11:19.207 UTC] [D] 485AcReq <C1:06> PutOStream [2][08000603002000084471]
[2026-08-08 04:11:19.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.238 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.339 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.439 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.539 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.568 UTC] [V] 485DevCtl <C1:06> AnalyzeResponseData proc restart cnt:301792 UPRstat:0
[2026-08-08 04:11:19.569 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:19.571 UTC] [D] 485DevCtl <C1:06> RcvDat status[2] len[21] [06031000000000022dc23800000000029163b396a1]
[2026-08-08 04:11:19.572 UTC] [D] 485DevCtl <C1:06> ResCnd OperationId [2] IsNormal[1] 
[2026-08-08 04:11:19.575 UTC] [V] StructInfo Add 36553.272000 = 0.000000+36553.272000+0.000000
[2026-08-08 04:11:19.579 UTC] [V] 485DevCtl <C1:06> [01][603238][3655327.200000][2][kWh]
[2026-08-08 04:11:19.581 UTC] [V] SummDat SetVrmValue dev_id:6 val:3655327.200000 sc:2
[2026-08-08 04:11:19.587 UTC] [V] OCMgr SetMeterValue PhId:0106, branchNo:01, valueId:603238, value:3655327.200000, scaleFactor:2, devId:6
[2026-08-08 04:11:19.595 UTC] [V] StructInfo Add 43082.675000 = 0.000000+43082.675000+0.000000
[2026-08-08 04:11:19.600 UTC] [V] 485DevCtl <C1:06> [01][613239][4308267.500000][2][kWh]
[2026-08-08 04:11:19.601 UTC] [V] SummDat SetVrmValue dev_id:6 val:4308267.500000 sc:2
[2026-08-08 04:11:19.605 UTC] [V] OCMgr SetMeterValue PhId:0106, branchNo:01, valueId:613239, value:4308267.500000, scaleFactor:2, devId:6
[2026-08-08 04:11:19.608 UTC] [V] 485DevCtl <C1:06> device_type:Batt-Meter
[2026-08-08 04:11:19.614 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:19.620 UTC] [D] 485ChCtl <C1> monitoring dev All Send
[2026-08-08 04:11:19.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.641 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018042, monitor_cnt:50, bc_elapsed:3018042, min:10, max:40
[2026-08-08 04:11:19.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:19.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:19.642 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :4
[2026-08-08 04:11:19.643 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:19.644 UTC] [D] 485AcReq <C3:01> PutOStream [4][0c00000100000006010427f0002f]
[2026-08-08 04:11:19.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:19.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.738 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.758 UTC] [D] 485DevCtl <C3:01> M/W framing err.
[2026-08-08 04:11:19.759 UTC] [D] 485DevCtl <C3:01> RcvDat status[16] len[0]
[2026-08-08 04:11:19.759 UTC] [D] 485DevCtl <C3:01> ResCnd Rcv status err.
[2026-08-08 04:11:19.759 UTC] [V] 485ChCtl <C3> set rt:-1
[2026-08-08 04:11:19.759 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:19.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.838 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:19.939 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:19.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:19.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5701.300000 = p_th_old_:5711.200000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:19.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14109.103173 = old:-14015.922173 +  kp:0.550000 * e:-148.700000 + ki:0.000000 * sume:9375354.400239 + kd:0.040000 * (e:-148.700000 - e1:136.200000)
[2026-08-08 04:11:19.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14109.103173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:19.940 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:19.940 UTC] [D] OFSCtrl battery ctrl val:-28.200000
[2026-08-08 04:11:19.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:19.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:19.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:19.941 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:19.946 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:20.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301799 UPRstat:0
[2026-08-08 04:11:20.100 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:20.101 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:20.101 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:20.101 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:20.103 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:20.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.139 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.220 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018048, monitor_cnt:50, bc_elapsed:3018048, min:10, max:40
[2026-08-08 04:11:20.221 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:20.221 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :9
[2026-08-08 04:11:20.221 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:20.223 UTC] [D] 485AcReq <C2:01> PutOStream [9][0800010413fa001794b1]
[2026-08-08 04:11:20.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.239 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1171->1171] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.339 UTC] [V] OFSCtrl angif value:1171 power_val_:5506.250000
[2026-08-08 04:11:20.405 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:20.405 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:20.405 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:20.405 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:20.405 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:20.406 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:20.407 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:20.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.438 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.538 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.594 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:20.595 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[51] [01042e194a001e197a001c1a02000fffffffffffffffff03e8ffffffff3fbf0000ffffffffffffffffffffffffffffffff8640]
[2026-08-08 04:11:20.595 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [9] IsNormal[1] 
[2026-08-08 04:11:20.596 UTC] [V] 485DevCtl <C2:01> [04][101100][6474.000000][1][V]
[2026-08-08 04:11:20.596 UTC] [V] SummDat SetVrmValue dev_id:7 val:647400.000000 sc:3
[2026-08-08 04:11:20.602 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:04, valueId:101100, value:6474.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:20.608 UTC] [V] 485DevCtl <C2:01> [04][101101][30.000000][1][A]
[2026-08-08 04:11:20.611 UTC] [V] SummDat SetVrmValue dev_id:7 val:3000.000000 sc:3
[2026-08-08 04:11:20.619 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:04, valueId:101101, value:30.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:20.620 UTC] [V] 485DevCtl <C2:01> [05][101100][6522.000000][1][V]
[2026-08-08 04:11:20.624 UTC] [V] SummDat SetVrmValue dev_id:7 val:652200.000000 sc:3
[2026-08-08 04:11:20.627 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:05, valueId:101100, value:6522.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:20.631 UTC] [V] 485DevCtl <C2:01> [05][101101][28.000000][1][A]
[2026-08-08 04:11:20.635 UTC] [V] SummDat SetVrmValue dev_id:7 val:2800.000000 sc:3
[2026-08-08 04:11:20.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.642 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:05, valueId:101101, value:28.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:20.643 UTC] [V] 485DevCtl <C2:01> [06][101100][6658.000000][1][V]
[2026-08-08 04:11:20.649 UTC] [V] SummDat SetVrmValue dev_id:7 val:665800.000000 sc:3
[2026-08-08 04:11:20.654 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:06, valueId:101100, value:6658.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:20.658 UTC] [V] 485DevCtl <C2:01> [06][101101][15.000000][1][A]
[2026-08-08 04:11:20.660 UTC] [V] SummDat SetVrmValue dev_id:7 val:1500.000000 sc:3
[2026-08-08 04:11:20.666 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:06, valueId:101101, value:15.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:20.677 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:20.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:20.692 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:20.720 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018053, monitor_cnt:55, bc_elapsed:3018053, min:10, max:40
[2026-08-08 04:11:20.720 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :9
[2026-08-08 04:11:20.721 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:20.722 UTC] [D] 485AcReq <C2:02> PutOStream [9][0800020413fa00179482]
[2026-08-08 04:11:20.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.739 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.744 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301801 UPRstat:0
[2026-08-08 04:11:20.745 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:20.745 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040408080223389f]
[2026-08-08 04:11:20.745 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:20.746 UTC] [V] OFSCtrl Rcv set flux_of_solar:205.600000
[2026-08-08 04:11:20.746 UTC] [V] 485DevCtl <C1:01> [01][401006][2056.000000][1][W/m2]
[2026-08-08 04:11:20.746 UTC] [V] SummDat SetVrmValue dev_id:1 val:205600.000000 sc:3
[2026-08-08 04:11:20.748 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2056.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:20.748 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:20.748 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:20.749 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:20.749 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:20.749 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:20.750 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:20.754 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:20.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:20.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:20.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:20.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:20.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:20.807 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:20.808 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:20.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.839 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:20.938 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:20.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:20.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5691.400000 = p_th_old_:5701.300000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:20.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14196.729173 = old:-14109.103173 +  kp:0.550000 * e:-158.600000 + ki:0.000000 * sume:9375195.800239 + kd:0.040000 * (e:-158.600000 - e1:-148.700000)
[2026-08-08 04:11:20.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14196.729173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:20.940 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):0.000000
[2026-08-08 04:11:20.940 UTC] [D] OFSCtrl battery ctrl val:-28.400000
[2026-08-08 04:11:20.940 UTC] [V] 485ChCtl <C3> battery limit on [-142.000000,] request.
[2026-08-08 04:11:20.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:20.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:20.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-142] set rate[-28.400000] value100[500] value-100[-500]
[2026-08-08 04:11:20.944 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff72]
[2026-08-08 04:11:21.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:21.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301800 UPRstat:0
[2026-08-08 04:11:21.100 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:21.100 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:21.101 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:21.101 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:21.101 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:21.104 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:21.105 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[51] [02042e1864002418e5002118f4001effffffffffffffff03e8ffffffff40c90000ffffffffffffffffffffffffffffffffd54c]
[2026-08-08 04:11:21.105 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [9] IsNormal[1] 
[2026-08-08 04:11:21.106 UTC] [V] 485DevCtl <C2:02> [04][101100][6244.000000][1][V]
[2026-08-08 04:11:21.106 UTC] [V] SummDat SetVrmValue dev_id:8 val:624400.000000 sc:3
[2026-08-08 04:11:21.107 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:04, valueId:101100, value:6244.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:21.109 UTC] [V] 485DevCtl <C2:02> [04][101101][36.000000][1][A]
[2026-08-08 04:11:21.109 UTC] [V] SummDat SetVrmValue dev_id:8 val:3600.000000 sc:3
[2026-08-08 04:11:21.121 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:04, valueId:101101, value:36.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:21.121 UTC] [V] 485DevCtl <C2:02> [05][101100][6373.000000][1][V]
[2026-08-08 04:11:21.122 UTC] [V] SummDat SetVrmValue dev_id:8 val:637300.000000 sc:3
[2026-08-08 04:11:21.131 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:05, valueId:101100, value:6373.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:21.131 UTC] [V] 485DevCtl <C2:02> [05][101101][33.000000][1][A]
[2026-08-08 04:11:21.132 UTC] [V] SummDat SetVrmValue dev_id:8 val:3300.000000 sc:3
[2026-08-08 04:11:21.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.138 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:21.143 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:05, valueId:101101, value:33.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:21.144 UTC] [V] 485DevCtl <C2:02> [06][101100][6388.000000][1][V]
[2026-08-08 04:11:21.144 UTC] [V] SummDat SetVrmValue dev_id:8 val:638800.000000 sc:3
[2026-08-08 04:11:21.154 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:06, valueId:101100, value:6388.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:21.155 UTC] [V] 485DevCtl <C2:02> [06][101101][30.000000][1][A]
[2026-08-08 04:11:21.155 UTC] [V] SummDat SetVrmValue dev_id:8 val:3000.000000 sc:3
[2026-08-08 04:11:21.164 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:06, valueId:101101, value:30.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:21.179 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:21.180 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:21.180 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:21.205 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301800 UPRstat:0
[2026-08-08 04:11:21.206 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:21.207 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [0403280000614b000061ea0000560a00000051000002580000fdb800000289ffff49c3fffffe2e0012168436e0]
[2026-08-08 04:11:21.208 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:21.208 UTC] [V] OFSCtrl Rcv set p_co:6490.000000, p_co_old:6580.000000
[2026-08-08 04:11:21.208 UTC] [V] 485DevCtl <C1:04> [01][601260][649.000000][2][kW]
[2026-08-08 04:11:21.208 UTC] [V] SummDat SetVrmValue dev_id:4 val:6490.000000 sc:3
[2026-08-08 04:11:21.209 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:649.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:21.209 UTC] [V] 485DevCtl <C1:04> [01][603260][1185412.000000][1][kWh]
[2026-08-08 04:11:21.209 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185412.000000 sc:1
[2026-08-08 04:11:21.209 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185412.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:21.210 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:21.210 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:21.210 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:21.210 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:21.210 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:21.210 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6490.000000
[2026-08-08 04:11:21.211 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:205.600000 < rad_th:80.000000
[2026-08-08 04:11:21.220 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301838:6490.000000
[2026-08-08 04:11:21.227 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:21.232 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:21.233 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:21.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:21.241 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:21.245 UTC] [D] OFSCtrl pv-pcs ctrl val:21.207506 old:21.362231
[2026-08-08 04:11:21.247 UTC] [V] OCHisDB set rate:21 t_rate:312 cnt:16
[2026-08-08 04:11:21.248 UTC] [V] 485ChCtl <C2> pv-pcs limit on [21.207506] request.
[2026-08-08 04:11:21.248 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:21.248 UTC] [V] OFSCtrl Nod calc proc start.
[2026-08-08 04:11:21.248 UTC] [V] OFSCtrl ProcNodCountCalculation cur:301838 >= next:301878 diff:-40
[2026-08-08 04:11:21.249 UTC] [V] OFSCtrl ProcNodCountCalculation time not reached:-40
[2026-08-08 04:11:21.249 UTC] [V] OFSCtrl update p_co_old:6490.000000
[2026-08-08 04:11:21.249 UTC] [V] OFSCtrl Nod calc proc:
[2026-08-08 04:11:21.249 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:21.258 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:21.321 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:21.321 UTC] [D] VarInf update ofs_rate:21.207506
[2026-08-08 04:11:21.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:21.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:21.322 UTC] [D] VarInf update ofs_rate:21.207506
[2026-08-08 04:11:21.322 UTC] [D] VarInf Limit setRate[212.075058] rate[21.207506] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:21.322 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:21.207506 set_rate212
[2026-08-08 04:11:21.322 UTC] [D] VarInf Limit rt[2] int_set_rate[212] server_rate[21.207506] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:21.323 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00d487f0]
[2026-08-08 04:11:21.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:21.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:21.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.538 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:21.616 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:21.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:21.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:21 val:6490.000000
[2026-08-08 04:11:21.691 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:21' , 6490.000000 , 0  )
[2026-08-08 04:11:21.711 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:21.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:21.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.839 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:21.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:21.938 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:21.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:21.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5681.500000 = p_th_old_:5691.400000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:21.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14127.550173 = old:-14196.729173 +  kp:0.550000 * e:106.500000 + ki:0.000000 * sume:9375302.300239 + kd:0.040000 * (e:106.500000 - e1:-158.600000)
[2026-08-08 04:11:21.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14127.550173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:21.940 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:21.940 UTC] [D] OFSCtrl battery ctrl val:-28.300000
[2026-08-08 04:11:21.941 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:21.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:22.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.039 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:22.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:22.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:22.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:22.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.138 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:22.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301801 UPRstat:0
[2026-08-08 04:11:22.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:22.202 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:22.202 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:22.203 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:22.206 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:22.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.238 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:22.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.339 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:22.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.439 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:22.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.538 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:22.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.638 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:22.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:22.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.739 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:22.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:22.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:22.939 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:22.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:22.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5671.600000 = p_th_old_:5681.500000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:22.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14115.378673 = old:-14127.550173 +  kp:0.550000 * e:27.850000 + ki:0.000000 * sume:9375330.150239 + kd:0.040000 * (e:27.850000 - e1:106.500000)
[2026-08-08 04:11:22.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14115.378673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:22.940 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:22.940 UTC] [D] OFSCtrl battery ctrl val:-28.200000
[2026-08-08 04:11:22.940 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:22.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:22.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:22.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:22.944 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:23.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.038 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301802 UPRstat:0
[2026-08-08 04:11:23.090 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:23.090 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:23.090 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:23.091 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:23.091 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:23.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.139 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.338 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.539 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:23.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.639 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:23.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:23.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.739 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:23.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.838 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:23.938 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:23.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:23.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5661.700000 = p_th_old_:5671.600000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:23.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14105.902173 = old:-14115.378673 +  kp:0.550000 * e:17.950000 + ki:0.000000 * sume:9375348.100239 + kd:0.040000 * (e:17.950000 - e1:27.850000)
[2026-08-08 04:11:23.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14105.902173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:23.939 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:23.939 UTC] [D] OFSCtrl battery ctrl val:-28.200000
[2026-08-08 04:11:23.940 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:23.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:23.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:23.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:23.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:24.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.039 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301803 UPRstat:0
[2026-08-08 04:11:24.101 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:24.101 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:24.101 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:24.101 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:24.102 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:24.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.139 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:24.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.338 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.641 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018092, monitor_cnt:50, bc_elapsed:3018092, min:10, max:40
[2026-08-08 04:11:24.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:24.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:24.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :4
[2026-08-08 04:11:24.643 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:24.644 UTC] [D] 485AcReq <C3:01> PutOStream [4][0c00000100000006010427f0002f]
[2026-08-08 04:11:24.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:24.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.739 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:24.788 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301804 UPRstat:0
[2026-08-08 04:11:24.791 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[103] [00010000006101045e1f1cff53ff760f900f8c0fbd00cd00cb00ceff73000000000000000000000000000000000222001b9ddc000091260000012c00000067030b301a00000001177503e701d4014e01bc00d6000019de00002f4b0001008e02220000001b0000]
[2026-08-08 04:11:24.791 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [4] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:24.791 UTC] [V] 485DevCtl <C3:01> [05][753053][0.000000][0][]
[2026-08-08 04:11:24.791 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:24.803 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:05, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:24.803 UTC] [V] 485DevCtl <C3:01> [06][753053][0.000000][0][]
[2026-08-08 04:11:24.804 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:24.821 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:06, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:24.824 UTC] [V] 485DevCtl <C3:01> [07][753053][0.000000][0][]
[2026-08-08 04:11:24.825 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:24.827 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:07, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:24.831 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:24.835 UTC] [V] 485DevCtl <C3:01> set2 StatusCode[020101]
[2026-08-08 04:11:24.836 UTC] [V] OFSCtrl Bat[0301] StCd[020101]->st[1].
[2026-08-08 04:11:24.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.843 UTC] [V] OFSCtrl set batt status:[0301]:Drive, All:[0301]:Drive, [DRIVE] 
[2026-08-08 04:11:24.845 UTC] [V] OFSCtrl change set SOC(t):61.000000 drive cnt:1
[2026-08-08 04:11:24.863 UTC] [V] 485DevCtl <C3:01> set2 StatusCode[020101] DeviceName[蓄電池1] DeviceNumber[1]
[2026-08-08 04:11:24.866 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:24.867 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:24.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:24.938 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:24.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:24.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5651.800000 = p_th_old_:5661.700000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:24.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14101.870673 = old:-14105.902173 +  kp:0.550000 * e:8.050000 + ki:0.000000 * sume:9375356.150239 + kd:0.040000 * (e:8.050000 - e1:17.950000)
[2026-08-08 04:11:24.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14101.870673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:24.940 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:24.940 UTC] [D] OFSCtrl battery ctrl val:-28.200000
[2026-08-08 04:11:24.941 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:24.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:25.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.039 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:25.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:25.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:25.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.139 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301804 UPRstat:0
[2026-08-08 04:11:25.189 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:25.190 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:25.190 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:25.190 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:25.191 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:25.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.339 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:25.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:25.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:25.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:25.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:25.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:25.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:25.407 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:25.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.538 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:25.721 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018103, monitor_cnt:50, bc_elapsed:3018103, min:10, max:40
[2026-08-08 04:11:25.721 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:25.721 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:25.722 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:25.723 UTC] [D] 485AcReq <C2:01> PutOStream [1][08000104138a0024d57f]
[2026-08-08 04:11:25.738 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301806 UPRstat:0
[2026-08-08 04:11:25.739 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:25.739 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [010404083c02237951]
[2026-08-08 04:11:25.740 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.740 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.739 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:25.741 UTC] [V] OFSCtrl Rcv set flux_of_solar:210.800000
[2026-08-08 04:11:25.741 UTC] [V] 485DevCtl <C1:01> [01][401006][2108.000000][1][W/m2]
[2026-08-08 04:11:25.741 UTC] [V] SummDat SetVrmValue dev_id:1 val:210800.000000 sc:3
[2026-08-08 04:11:25.741 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2108.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:25.742 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:25.742 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:25.746 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:25.750 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:25.751 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:25.756 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:25.758 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:25.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:25.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:25.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:25.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:25.805 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:25.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:25.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:25.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:25.939 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:25.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:25.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5641.900000 = p_th_old_:5651.800000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:25.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14103.284173 = old:-14101.870673 +  kp:0.550000 * e:-1.850000 + ki:0.000000 * sume:9375354.300239 + kd:0.040000 * (e:-1.850000 - e1:8.050000)
[2026-08-08 04:11:25.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14103.284173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:25.940 UTC] [V] OFSCtrl CHG 29 q:-142.000000, mod(round):1.000000
[2026-08-08 04:11:25.940 UTC] [D] OFSCtrl battery ctrl val:-28.200000
[2026-08-08 04:11:25.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:25.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-141] set rate[-28.200000] value100[500] value-100[-500]
[2026-08-08 04:11:25.940 UTC] [V] 485ChCtl <C3> battery limit on [-141.000000,] request.
[2026-08-08 04:11:25.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:25.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff73]
[2026-08-08 04:11:26.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.039 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301805 UPRstat:0
[2026-08-08 04:11:26.090 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:26.092 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:26.092 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:26.093 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:26.096 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:26.126 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:26.129 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[77] [01044801b2fc9f00001726000001992901000019b7001a199b001b19c1001928e7000010bc10bf10de008f008e008fffffffffffffffffffffffff284a0000067e000003db0258267a82001bf0]
[2026-08-08 04:11:26.129 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:26.129 UTC] [V] 485DevCtl <C2:01> [01][115202][434.000000][1][kWh]
[2026-08-08 04:11:26.129 UTC] [V] SummDat SetVrmValue dev_id:7 val:434.000000 sc:1
[2026-08-08 04:11:26.134 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:115202, value:434.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.139 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:26.141 UTC] [V] 485DevCtl <C2:01> [01][113202][64671.000000][0][kWh]
[2026-08-08 04:11:26.142 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671.000000 sc:0
[2026-08-08 04:11:26.143 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:113202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:26.149 UTC] [V] 485DevCtl <C2:01> [01][121005][409.000000][1][℃]
[2026-08-08 04:11:26.153 UTC] [V] SummDat SetVrmValue dev_id:7 val:40900.000000 sc:3
[2026-08-08 04:11:26.154 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121005, value:409.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.163 UTC] [V] 485DevCtl <C2:01> [01][101100][6583.000000][1][V]
[2026-08-08 04:11:26.163 UTC] [V] SummDat SetVrmValue dev_id:7 val:658300.000000 sc:3
[2026-08-08 04:11:26.164 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101100, value:6583.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.171 UTC] [V] 485DevCtl <C2:01> [01][101101][26.000000][1][A]
[2026-08-08 04:11:26.174 UTC] [V] SummDat SetVrmValue dev_id:7 val:2600.000000 sc:3
[2026-08-08 04:11:26.174 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101101, value:26.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.175 UTC] [V] 485DevCtl <C2:01> [02][101100][6555.000000][1][V]
[2026-08-08 04:11:26.183 UTC] [V] SummDat SetVrmValue dev_id:7 val:655500.000000 sc:3
[2026-08-08 04:11:26.188 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101100, value:6555.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.189 UTC] [V] 485DevCtl <C2:01> [02][101101][27.000000][1][A]
[2026-08-08 04:11:26.189 UTC] [V] SummDat SetVrmValue dev_id:7 val:2700.000000 sc:3
[2026-08-08 04:11:26.205 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301805 UPRstat:0
[2026-08-08 04:11:26.205 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:26.207 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800006080000060eb0000552200000050000002580000f9340000027dffff499dfffffe2e001216851e0e]
[2026-08-08 04:11:26.207 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:26.207 UTC] [V] OFSCtrl Rcv set p_co:6370.000000, p_co_old:6490.000000
[2026-08-08 04:11:26.208 UTC] [V] 485DevCtl <C1:04> [01][601260][637.000000][2][kW]
[2026-08-08 04:11:26.211 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101101, value:27.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.212 UTC] [V] 485DevCtl <C2:01> [03][101100][6593.000000][1][V]
[2026-08-08 04:11:26.218 UTC] [V] SummDat SetVrmValue dev_id:4 val:6370.000000 sc:3
[2026-08-08 04:11:26.212 UTC] [V] SummDat SetVrmValue dev_id:7 val:659300.000000 sc:3
[2026-08-08 04:11:26.222 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:637.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:26.222 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101100, value:6593.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.224 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:26.224 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:26.224 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:26.225 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:26.225 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:26.225 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:26.225 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:26.225 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:26.225 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6370.000000
[2026-08-08 04:11:26.226 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:210.800000 < rad_th:80.000000
[2026-08-08 04:11:26.226 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301843:6370.000000
[2026-08-08 04:11:26.226 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:26.226 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:26.227 UTC] [V] 485DevCtl <C2:01> [03][101101][25.000000][1][A]
[2026-08-08 04:11:26.227 UTC] [V] SummDat SetVrmValue dev_id:7 val:2500.000000 sc:3
[2026-08-08 04:11:26.227 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101101, value:25.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.227 UTC] [V] 485DevCtl <C2:01> [01][101102][10471.000000][0][W]
[2026-08-08 04:11:26.227 UTC] [V] SummDat SetVrmValue dev_id:7 val:10471000.000000 sc:3
[2026-08-08 04:11:26.234 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101102, value:10471.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:26.236 UTC] [V] 485DevCtl <C2:01> [01][111200][4284.000000][1][V]
[2026-08-08 04:11:26.237 UTC] [V] SummDat SetVrmValue dev_id:7 val:428400.000000 sc:3
[2026-08-08 04:11:26.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.238 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.245 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111200, value:4284.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.245 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:26.259 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:26.259 UTC] [D] OFSCtrl pv-pcs ctrl val:21.707506 old:21.207506
[2026-08-08 04:11:26.259 UTC] [V] OCHisDB set rate:22 t_rate:334 cnt:17
[2026-08-08 04:11:26.259 UTC] [V] 485ChCtl <C2> pv-pcs limit on [21.707506] request.
[2026-08-08 04:11:26.259 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:26.260 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:26.254 UTC] [V] 485DevCtl <C2:01> [02][111200][4287.000000][1][V]
[2026-08-08 04:11:26.264 UTC] [V] SummDat SetVrmValue dev_id:7 val:428700.000000 sc:3
[2026-08-08 04:11:26.264 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111200, value:4287.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.265 UTC] [V] 485DevCtl <C2:01> [03][111200][4318.000000][1][V]
[2026-08-08 04:11:26.265 UTC] [V] SummDat SetVrmValue dev_id:7 val:431800.000000 sc:3
[2026-08-08 04:11:26.265 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111200, value:4318.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.265 UTC] [V] 485DevCtl <C2:01> [01][111201][143.000000][1][A]
[2026-08-08 04:11:26.265 UTC] [V] SummDat SetVrmValue dev_id:7 val:14300.000000 sc:3
[2026-08-08 04:11:26.266 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111201, value:143.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.269 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:26.274 UTC] [V] 485DevCtl <C2:01> [02][111201][142.000000][1][A]
[2026-08-08 04:11:26.278 UTC] [V] SummDat SetVrmValue dev_id:7 val:14200.000000 sc:3
[2026-08-08 04:11:26.288 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111201, value:142.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.289 UTC] [V] 485DevCtl <C2:01> [03][111201][143.000000][1][A]
[2026-08-08 04:11:26.289 UTC] [V] SummDat SetVrmValue dev_id:7 val:14300.000000 sc:3
[2026-08-08 04:11:26.297 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111201, value:143.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.301 UTC] [V] 485DevCtl <C2:01> [01][111202][10314.000000][0][W]
[2026-08-08 04:11:26.303 UTC] [V] SummDat SetVrmValue dev_id:7 val:10314000.000000 sc:3
[2026-08-08 04:11:26.304 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111202, value:10314.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:26.312 UTC] [V] 485DevCtl <C2:01> [01][111203][1662.000000][0][var]
[2026-08-08 04:11:26.314 UTC] [V] SummDat SetVrmValue dev_id:7 val:1662000.000000 sc:3
[2026-08-08 04:11:26.319 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111203, value:1662.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:26.324 UTC] [V] 485DevCtl <C2:01> [01][121007][987.000000][3][]
[2026-08-08 04:11:26.324 UTC] [V] SummDat SetVrmValue dev_id:7 val:987.000000 sc:3
[2026-08-08 04:11:26.324 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121007, value:987.000000, scaleFactor:3, devId:7
[2026-08-08 04:11:26.324 UTC] [V] 485DevCtl <C2:01> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:26.325 UTC] [V] SummDat SetVrmValue dev_id:7 val:60000.000000 sc:3
[2026-08-08 04:11:26.325 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:26.325 UTC] [V] 485DevCtl <C2:01> [01][114202][64671.000000][0][kWh]
[2026-08-08 04:11:26.325 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671000.000000 sc:3
[2026-08-08 04:11:26.326 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:114202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:26.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.341 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:26.349 UTC] [V] 485DevCtl <C2:01> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:26.352 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:26.421 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:26.421 UTC] [D] VarInf update ofs_rate:21.707506
[2026-08-08 04:11:26.421 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:26.422 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:26.422 UTC] [D] VarInf update ofs_rate:21.707506
[2026-08-08 04:11:26.422 UTC] [D] VarInf Limit setRate[217.075058] rate[21.707506] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:26.422 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:21.707506 set_rate217
[2026-08-08 04:11:26.422 UTC] [D] VarInf Limit rt[2] int_set_rate[217] server_rate[21.707506] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:26.426 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00d94635]
[2026-08-08 04:11:26.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.439 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:26 val:6370.000000
[2026-08-08 04:11:26.691 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:26' , 6370.000000 , 0  )
[2026-08-08 04:11:26.712 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:26.723 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:26.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.738 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:26.821 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018114, monitor_cnt:61, bc_elapsed:3018114, min:10, max:40
[2026-08-08 04:11:26.821 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:26.822 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:26.823 UTC] [D] 485AcReq <C2:02> PutOStream [1][08000204138a0024d54c]
[2026-08-08 04:11:26.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:26.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1171->1171] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:26.939 UTC] [V] OFSCtrl angif value:1171 power_val_:5506.250000
[2026-08-08 04:11:26.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:26.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5632.000000 = p_th_old_:5641.900000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:26.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14029.017673 = old:-14103.284173 +  kp:0.550000 * e:125.750000 + ki:0.000000 * sume:9375480.050239 + kd:0.040000 * (e:125.750000 - e1:-1.850000)
[2026-08-08 04:11:26.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14029.017673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:26.940 UTC] [V] OFSCtrl CHG 29 q:-141.000000, mod(round):1.000000
[2026-08-08 04:11:26.940 UTC] [D] OFSCtrl battery ctrl val:-28.100000
[2026-08-08 04:11:26.941 UTC] [V] 485ChCtl <C3> battery limit on [-140.000000,] request.
[2026-08-08 04:11:26.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:27.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.038 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:27.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:27.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-140] set rate[-28.000000] value100[500] value-100[-500]
[2026-08-08 04:11:27.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff74]
[2026-08-08 04:11:27.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.138 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:27.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301806 UPRstat:0
[2026-08-08 04:11:27.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:27.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:27.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:27.203 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:27.204 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:27.229 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:27.231 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[77] [02044801af022a00011719000001942a6500001a23000f18cf00241a1900122a05000010c410c010e9009300920093ffffffffffffffffffffffff29640000068a000003dc0258267a82001749]
[2026-08-08 04:11:27.231 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:27.231 UTC] [V] 485DevCtl <C2:02> [01][115202][431.000000][1][kWh]
[2026-08-08 04:11:27.231 UTC] [V] SummDat SetVrmValue dev_id:8 val:431.000000 sc:1
[2026-08-08 04:11:27.232 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:115202, value:431.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:27.247 UTC] [V] 485DevCtl <C2:02> [01][113202][66090.000000][0][kWh]
[2026-08-08 04:11:27.247 UTC] [V] SummDat SetVrmValue dev_id:8 val:66090.000000 sc:0
[2026-08-08 04:11:27.251 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:113202, value:66090.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:27.254 UTC] [V] 485DevCtl <C2:02> [01][121005][404.000000][1][℃]
[2026-08-08 04:11:27.256 UTC] [V] SummDat SetVrmValue dev_id:8 val:40400.000000 sc:3
[2026-08-08 04:11:27.265 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121005, value:404.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.266 UTC] [V] 485DevCtl <C2:02> [01][101100][6691.000000][1][V]
[2026-08-08 04:11:27.275 UTC] [V] SummDat SetVrmValue dev_id:8 val:669100.000000 sc:3
[2026-08-08 04:11:27.282 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101100, value:6691.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.283 UTC] [V] 485DevCtl <C2:02> [01][101101][15.000000][1][A]
[2026-08-08 04:11:27.283 UTC] [V] SummDat SetVrmValue dev_id:8 val:1500.000000 sc:3
[2026-08-08 04:11:27.283 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101101, value:15.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.284 UTC] [V] 485DevCtl <C2:02> [02][101100][6351.000000][1][V]
[2026-08-08 04:11:27.284 UTC] [V] SummDat SetVrmValue dev_id:8 val:635100.000000 sc:3
[2026-08-08 04:11:27.284 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101100, value:6351.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.284 UTC] [V] 485DevCtl <C2:02> [02][101101][36.000000][1][A]
[2026-08-08 04:11:27.284 UTC] [V] SummDat SetVrmValue dev_id:8 val:3600.000000 sc:3
[2026-08-08 04:11:27.285 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101101, value:36.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.285 UTC] [V] 485DevCtl <C2:02> [03][101100][6681.000000][1][V]
[2026-08-08 04:11:27.307 UTC] [V] SummDat SetVrmValue dev_id:8 val:668100.000000 sc:3
[2026-08-08 04:11:27.312 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101100, value:6681.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.313 UTC] [V] 485DevCtl <C2:02> [03][101101][18.000000][1][A]
[2026-08-08 04:11:27.313 UTC] [V] SummDat SetVrmValue dev_id:8 val:1800.000000 sc:3
[2026-08-08 04:11:27.313 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101101, value:18.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.334 UTC] [V] 485DevCtl <C2:02> [01][101102][10757.000000][0][W]
[2026-08-08 04:11:27.334 UTC] [V] SummDat SetVrmValue dev_id:8 val:10757000.000000 sc:3
[2026-08-08 04:11:27.335 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101102, value:10757.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:27.335 UTC] [V] 485DevCtl <C2:02> [01][111200][4292.000000][1][V]
[2026-08-08 04:11:27.335 UTC] [V] SummDat SetVrmValue dev_id:8 val:429200.000000 sc:3
[2026-08-08 04:11:27.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.339 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:27.345 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111200, value:4292.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.349 UTC] [V] 485DevCtl <C2:02> [02][111200][4288.000000][1][V]
[2026-08-08 04:11:27.351 UTC] [V] SummDat SetVrmValue dev_id:8 val:428800.000000 sc:3
[2026-08-08 04:11:27.356 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111200, value:4288.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.356 UTC] [V] 485DevCtl <C2:02> [03][111200][4329.000000][1][V]
[2026-08-08 04:11:27.356 UTC] [V] SummDat SetVrmValue dev_id:8 val:432900.000000 sc:3
[2026-08-08 04:11:27.357 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111200, value:4329.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.357 UTC] [V] 485DevCtl <C2:02> [01][111201][147.000000][1][A]
[2026-08-08 04:11:27.357 UTC] [V] SummDat SetVrmValue dev_id:8 val:14700.000000 sc:3
[2026-08-08 04:11:27.362 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111201, value:147.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.364 UTC] [V] 485DevCtl <C2:02> [02][111201][146.000000][1][A]
[2026-08-08 04:11:27.365 UTC] [V] SummDat SetVrmValue dev_id:8 val:14600.000000 sc:3
[2026-08-08 04:11:27.371 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111201, value:146.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.376 UTC] [V] 485DevCtl <C2:02> [03][111201][147.000000][1][A]
[2026-08-08 04:11:27.380 UTC] [V] SummDat SetVrmValue dev_id:8 val:14700.000000 sc:3
[2026-08-08 04:11:27.388 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111201, value:147.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.392 UTC] [V] 485DevCtl <C2:02> [01][111202][10596.000000][0][W]
[2026-08-08 04:11:27.392 UTC] [V] SummDat SetVrmValue dev_id:8 val:10596000.000000 sc:3
[2026-08-08 04:11:27.393 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111202, value:10596.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:27.404 UTC] [V] 485DevCtl <C2:02> [01][111203][1674.000000][0][var]
[2026-08-08 04:11:27.406 UTC] [V] SummDat SetVrmValue dev_id:8 val:1674000.000000 sc:3
[2026-08-08 04:11:27.408 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111203, value:1674.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:27.410 UTC] [V] 485DevCtl <C2:02> [01][121007][988.000000][3][]
[2026-08-08 04:11:27.412 UTC] [V] SummDat SetVrmValue dev_id:8 val:988.000000 sc:3
[2026-08-08 04:11:27.417 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121007, value:988.000000, scaleFactor:3, devId:8
[2026-08-08 04:11:27.421 UTC] [V] 485DevCtl <C2:02> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:27.424 UTC] [V] SummDat SetVrmValue dev_id:8 val:60000.000000 sc:3
[2026-08-08 04:11:27.428 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:27.432 UTC] [V] 485DevCtl <C2:02> [01][114202][66090.000000][0][kWh]
[2026-08-08 04:11:27.432 UTC] [V] SummDat SetVrmValue dev_id:8 val:66090000.000000 sc:3
[2026-08-08 04:11:27.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.438 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:27.440 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:114202, value:66090.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:27.443 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:27.448 UTC] [V] 485DevCtl <C2:02> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:27.449 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:27.449 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:27.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.538 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:27.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.639 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:27.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:27.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.739 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:27.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.839 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:27.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:27.939 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:27.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:27.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5622.100000 = p_th_old_:5632.000000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:27.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14371.321173 = old:-14029.017673 +  kp:0.550000 * e:-571.650000 + ki:0.000000 * sume:9374908.400239 + kd:0.040000 * (e:-571.650000 - e1:125.750000)
[2026-08-08 04:11:27.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14371.321173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:27.941 UTC] [V] OFSCtrl CHG 29 q:-144.000000, mod(round):0.000000
[2026-08-08 04:11:27.941 UTC] [D] OFSCtrl battery ctrl val:-28.700000
[2026-08-08 04:11:27.941 UTC] [V] 485ChCtl <C3> battery limit on [-144.000000,] request.
[2026-08-08 04:11:27.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:28.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.038 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:28.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:28.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-144] set rate[-28.800000] value100[500] value-100[-500]
[2026-08-08 04:11:28.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff70]
[2026-08-08 04:11:28.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.138 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:28.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301807 UPRstat:0
[2026-08-08 04:11:28.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:28.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:28.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:28.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:28.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:28.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.239 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:28.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1181->1181] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.339 UTC] [V] OFSCtrl angif value:1181 power_val_:6193.750000
[2026-08-08 04:11:28.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.439 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:28.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.538 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:28.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:28.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:28.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:28.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.839 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:28.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:28.938 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:28.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:28.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5612.200000 = p_th_old_:5622.100000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:28.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14448.194673 = old:-14371.321173 +  kp:0.550000 * e:-169.050000 + ki:0.000000 * sume:9374739.350239 + kd:0.040000 * (e:-169.050000 - e1:-571.650000)
[2026-08-08 04:11:28.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14448.194673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:28.940 UTC] [V] OFSCtrl CHG 29 q:-145.000000, mod(round):1.000000
[2026-08-08 04:11:28.940 UTC] [D] OFSCtrl battery ctrl val:-28.900000
[2026-08-08 04:11:28.941 UTC] [V] 485ChCtl <C3> battery limit on [-144.000000,] request.
[2026-08-08 04:11:28.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:29.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:29.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:29.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-144] set rate[-28.800000] value100[500] value-100[-500]
[2026-08-08 04:11:29.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff70]
[2026-08-08 04:11:29.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:29.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301808 UPRstat:0
[2026-08-08 04:11:29.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:29.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:29.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:29.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:29.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:29.204 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018138, monitor_cnt:100, bc_elapsed:38, min:10, max:40
[2026-08-08 04:11:29.205 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:29.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:29.304 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018139, monitor_cnt:101, bc_elapsed:39, min:10, max:40
[2026-08-08 04:11:29.304 UTC] [V] 485DevCtl <C1:02> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:29.304 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:29.305 UTC] [V] 485ChCtl <C1> send request:IMT01
[2026-08-08 04:11:29.306 UTC] [D] 485AcReq <C1:02> PutOStream [1][08000204000200019039]
[2026-08-08 04:11:29.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:29.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.438 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:29.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.538 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:29.641 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.641 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:29.641 UTC] [V] 485DevCtl <C1:02> AnalyzeResponseData proc restart cnt:301803 UPRstat:0
[2026-08-08 04:11:29.641 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:29.642 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018142, monitor_cnt:50, bc_elapsed:3018142, min:10, max:40
[2026-08-08 04:11:29.643 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:29.643 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:29.643 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :5
[2026-08-08 04:11:29.644 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:29.645 UTC] [D] 485AcReq <C3:01> PutOStream [5][0c00000100000006010469780001]
[2026-08-08 04:11:29.642 UTC] [D] 485DevCtl <C1:02> RcvDat status[2] len[7] [020402021cfd99]
[2026-08-08 04:11:29.648 UTC] [D] 485DevCtl <C1:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:29.648 UTC] [V] 485DevCtl <C1:02> [01][431005][290.000000][1][°C]
[2026-08-08 04:11:29.648 UTC] [V] SummDat SetVrmValue dev_id:2 val:29000.000000 sc:3
[2026-08-08 04:11:29.649 UTC] [V] OCMgr SetMeterValue PhId:0102, branchNo:01, valueId:431005, value:290.000000, scaleFactor:1, devId:2
[2026-08-08 04:11:29.649 UTC] [V] 485DevCtl <C1:02> device_type:
[2026-08-08 04:11:29.650 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:29.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:29.703 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:29.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:29.768 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301809 UPRstat:0
[2026-08-08 04:11:29.769 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[11] [000100000005010402012b]
[2026-08-08 04:11:29.769 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [5] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:29.769 UTC] [V] 485DevCtl <C3:01> [01][121005][299.000000][1][℃]
[2026-08-08 04:11:29.769 UTC] [V] SummDat SetVrmValue dev_id:9 val:29900.000000 sc:3
[2026-08-08 04:11:29.770 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:121005, value:299.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:29.770 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:29.771 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:29.784 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:29.804 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:29.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.838 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:29.904 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:29.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:29.938 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:29.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:29.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5602.300000 = p_th_old_:5612.200000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:29.939 UTC] [V] OFSCtrl CHG 21 batt_w:-14547.013173 = old:-14448.194673 +  kp:0.550000 * e:-178.950000 + ki:0.000000 * sume:9374560.400239 + kd:0.040000 * (e:-178.950000 - e1:-169.050000)
[2026-08-08 04:11:29.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14547.013173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:29.939 UTC] [V] OFSCtrl CHG 29 q:-146.000000, mod(round):1.000000
[2026-08-08 04:11:29.940 UTC] [D] OFSCtrl battery ctrl val:-29.100000
[2026-08-08 04:11:29.940 UTC] [V] 485ChCtl <C3> battery limit on [-145.000000,] request.
[2026-08-08 04:11:29.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:29.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:29.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-145] set rate[-29.000000] value100[500] value-100[-500]
[2026-08-08 04:11:29.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff6f]
[2026-08-08 04:11:30.003 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:30.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:30.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301809 UPRstat:0
[2026-08-08 04:11:30.100 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:30.101 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:30.101 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:30.101 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:30.101 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:30.104 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:30.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.139 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:30.204 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:30.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.238 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:30.303 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:30.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.338 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:30.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:30.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:30.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:30.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:30.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:30.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:30.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.639 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:30.738 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301811 UPRstat:0
[2026-08-08 04:11:30.738 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:30.738 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040408b20223197a]
[2026-08-08 04:11:30.739 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:30.739 UTC] [V] OFSCtrl Rcv set flux_of_solar:222.600000
[2026-08-08 04:11:30.739 UTC] [V] 485DevCtl <C1:01> [01][401006][2226.000000][1][W/m2]
[2026-08-08 04:11:30.739 UTC] [V] SummDat SetVrmValue dev_id:1 val:222600.000000 sc:3
[2026-08-08 04:11:30.740 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2226.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:30.740 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:30.740 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:30.741 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.741 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.743 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:30.743 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:30.743 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:30.743 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:30.757 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:30.805 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:30.806 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:30.806 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:30.806 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:30.806 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:30.807 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:30.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:30.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.839 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:30.939 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:30.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:30.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5592.400000 = p_th_old_:5602.300000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:30.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14610.714173 = old:-14547.013173 +  kp:0.550000 * e:-120.100000 + ki:0.000000 * sume:9374440.300239 + kd:0.040000 * (e:-120.100000 - e1:-178.950000)
[2026-08-08 04:11:30.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14610.714173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:30.940 UTC] [V] OFSCtrl CHG 29 q:-147.000000, mod(round):1.000000
[2026-08-08 04:11:30.940 UTC] [D] OFSCtrl battery ctrl val:-29.200000
[2026-08-08 04:11:30.941 UTC] [V] 485ChCtl <C3> battery limit on [-146.000000,] request.
[2026-08-08 04:11:30.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:30.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-146] set rate[-29.200000] value100[500] value-100[-500]
[2026-08-08 04:11:30.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff6e]
[2026-08-08 04:11:30.946 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:31.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:31.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301810 UPRstat:0
[2026-08-08 04:11:31.090 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:31.090 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:31.090 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:31.090 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:31.091 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:31.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.139 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:31.219 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301810 UPRstat:0
[2026-08-08 04:11:31.220 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:31.221 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800006092000060fe0000553400000050000002580000f9610000027effff4984fffffe2d00121685ac63]
[2026-08-08 04:11:31.221 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:31.222 UTC] [V] OFSCtrl Rcv set p_co:6380.000000, p_co_old:6490.000000
[2026-08-08 04:11:31.222 UTC] [V] 485DevCtl <C1:04> [01][601260][638.000000][2][kW]
[2026-08-08 04:11:31.223 UTC] [V] SummDat SetVrmValue dev_id:4 val:6380.000000 sc:3
[2026-08-08 04:11:31.231 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:638.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:31.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.239 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:31.237 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:31.240 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:31.240 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:31.246 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:31.249 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:31.249 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:31.249 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:31.250 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:31.250 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6380.000000
[2026-08-08 04:11:31.250 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:222.600000 < rad_th:80.000000
[2026-08-08 04:11:31.250 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301848:6380.000000
[2026-08-08 04:11:31.250 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:31.251 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:31.251 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:31.251 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:31.251 UTC] [D] OFSCtrl pv-pcs ctrl val:22.207506 old:21.707506
[2026-08-08 04:11:31.252 UTC] [V] OCHisDB set rate:22 t_rate:356 cnt:18
[2026-08-08 04:11:31.252 UTC] [V] 485ChCtl <C2> pv-pcs limit on [22.207506] request.
[2026-08-08 04:11:31.273 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:31.275 UTC] [V] OFSCtrl Nod calc proc start.
[2026-08-08 04:11:31.276 UTC] [V] OFSCtrl ProcNodCountCalculation cur:301848 >= next:301878 diff:-30
[2026-08-08 04:11:31.276 UTC] [V] OFSCtrl ProcNodCountCalculation time not reached:-30
[2026-08-08 04:11:31.276 UTC] [V] OFSCtrl update p_co_old:6380.000000
[2026-08-08 04:11:31.276 UTC] [V] OFSCtrl Nod calc proc:
[2026-08-08 04:11:31.287 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:31.289 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:31.304 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:31.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:31.321 UTC] [D] VarInf update ofs_rate:22.207506
[2026-08-08 04:11:31.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:31.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:31.321 UTC] [D] VarInf update ofs_rate:22.207506
[2026-08-08 04:11:31.321 UTC] [D] VarInf Limit setRate[222.075058] rate[22.207506] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:31.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:22.207506 set_rate222
[2026-08-08 04:11:31.321 UTC] [D] VarInf Limit rt[2] int_set_rate[222] server_rate[22.207506] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:31.323 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00de07f7]
[2026-08-08 04:11:31.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.339 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:31.404 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:31.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:31.504 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018161, monitor_cnt:123, bc_elapsed:11, min:10, max:40
[2026-08-08 04:11:31.504 UTC] [V] 485DevCtl <C1:03> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:31.504 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:31.505 UTC] [V] 485ChCtl <C1> send request:omron03
[2026-08-08 04:11:31.506 UTC] [D] 485AcReq <C1:03> PutOStream [1][08000303000000144427]
[2026-08-08 04:11:31.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.539 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:31.612 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:31.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:31.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:31 val:6380.000000
[2026-08-08 04:11:31.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:31' , 6380.000000 , 0  )
[2026-08-08 04:11:31.713 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:31.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.738 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:31.821 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018164, monitor_cnt:50, bc_elapsed:3018164, min:10, max:40
[2026-08-08 04:11:31.821 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:31.821 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :10
[2026-08-08 04:11:31.822 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:31.823 UTC] [D] 485AcReq <C2:01> PutOStream [10][0800010413d80002f574]
[2026-08-08 04:11:31.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.838 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:31.900 UTC] [V] 485DevCtl <C1:03> AnalyzeResponseData proc restart cnt:301805 UPRstat:0
[2026-08-08 04:11:31.900 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:31.903 UTC] [D] 485DevCtl <C1:03> RcvDat status[2] len[45] [0303280000fc290000ff380000fe70000021730000268400002d0c0000005e0000025900100a4100002910cc04]
[2026-08-08 04:11:31.903 UTC] [D] 485DevCtl <C1:03> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:31.903 UTC] [V] 485DevCtl <C1:03> [01][301200][64553.000000][1][V]
[2026-08-08 04:11:31.904 UTC] [V] SummDat SetVrmValue dev_id:3 val:6455300.000000 sc:3
[2026-08-08 04:11:31.904 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301200, value:64553.000000, scaleFactor:1, devId:3
[2026-08-08 04:11:31.904 UTC] [V] 485DevCtl <C1:03> [01][301201][8563.000000][3][A]
[2026-08-08 04:11:31.905 UTC] [V] SummDat SetVrmValue dev_id:3 val:8563.000000 sc:3
[2026-08-08 04:11:31.905 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301201, value:8563.000000, scaleFactor:3, devId:3
[2026-08-08 04:11:31.905 UTC] [V] OFSCtrl Rcv set p_grid:105120.000000
[2026-08-08 04:11:31.905 UTC] [V] 485DevCtl <C1:03> [01][601202][10512.000000][2][kW]
[2026-08-08 04:11:31.905 UTC] [V] SummDat SetVrmValue dev_id:3 val:105120.000000 sc:3
[2026-08-08 04:11:31.906 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:601202, value:10512.000000, scaleFactor:2, devId:3
[2026-08-08 04:11:31.906 UTC] [V] 485DevCtl <C1:03> device_type:Grid-Meter
[2026-08-08 04:11:31.928 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:31.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:31.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:31.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:31.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5582.500000 = p_th_old_:5592.400000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:31.940 UTC] [V] OFSCtrl CHG 21 batt_w:-14723.172673 = old:-14610.714173 +  kp:0.550000 * e:-198.750000 + ki:0.000000 * sume:9374241.550239 + kd:0.040000 * (e:-198.750000 - e1:-120.100000)
[2026-08-08 04:11:31.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:14723.172673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:31.940 UTC] [V] OFSCtrl CHG 29 q:-148.000000, mod(round):1.000000
[2026-08-08 04:11:31.940 UTC] [D] OFSCtrl battery ctrl val:-29.400000
[2026-08-08 04:11:31.941 UTC] [V] 485ChCtl <C3> battery limit on [-147.000000,] request.
[2026-08-08 04:11:31.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:32.004 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018166, monitor_cnt:128, bc_elapsed:16, min:10, max:40
[2026-08-08 04:11:32.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:32.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:32.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-147] set rate[-29.400000] value100[500] value-100[-500]
[2026-08-08 04:11:32.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff6d]
[2026-08-08 04:11:32.104 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018167, monitor_cnt:129, bc_elapsed:17, min:10, max:40
[2026-08-08 04:11:32.104 UTC] [V] 485DevCtl <C1:05> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:32.105 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:32.105 UTC] [V] 485ChCtl <C1> send request:omron04
[2026-08-08 04:11:32.106 UTC] [D] 485AcReq <C1:05> PutOStream [1][0800050300030014b441]
[2026-08-08 04:11:32.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.138 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:32.159 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[9] [010404100000027e85]
[2026-08-08 04:11:32.159 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [10] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:32.160 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:32.162 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounter value0
[2026-08-08 04:11:32.162 UTC] [V] 485DevCtl <C2:01> ExecuteAction set start cnt:0
[2026-08-08 04:11:32.162 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:11:32.166 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:32.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301811 UPRstat:0
[2026-08-08 04:11:32.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:32.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:32.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:32.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:32.202 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:32.220 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018168, monitor_cnt:54, bc_elapsed:3018168, min:10, max:40
[2026-08-08 04:11:32.221 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :10
[2026-08-08 04:11:32.221 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:32.222 UTC] [D] 485AcReq <C2:02> PutOStream [10][0800020413d80002f547]
[2026-08-08 04:11:32.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.238 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:32.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.339 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:32.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.439 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:32.498 UTC] [V] 485DevCtl <C1:05> AnalyzeResponseData proc restart cnt:301804 UPRstat:0
[2026-08-08 04:11:32.498 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:32.500 UTC] [D] 485DevCtl <C1:05> RcvDat status[2] len[45] [0503280000f1980000f8c20000ebd0000000610000025800033cbc00000849ffff4decfffffe39001382bac284]
[2026-08-08 04:11:32.500 UTC] [D] 485DevCtl <C1:05> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:32.500 UTC] [V] OFSCtrl Rcv set p_pv:21210.000000
[2026-08-08 04:11:32.500 UTC] [V] 485DevCtl <C1:05> [01][601259][2121.000000][2][kW]
[2026-08-08 04:11:32.500 UTC] [V] SummDat SetVrmValue dev_id:5 val:21210.000000 sc:3
[2026-08-08 04:11:32.508 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:601259, value:2121.000000, scaleFactor:2, devId:5
[2026-08-08 04:11:32.511 UTC] [V] 485DevCtl <C1:05> [01][603259][1278650.000000][1][kWh]
[2026-08-08 04:11:32.515 UTC] [V] SummDat SetVrmValue dev_id:5 val:1278650.000000 sc:1
[2026-08-08 04:11:32.515 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:603259, value:1278650.000000, scaleFactor:1, devId:5
[2026-08-08 04:11:32.520 UTC] [V] 485DevCtl <C1:05> device_type:PV-Meter
[2026-08-08 04:11:32.527 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:32.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.539 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:32.561 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[9] [020404100000024d85]
[2026-08-08 04:11:32.561 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [10] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:32.562 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:32.562 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounter value0
[2026-08-08 04:11:32.562 UTC] [V] 485DevCtl <C2:02> ExecuteAction set start cnt:0
[2026-08-08 04:11:32.562 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:11:32.568 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:32.570 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:32.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018172, monitor_cnt:134, bc_elapsed:22, min:10, max:40
[2026-08-08 04:11:32.604 UTC] [V] 485DevCtl <C1:06> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:32.604 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:32.605 UTC] [V] 485ChCtl <C1> send request:omron06
[2026-08-08 04:11:32.606 UTC] [D] 485AcReq <C1:06> PutOStream [1][08000603000000144472]
[2026-08-08 04:11:32.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.638 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:32.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:32.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.739 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:32.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.839 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:32.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:32.939 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:32.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:32.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5572.600000 = p_th_old_:5582.500000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:32.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15000.576173 = old:-14723.172673 +  kp:0.550000 * e:-483.650000 + ki:0.000000 * sume:9373757.900239 + kd:0.040000 * (e:-483.650000 - e1:-198.750000)
[2026-08-08 04:11:32.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15000.576173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:32.941 UTC] [V] OFSCtrl CHG 29 q:-151.000000, mod(round):1.000000
[2026-08-08 04:11:32.942 UTC] [D] OFSCtrl battery ctrl val:-30.000000
[2026-08-08 04:11:32.944 UTC] [V] 485ChCtl <C3> battery limit on [-150.000000,] request.
[2026-08-08 04:11:32.945 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:32.994 UTC] [V] 485DevCtl <C1:06> AnalyzeResponseData proc restart cnt:301805 UPRstat:0
[2026-08-08 04:11:32.995 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:32.996 UTC] [D] 485DevCtl <C1:06> RcvDat status[2] len[45] [060328000007f400000807000008080000a2eb0000a3e60000a5deffffff9c00000258fffdb9c4fffffa2e868d]
[2026-08-08 04:11:32.998 UTC] [D] 485DevCtl <C1:06> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:32.999 UTC] [V] OFSCtrl Rcv set p_batt:-14900.000000
[2026-08-08 04:11:33.001 UTC] [V] 485DevCtl <C1:06> [01][601237][-1490.000000][2][kW]
[2026-08-08 04:11:33.007 UTC] [V] SummDat SetVrmValue dev_id:6 val:-14900.000000 sc:3
[2026-08-08 04:11:33.016 UTC] [V] OCMgr SetMeterValue PhId:0106, branchNo:01, valueId:601237, value:-1490.000000, scaleFactor:2, devId:6
[2026-08-08 04:11:33.021 UTC] [V] 485DevCtl <C1:06> device_type:Batt-Meter
[2026-08-08 04:11:33.026 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:33.027 UTC] [D] 485ChCtl <C1> monitoring dev All Send
[2026-08-08 04:11:33.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:33.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:33.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-150] set rate[-30.000000] value100[500] value-100[-500]
[2026-08-08 04:11:33.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff6a]
[2026-08-08 04:11:33.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.138 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:33.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301812 UPRstat:0
[2026-08-08 04:11:33.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:33.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:33.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:33.201 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:33.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:33.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.238 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:33.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.339 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:33.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.439 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:33.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.539 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:33.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.638 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:33.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:33.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.738 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:33.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:33.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:33.939 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:33.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:33.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5562.700000 = p_th_old_:5572.600000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:33.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15029.049673 = old:-15000.576173 +  kp:0.550000 * e:-81.050000 + ki:0.000000 * sume:9373676.850239 + kd:0.040000 * (e:-81.050000 - e1:-483.650000)
[2026-08-08 04:11:33.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15029.049673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:33.940 UTC] [V] OFSCtrl CHG 29 q:-151.000000, mod(round):1.000000
[2026-08-08 04:11:33.940 UTC] [D] OFSCtrl battery ctrl val:-30.100000
[2026-08-08 04:11:33.941 UTC] [V] 485ChCtl <C3> battery limit on [-150.000000,] request.
[2026-08-08 04:11:33.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:34.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.039 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:34.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-150] set rate[-30.000000] value100[500] value-100[-500]
[2026-08-08 04:11:34.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff6a]
[2026-08-08 04:11:34.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.138 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301813 UPRstat:0
[2026-08-08 04:11:34.202 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:34.204 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:34.204 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:34.205 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:34.208 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:34.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.439 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.538 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.638 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.640 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018192, monitor_cnt:50, bc_elapsed:3018192, min:10, max:40
[2026-08-08 04:11:34.640 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:34.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:34.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :12
[2026-08-08 04:11:34.642 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:34.643 UTC] [D] 485AcReq <C3:01> PutOStream [12][0c00000100000006010427580001]
[2026-08-08 04:11:34.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:34.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.738 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.768 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301814 UPRstat:0
[2026-08-08 04:11:34.769 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[11] [0001000000050104020010]
[2026-08-08 04:11:34.769 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [12] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:34.769 UTC] [V] 485DevCtl <C3:01> [02][753040][1.000000][0][]
[2026-08-08 04:11:34.769 UTC] [V] SummDat SetVrmValue dev_id:9 val:1.000000 sc:0
[2026-08-08 04:11:34.770 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:02, valueId:753040, value:1.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:34.770 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:34.771 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:34.773 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:34.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:34.939 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:34.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:34.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5552.800000 = p_th_old_:5562.700000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:34.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15079.468173 = old:-15029.049673 +  kp:0.550000 * e:-90.950000 + ki:0.000000 * sume:9373585.900239 + kd:0.040000 * (e:-90.950000 - e1:-81.050000)
[2026-08-08 04:11:34.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15079.468173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:34.940 UTC] [V] OFSCtrl CHG 29 q:-151.000000, mod(round):0.000000
[2026-08-08 04:11:34.941 UTC] [D] OFSCtrl battery ctrl val:-30.200000
[2026-08-08 04:11:34.942 UTC] [V] 485ChCtl <C3> battery limit on [-151.000000,] request.
[2026-08-08 04:11:34.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:35.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.039 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:35.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-151] set rate[-30.200000] value100[500] value-100[-500]
[2026-08-08 04:11:35.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff69]
[2026-08-08 04:11:35.049 UTC] [V] CIStDb UpdateStatusData. [SELECT no, on_time, off_time FROM contact_input_status WHERE no BETWEEN '1' AND '9' ORDER BY no ASC ]
[2026-08-08 04:11:35.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.139 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301814 UPRstat:0
[2026-08-08 04:11:35.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:35.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:35.201 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:35.201 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:35.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:35.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.338 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:35.405 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:35.405 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:35.405 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:35.405 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:35.406 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:35.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:35.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:35.740 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.740 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.740 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301816 UPRstat:0
[2026-08-08 04:11:35.741 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:35.741 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040409200223b96b]
[2026-08-08 04:11:35.741 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:35.742 UTC] [V] OFSCtrl Rcv set flux_of_solar:233.600000
[2026-08-08 04:11:35.743 UTC] [V] 485DevCtl <C1:01> [01][401006][2336.000000][1][W/m2]
[2026-08-08 04:11:35.743 UTC] [V] SummDat SetVrmValue dev_id:1 val:233600.000000 sc:3
[2026-08-08 04:11:35.745 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2336.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:35.747 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:35.752 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:35.759 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:35.765 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:35.765 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:35.765 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:35.776 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:35.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:35.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:35.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:35.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:35.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:35.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:35.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:35.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:35.939 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:35.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:35.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5562.700000 = p_th_old_:5552.800000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:35.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15123.649673 = old:-15079.468173 +  kp:0.550000 * e:-81.050000 + ki:0.000000 * sume:9373504.850239 + kd:0.040000 * (e:-81.050000 - e1:-90.950000)
[2026-08-08 04:11:35.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15123.649673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:35.940 UTC] [V] OFSCtrl CHG 29 q:-152.000000, mod(round):1.000000
[2026-08-08 04:11:35.940 UTC] [D] OFSCtrl battery ctrl val:-30.200000
[2026-08-08 04:11:35.940 UTC] [V] 485ChCtl <C3> battery limit on [-151.000000,] request.
[2026-08-08 04:11:35.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:36.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.038 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:36.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-151] set rate[-30.200000] value100[500] value-100[-500]
[2026-08-08 04:11:36.044 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff69]
[2026-08-08 04:11:36.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.138 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.196 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301815 UPRstat:0
[2026-08-08 04:11:36.196 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:36.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301815 UPRstat:0
[2026-08-08 04:11:36.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:36.202 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:36.202 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:36.202 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:36.203 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:36.204 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800006068000060c0000054fb00000050000002580000f8640000027bffff4950fffffe2d001216856567]
[2026-08-08 04:11:36.204 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:36.204 UTC] [V] OFSCtrl Rcv set p_co:6350.000000, p_co_old:6380.000000
[2026-08-08 04:11:36.204 UTC] [V] 485DevCtl <C1:04> [01][601260][635.000000][2][kW]
[2026-08-08 04:11:36.204 UTC] [V] SummDat SetVrmValue dev_id:4 val:6350.000000 sc:3
[2026-08-08 04:11:36.205 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:635.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:36.205 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:36.205 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:36.206 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:36.206 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:36.206 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:36.206 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:36.206 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:36.226 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:36.231 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6350.000000
[2026-08-08 04:11:36.231 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:233.600000 < rad_th:80.000000
[2026-08-08 04:11:36.231 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301853:6350.000000
[2026-08-08 04:11:36.231 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:36.232 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:36.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.239 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:36.242 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:36.246 UTC] [D] OFSCtrl pv-pcs ctrl val:22.707506 old:22.207506
[2026-08-08 04:11:36.247 UTC] [V] OCHisDB set rate:23 t_rate:379 cnt:19
[2026-08-08 04:11:36.249 UTC] [V] 485ChCtl <C2> pv-pcs limit on [22.707506] request.
[2026-08-08 04:11:36.250 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:36.257 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:36.259 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:36.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:36.321 UTC] [D] VarInf update ofs_rate:22.707506
[2026-08-08 04:11:36.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:36.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:36.321 UTC] [D] VarInf update ofs_rate:22.707506
[2026-08-08 04:11:36.321 UTC] [D] VarInf Limit setRate[227.075058] rate[22.707506] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:36.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:22.707506 set_rate227
[2026-08-08 04:11:36.321 UTC] [D] VarInf Limit rt[2] int_set_rate[227] server_rate[22.707506] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:36.324 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00e3c626]
[2026-08-08 04:11:36.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.439 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.538 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.619 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:36.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.638 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.689 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:36 val:6350.000000
[2026-08-08 04:11:36.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:36' , 6350.000000 , 0  )
[2026-08-08 04:11:36.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:36.831 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:36.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.839 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:36.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:36.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:36.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:36.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5572.600000 = p_th_old_:5562.700000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:36.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15243.511173 = old:-15123.649673 +  kp:0.550000 * e:-208.650000 + ki:0.000000 * sume:9373296.200239 + kd:0.040000 * (e:-208.650000 - e1:-81.050000)
[2026-08-08 04:11:36.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15243.511173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:36.940 UTC] [V] OFSCtrl CHG 29 q:-153.000000, mod(round):1.000000
[2026-08-08 04:11:36.940 UTC] [D] OFSCtrl battery ctrl val:-30.500000
[2026-08-08 04:11:36.942 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:11:36.943 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:37.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:37.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:37.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:11:37.044 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:11:37.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.139 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:37.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301816 UPRstat:0
[2026-08-08 04:11:37.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:37.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:37.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:37.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:37.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:37.221 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018218, monitor_cnt:50, bc_elapsed:3018218, min:10, max:40
[2026-08-08 04:11:37.221 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:37.221 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :9
[2026-08-08 04:11:37.222 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:37.223 UTC] [D] 485AcReq <C2:01> PutOStream [9][0800010413fa001794b1]
[2026-08-08 04:11:37.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.239 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:37.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.338 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:37.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.439 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:37.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.539 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:37.594 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:37.596 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[51] [01042e1978002119b3001e1a31000fffffffffffffffff03e8ffffffff3fbf0000ffffffffffffffffffffffffffffffff34a8]
[2026-08-08 04:11:37.596 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [9] IsNormal[1] 
[2026-08-08 04:11:37.596 UTC] [V] 485DevCtl <C2:01> [04][101100][6520.000000][1][V]
[2026-08-08 04:11:37.597 UTC] [V] SummDat SetVrmValue dev_id:7 val:652000.000000 sc:3
[2026-08-08 04:11:37.597 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:04, valueId:101100, value:6520.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:37.597 UTC] [V] 485DevCtl <C2:01> [04][101101][33.000000][1][A]
[2026-08-08 04:11:37.597 UTC] [V] SummDat SetVrmValue dev_id:7 val:3300.000000 sc:3
[2026-08-08 04:11:37.598 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:04, valueId:101101, value:33.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:37.598 UTC] [V] 485DevCtl <C2:01> [05][101100][6579.000000][1][V]
[2026-08-08 04:11:37.598 UTC] [V] SummDat SetVrmValue dev_id:7 val:657900.000000 sc:3
[2026-08-08 04:11:37.598 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:05, valueId:101100, value:6579.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:37.598 UTC] [V] 485DevCtl <C2:01> [05][101101][30.000000][1][A]
[2026-08-08 04:11:37.603 UTC] [V] SummDat SetVrmValue dev_id:7 val:3000.000000 sc:3
[2026-08-08 04:11:37.614 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:05, valueId:101101, value:30.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:37.617 UTC] [V] 485DevCtl <C2:01> [06][101100][6705.000000][1][V]
[2026-08-08 04:11:37.619 UTC] [V] SummDat SetVrmValue dev_id:7 val:670500.000000 sc:3
[2026-08-08 04:11:37.624 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:06, valueId:101100, value:6705.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:37.627 UTC] [V] 485DevCtl <C2:01> [06][101101][15.000000][1][A]
[2026-08-08 04:11:37.628 UTC] [V] SummDat SetVrmValue dev_id:7 val:1500.000000 sc:3
[2026-08-08 04:11:37.632 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:06, valueId:101101, value:15.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:37.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.639 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:37.642 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:37.649 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:37.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:37.721 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018223, monitor_cnt:55, bc_elapsed:3018223, min:10, max:40
[2026-08-08 04:11:37.721 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :9
[2026-08-08 04:11:37.722 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:37.723 UTC] [D] 485AcReq <C2:02> PutOStream [9][0800020413fa00179482]
[2026-08-08 04:11:37.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.738 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:37.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.838 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:37.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:37.939 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:37.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:37.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5582.500000 = p_th_old_:5572.600000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:37.941 UTC] [V] OFSCtrl CHG 21 batt_w:-15474.115173 = old:-15243.511173 +  kp:0.550000 * e:-405.000000 + ki:0.000000 * sume:9372891.200239 + kd:0.040000 * (e:-405.000000 - e1:-208.650000)
[2026-08-08 04:11:37.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15474.115173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:37.941 UTC] [V] OFSCtrl CHG 29 q:-155.000000, mod(round):0.000000
[2026-08-08 04:11:37.941 UTC] [D] OFSCtrl battery ctrl val:-30.900000
[2026-08-08 04:11:37.942 UTC] [V] 485ChCtl <C3> battery limit on [-155.000000,] request.
[2026-08-08 04:11:37.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:38.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:38.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:38.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-155] set rate[-31.000000] value100[500] value-100[-500]
[2026-08-08 04:11:38.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff65]
[2026-08-08 04:11:38.107 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:38.108 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[51] [02042e194b002219a100201980001dffffffffffffffff03e8ffffffff40c90000ffffffffffffffffffffffffffffffff48d6]
[2026-08-08 04:11:38.108 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [9] IsNormal[1] 
[2026-08-08 04:11:38.109 UTC] [V] 485DevCtl <C2:02> [04][101100][6475.000000][1][V]
[2026-08-08 04:11:38.109 UTC] [V] SummDat SetVrmValue dev_id:8 val:647500.000000 sc:3
[2026-08-08 04:11:38.109 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:04, valueId:101100, value:6475.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:38.110 UTC] [V] 485DevCtl <C2:02> [04][101101][34.000000][1][A]
[2026-08-08 04:11:38.110 UTC] [V] SummDat SetVrmValue dev_id:8 val:3400.000000 sc:3
[2026-08-08 04:11:38.110 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:04, valueId:101101, value:34.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:38.121 UTC] [V] 485DevCtl <C2:02> [05][101100][6561.000000][1][V]
[2026-08-08 04:11:38.122 UTC] [V] SummDat SetVrmValue dev_id:8 val:656100.000000 sc:3
[2026-08-08 04:11:38.127 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:05, valueId:101100, value:6561.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:38.131 UTC] [V] 485DevCtl <C2:02> [05][101101][32.000000][1][A]
[2026-08-08 04:11:38.134 UTC] [V] SummDat SetVrmValue dev_id:8 val:3200.000000 sc:3
[2026-08-08 04:11:38.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.139 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:38.141 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:05, valueId:101101, value:32.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:38.141 UTC] [V] 485DevCtl <C2:02> [06][101100][6528.000000][1][V]
[2026-08-08 04:11:38.141 UTC] [V] SummDat SetVrmValue dev_id:8 val:652800.000000 sc:3
[2026-08-08 04:11:38.142 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:06, valueId:101100, value:6528.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:38.162 UTC] [V] 485DevCtl <C2:02> [06][101101][29.000000][1][A]
[2026-08-08 04:11:38.165 UTC] [V] SummDat SetVrmValue dev_id:8 val:2900.000000 sc:3
[2026-08-08 04:11:38.165 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:06, valueId:101101, value:29.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:38.174 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:38.174 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:38.187 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:38.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301817 UPRstat:0
[2026-08-08 04:11:38.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:38.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:38.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:38.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:38.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:38.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.239 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:38.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.338 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:38.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:38.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:38.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:38.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:38.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:38.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.838 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:38.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:38.938 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:38.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:38.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5592.400000 = p_th_old_:5582.500000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:38.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15488.211673 = old:-15474.115173 +  kp:0.550000 * e:-51.350000 + ki:0.000000 * sume:9372839.850239 + kd:0.040000 * (e:-51.350000 - e1:-405.000000)
[2026-08-08 04:11:38.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15488.211673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:38.939 UTC] [V] OFSCtrl CHG 29 q:-155.000000, mod(round):0.000000
[2026-08-08 04:11:38.940 UTC] [D] OFSCtrl battery ctrl val:-31.000000
[2026-08-08 04:11:38.941 UTC] [V] 485ChCtl <C3> battery limit on [-155.000000,] request.
[2026-08-08 04:11:38.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:39.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:39.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:39.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-155] set rate[-31.000000] value100[500] value-100[-500]
[2026-08-08 04:11:39.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff65]
[2026-08-08 04:11:39.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.139 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:39.199 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301818 UPRstat:0
[2026-08-08 04:11:39.201 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:39.203 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:39.203 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:39.204 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:39.207 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:39.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.239 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:39.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:39.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.438 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:39.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.538 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:39.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.639 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:39.641 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018242, monitor_cnt:50, bc_elapsed:3018242, min:10, max:40
[2026-08-08 04:11:39.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:39.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:39.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:39.642 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:39.643 UTC] [D] 485AcReq <C3:01> PutOStream [1][0c00000100000006010327470048]
[2026-08-08 04:11:39.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:39.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:39.808 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301819 UPRstat:0
[2026-08-08 04:11:39.832 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[153] [0001000000930103900001000200000000005500550000005500aa00a000fa000000fa0001000000000000000000000019ffffffffffffffffffffffffffffffffffffffffffff000100000000ffff0000ffffffffffffffffffffffffffffffffffff0fa0177003e800000e101388000a000a00000000195021c000000000000000550055ffe201f4ffff000000000000000000000000ff65]
[2026-08-08 04:11:39.833 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [1] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:39.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.838 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:39.839 UTC] [V] 485DevCtl <C3:01> [01][753049][0.000000][0][]
[2026-08-08 04:11:39.841 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:39.849 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753049, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:39.857 UTC] [V] OFSCtrl Rcv set BATT(t-1)[0301]:-0.310000 value:-15500.000000/50000 BATT(t-1):-0.310000 <- -15500.000000/50000
[2026-08-08 04:11:39.857 UTC] [V] 485DevCtl <C3:01> [01][753102][-155.000000][1][kW]
[2026-08-08 04:11:39.857 UTC] [V] SummDat SetVrmValue dev_id:9 val:-155.000000 sc:1
[2026-08-08 04:11:39.857 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753102, value:-155.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:39.858 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:39.859 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:39.874 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:39.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:39.938 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:39.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:39.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5582.500000 = p_th_old_:5592.400000 + lev_cd_:-0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:39.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15522.295173 = old:-15488.211673 +  kp:0.550000 * e:-61.250000 + ki:0.000000 * sume:9372778.600239 + kd:0.040000 * (e:-61.250000 - e1:-51.350000)
[2026-08-08 04:11:39.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15522.295173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:39.940 UTC] [V] OFSCtrl CHG 29 q:-156.000000, mod(round):1.000000
[2026-08-08 04:11:39.940 UTC] [D] OFSCtrl battery ctrl val:-31.000000
[2026-08-08 04:11:39.940 UTC] [V] 485ChCtl <C3> battery limit on [-155.000000,] request.
[2026-08-08 04:11:39.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->05->06->10->12->13->15->19->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:39.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:39.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-155] set rate[-31.000000] value100[500] value-100[-500]
[2026-08-08 04:11:39.942 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff65]
[2026-08-08 04:11:40.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:40.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301819 UPRstat:0
[2026-08-08 04:11:40.101 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:40.102 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:40.102 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:40.102 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:40.104 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:40.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.139 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.238 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:40.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.338 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:40.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:40.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:40.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:40.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:40.406 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:40.407 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:40.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.439 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:40.738 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301821 UPRstat:0
[2026-08-08 04:11:40.739 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:40.739 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [010404094302234975]
[2026-08-08 04:11:40.739 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:40.740 UTC] [V] OFSCtrl Rcv set flux_of_solar:237.100000
[2026-08-08 04:11:40.740 UTC] [V] 485DevCtl <C1:01> [01][401006][2371.000000][1][W/m2]
[2026-08-08 04:11:40.741 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.741 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.742 UTC] [V] SummDat SetVrmValue dev_id:1 val:237100.000000 sc:3
[2026-08-08 04:11:40.742 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2371.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:40.743 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:40.744 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:40.748 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:40.749 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:40.749 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:40.749 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:40.759 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:40.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:40.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:40.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:40.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:40.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:40.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:40.808 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:40.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.838 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:40.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:40.938 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:40.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:40.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5592.400000 = p_th_old_:5582.500000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:40.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15550.141673 = old:-15522.295173 +  kp:0.550000 * e:-51.350000 + ki:0.000000 * sume:9372727.250239 + kd:0.040000 * (e:-51.350000 - e1:-61.250000)
[2026-08-08 04:11:40.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15550.141673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:40.940 UTC] [V] OFSCtrl CHG 29 q:-156.000000, mod(round):0.000000
[2026-08-08 04:11:40.941 UTC] [D] OFSCtrl battery ctrl val:-31.100000
[2026-08-08 04:11:40.941 UTC] [V] 485ChCtl <C3> battery limit on [-156.000000,] request.
[2026-08-08 04:11:40.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:41.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:41.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:41.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-156] set rate[-31.200000] value100[500] value-100[-500]
[2026-08-08 04:11:41.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff64]
[2026-08-08 04:11:41.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.139 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:41.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301820 UPRstat:0
[2026-08-08 04:11:41.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:41.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:41.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:41.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:41.205 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:41.215 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301820 UPRstat:0
[2026-08-08 04:11:41.215 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:41.219 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [0403280000603f000060a5000054cf00000050000002580000f7d00000027affff4952fffffe2d00121685dbb5]
[2026-08-08 04:11:41.219 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:41.223 UTC] [V] OFSCtrl Rcv set p_co:6340.000000, p_co_old:6380.000000
[2026-08-08 04:11:41.228 UTC] [V] 485DevCtl <C1:04> [01][601260][634.000000][2][kW]
[2026-08-08 04:11:41.231 UTC] [V] SummDat SetVrmValue dev_id:4 val:6340.000000 sc:3
[2026-08-08 04:11:41.231 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:634.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:41.232 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:41.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.239 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:41.232 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:41.243 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:41.248 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:41.250 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:41.255 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:41.261 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:41.261 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:41.262 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6340.000000
[2026-08-08 04:11:41.262 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:237.100000 < rad_th:80.000000
[2026-08-08 04:11:41.270 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301858:6340.000000
[2026-08-08 04:11:41.271 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:41.273 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:41.283 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:41.291 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:41.297 UTC] [D] OFSCtrl pv-pcs ctrl val:23.207506 old:22.707506
[2026-08-08 04:11:41.297 UTC] [V] OCHisDB set rate:23 t_rate:402 cnt:20
[2026-08-08 04:11:41.298 UTC] [V] 485ChCtl <C2> pv-pcs limit on [23.207506] request.
[2026-08-08 04:11:41.306 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:41.307 UTC] [V] OFSCtrl Nod calc proc start.
[2026-08-08 04:11:41.310 UTC] [V] OFSCtrl ProcNodCountCalculation cur:301858 >= next:301878 diff:-20
[2026-08-08 04:11:41.313 UTC] [V] OFSCtrl ProcNodCountCalculation time not reached:-20
[2026-08-08 04:11:41.317 UTC] [V] OFSCtrl update p_co_old:6340.000000
[2026-08-08 04:11:41.317 UTC] [V] OFSCtrl Nod calc proc:
[2026-08-08 04:11:41.321 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:41.321 UTC] [D] VarInf update ofs_rate:23.207506
[2026-08-08 04:11:41.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:41.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:41.322 UTC] [D] VarInf update ofs_rate:23.207506
[2026-08-08 04:11:41.322 UTC] [D] VarInf Limit setRate[232.075058] rate[23.207506] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:41.322 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:23.207506 set_rate232
[2026-08-08 04:11:41.322 UTC] [D] VarInf Limit rt[2] int_set_rate[232] server_rate[23.207506] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:41.324 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00e887e1]
[2026-08-08 04:11:41.329 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:41.330 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:41.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.338 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:41.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.438 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:41.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:41.615 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:41.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.639 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:41.689 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:41 val:6340.000000
[2026-08-08 04:11:41.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:41' , 6340.000000 , 0  )
[2026-08-08 04:11:41.711 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:41.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:41.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:41.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:41.939 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:41.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:41.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5602.300000 = p_th_old_:5592.400000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:41.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15694.230673 = old:-15550.141673 +  kp:0.550000 * e:-247.700000 + ki:0.000000 * sume:9372479.550239 + kd:0.040000 * (e:-247.700000 - e1:-51.350000)
[2026-08-08 04:11:41.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15694.230673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:41.940 UTC] [V] OFSCtrl CHG 29 q:-157.000000, mod(round):0.000000
[2026-08-08 04:11:41.942 UTC] [D] OFSCtrl battery ctrl val:-31.400000
[2026-08-08 04:11:41.942 UTC] [V] 485ChCtl <C3> battery limit on [-157.000000,] request.
[2026-08-08 04:11:41.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:42.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:42.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:42.042 UTC] [D] VarInf Limit_Bat rt[2]set val[-157] set rate[-31.400000] value100[500] value-100[-500]
[2026-08-08 04:11:42.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff63]
[2026-08-08 04:11:42.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.139 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:42.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301821 UPRstat:0
[2026-08-08 04:11:42.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:42.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:42.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:42.201 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:42.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:42.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.239 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:42.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.339 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:42.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.439 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:42.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.538 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:42.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018272, monitor_cnt:100, bc_elapsed:22, min:10, max:40
[2026-08-08 04:11:42.604 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:42.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.639 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:42.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:42.704 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018273, monitor_cnt:101, bc_elapsed:23, min:10, max:40
[2026-08-08 04:11:42.705 UTC] [V] 485DevCtl <C1:02> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:42.705 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:42.706 UTC] [V] 485ChCtl <C1> send request:IMT01
[2026-08-08 04:11:42.706 UTC] [D] 485AcReq <C1:02> PutOStream [1][08000204000200019039]
[2026-08-08 04:11:42.720 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018273, monitor_cnt:50, bc_elapsed:3018273, min:10, max:40
[2026-08-08 04:11:42.721 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:42.721 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:42.721 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:42.723 UTC] [D] 485AcReq <C2:01> PutOStream [1][08000104138a0024d57f]
[2026-08-08 04:11:42.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.739 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:42.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.839 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:42.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:42.939 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:42.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:42.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5612.200000 = p_th_old_:5602.300000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:42.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15865.187173 = old:-15694.230673 +  kp:0.550000 * e:-306.550000 + ki:0.000000 * sume:9372173.000239 + kd:0.040000 * (e:-306.550000 - e1:-247.700000)
[2026-08-08 04:11:42.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15865.187173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:42.942 UTC] [V] OFSCtrl CHG 29 q:-159.000000, mod(round):0.000000
[2026-08-08 04:11:42.942 UTC] [D] OFSCtrl battery ctrl val:-31.700000
[2026-08-08 04:11:42.943 UTC] [V] 485ChCtl <C3> battery limit on [-159.000000,] request.
[2026-08-08 04:11:42.943 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:43.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.039 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:43.042 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:43.043 UTC] [D] VarInf Limit_Bat rt[2]set val[-159] set rate[-31.800000] value100[500] value-100[-500]
[2026-08-08 04:11:43.044 UTC] [V] 485DevCtl <C1:02> AnalyzeResponseData proc restart cnt:301816 UPRstat:0
[2026-08-08 04:11:43.044 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:43.045 UTC] [D] 485DevCtl <C1:02> RcvDat status[2] len[7] [020402021cfd99]
[2026-08-08 04:11:43.045 UTC] [D] 485DevCtl <C1:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:43.045 UTC] [V] 485DevCtl <C1:02> [01][431005][290.000000][1][°C]
[2026-08-08 04:11:43.046 UTC] [V] SummDat SetVrmValue dev_id:2 val:29000.000000 sc:3
[2026-08-08 04:11:43.046 UTC] [V] OCMgr SetMeterValue PhId:0102, branchNo:01, valueId:431005, value:290.000000, scaleFactor:1, devId:2
[2026-08-08 04:11:43.048 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff61]
[2026-08-08 04:11:43.046 UTC] [V] 485DevCtl <C1:02> device_type:
[2026-08-08 04:11:43.051 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:43.104 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018277, monitor_cnt:105, bc_elapsed:27, min:10, max:40
[2026-08-08 04:11:43.104 UTC] [V] 485DevCtl <C1:03> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:43.104 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:43.105 UTC] [V] 485ChCtl <C1> send request:omron03
[2026-08-08 04:11:43.106 UTC] [D] 485AcReq <C1:03> PutOStream [1][08000303000000144427]
[2026-08-08 04:11:43.126 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:43.128 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[77] [01044801b2fc9f00001726000001982c6000001996001f1987001f19a0001d2cad000010be10c010de009b009b009bffffffffffffffffffffffff2c010000067e000003dd0258267a820080c2]
[2026-08-08 04:11:43.128 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:43.129 UTC] [V] 485DevCtl <C2:01> [01][115202][434.000000][1][kWh]
[2026-08-08 04:11:43.129 UTC] [V] SummDat SetVrmValue dev_id:7 val:434.000000 sc:1
[2026-08-08 04:11:43.129 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:115202, value:434.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.129 UTC] [V] 485DevCtl <C2:01> [01][113202][64671.000000][0][kWh]
[2026-08-08 04:11:43.130 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671.000000 sc:0
[2026-08-08 04:11:43.130 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:113202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:43.130 UTC] [V] 485DevCtl <C2:01> [01][121005][408.000000][1][℃]
[2026-08-08 04:11:43.130 UTC] [V] SummDat SetVrmValue dev_id:7 val:40800.000000 sc:3
[2026-08-08 04:11:43.130 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121005, value:408.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.131 UTC] [V] 485DevCtl <C2:01> [01][101100][6550.000000][1][V]
[2026-08-08 04:11:43.131 UTC] [V] SummDat SetVrmValue dev_id:7 val:655000.000000 sc:3
[2026-08-08 04:11:43.131 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101100, value:6550.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.139 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:43.150 UTC] [V] 485DevCtl <C2:01> [01][101101][31.000000][1][A]
[2026-08-08 04:11:43.152 UTC] [V] SummDat SetVrmValue dev_id:7 val:3100.000000 sc:3
[2026-08-08 04:11:43.158 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101101, value:31.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.162 UTC] [V] 485DevCtl <C2:01> [02][101100][6535.000000][1][V]
[2026-08-08 04:11:43.162 UTC] [V] SummDat SetVrmValue dev_id:7 val:653500.000000 sc:3
[2026-08-08 04:11:43.165 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101100, value:6535.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.168 UTC] [V] 485DevCtl <C2:01> [02][101101][31.000000][1][A]
[2026-08-08 04:11:43.169 UTC] [V] SummDat SetVrmValue dev_id:7 val:3100.000000 sc:3
[2026-08-08 04:11:43.171 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101101, value:31.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.173 UTC] [V] 485DevCtl <C2:01> [03][101100][6560.000000][1][V]
[2026-08-08 04:11:43.174 UTC] [V] SummDat SetVrmValue dev_id:7 val:656000.000000 sc:3
[2026-08-08 04:11:43.179 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101100, value:6560.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.182 UTC] [V] 485DevCtl <C2:01> [03][101101][29.000000][1][A]
[2026-08-08 04:11:43.185 UTC] [V] SummDat SetVrmValue dev_id:7 val:2900.000000 sc:3
[2026-08-08 04:11:43.191 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101101, value:29.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.195 UTC] [V] 485DevCtl <C2:01> [01][101102][11437.000000][0][W]
[2026-08-08 04:11:43.202 UTC] [V] SummDat SetVrmValue dev_id:7 val:11437000.000000 sc:3
[2026-08-08 04:11:43.202 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101102, value:11437.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:43.203 UTC] [V] 485DevCtl <C2:01> [01][111200][4286.000000][1][V]
[2026-08-08 04:11:43.205 UTC] [V] SummDat SetVrmValue dev_id:7 val:428600.000000 sc:3
[2026-08-08 04:11:43.208 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301822 UPRstat:0
[2026-08-08 04:11:43.209 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:43.210 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:43.210 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:43.210 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:43.210 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:43.214 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111200, value:4286.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.217 UTC] [V] 485DevCtl <C2:01> [02][111200][4288.000000][1][V]
[2026-08-08 04:11:43.218 UTC] [V] SummDat SetVrmValue dev_id:7 val:428800.000000 sc:3
[2026-08-08 04:11:43.220 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111200, value:4288.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.223 UTC] [V] 485DevCtl <C2:01> [03][111200][4318.000000][1][V]
[2026-08-08 04:11:43.224 UTC] [V] SummDat SetVrmValue dev_id:7 val:431800.000000 sc:3
[2026-08-08 04:11:43.227 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111200, value:4318.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.230 UTC] [V] 485DevCtl <C2:01> [01][111201][155.000000][1][A]
[2026-08-08 04:11:43.231 UTC] [V] SummDat SetVrmValue dev_id:7 val:15500.000000 sc:3
[2026-08-08 04:11:43.235 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111201, value:155.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.239 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:43.239 UTC] [V] 485DevCtl <C2:01> [02][111201][155.000000][1][A]
[2026-08-08 04:11:43.241 UTC] [V] SummDat SetVrmValue dev_id:7 val:15500.000000 sc:3
[2026-08-08 04:11:43.246 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111201, value:155.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.249 UTC] [V] 485DevCtl <C2:01> [03][111201][155.000000][1][A]
[2026-08-08 04:11:43.250 UTC] [V] SummDat SetVrmValue dev_id:7 val:15500.000000 sc:3
[2026-08-08 04:11:43.254 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111201, value:155.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.258 UTC] [V] 485DevCtl <C2:01> [01][111202][11265.000000][0][W]
[2026-08-08 04:11:43.259 UTC] [V] SummDat SetVrmValue dev_id:7 val:11265000.000000 sc:3
[2026-08-08 04:11:43.261 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111202, value:11265.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:43.261 UTC] [V] 485DevCtl <C2:01> [01][111203][1662.000000][0][var]
[2026-08-08 04:11:43.261 UTC] [V] SummDat SetVrmValue dev_id:7 val:1662000.000000 sc:3
[2026-08-08 04:11:43.269 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111203, value:1662.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:43.272 UTC] [V] 485DevCtl <C2:01> [01][121007][989.000000][3][]
[2026-08-08 04:11:43.273 UTC] [V] SummDat SetVrmValue dev_id:7 val:989.000000 sc:3
[2026-08-08 04:11:43.276 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121007, value:989.000000, scaleFactor:3, devId:7
[2026-08-08 04:11:43.280 UTC] [V] 485DevCtl <C2:01> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:43.281 UTC] [V] SummDat SetVrmValue dev_id:7 val:60000.000000 sc:3
[2026-08-08 04:11:43.285 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:43.291 UTC] [V] 485DevCtl <C2:01> [01][114202][64671.000000][0][kWh]
[2026-08-08 04:11:43.292 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671000.000000 sc:3
[2026-08-08 04:11:43.294 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:114202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:43.294 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:43.295 UTC] [V] 485DevCtl <C2:01> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:43.295 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:43.321 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018279, monitor_cnt:56, bc_elapsed:3018279, min:10, max:40
[2026-08-08 04:11:43.321 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:43.323 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:43.323 UTC] [D] 485AcReq <C2:02> PutOStream [1][08000204138a0024d54c]
[2026-08-08 04:11:43.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.338 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:43.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.438 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:43.501 UTC] [V] 485DevCtl <C1:03> AnalyzeResponseData proc restart cnt:301816 UPRstat:0
[2026-08-08 04:11:43.502 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:43.503 UTC] [D] 485DevCtl <C1:03> RcvDat status[2] len[45] [0303280000fc170000ff090000fe4d0000217d0000268300002d0c0000005e00000258001009290000290d6988]
[2026-08-08 04:11:43.503 UTC] [D] 485DevCtl <C1:03> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:43.504 UTC] [V] 485DevCtl <C1:03> [01][301200][64535.000000][1][V]
[2026-08-08 04:11:43.504 UTC] [V] SummDat SetVrmValue dev_id:3 val:6453500.000000 sc:3
[2026-08-08 04:11:43.504 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301200, value:64535.000000, scaleFactor:1, devId:3
[2026-08-08 04:11:43.505 UTC] [V] 485DevCtl <C1:03> [01][301201][8573.000000][3][A]
[2026-08-08 04:11:43.505 UTC] [V] SummDat SetVrmValue dev_id:3 val:8573.000000 sc:3
[2026-08-08 04:11:43.505 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301201, value:8573.000000, scaleFactor:3, devId:3
[2026-08-08 04:11:43.505 UTC] [V] OFSCtrl Rcv set p_grid:105090.000000
[2026-08-08 04:11:43.506 UTC] [V] 485DevCtl <C1:03> [01][601202][10509.000000][2][kW]
[2026-08-08 04:11:43.506 UTC] [V] SummDat SetVrmValue dev_id:3 val:105090.000000 sc:3
[2026-08-08 04:11:43.506 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:601202, value:10509.000000, scaleFactor:2, devId:3
[2026-08-08 04:11:43.527 UTC] [V] 485DevCtl <C1:03> device_type:Grid-Meter
[2026-08-08 04:11:43.535 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:43.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.540 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:43.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018282, monitor_cnt:110, bc_elapsed:32, min:10, max:40
[2026-08-08 04:11:43.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.638 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:43.689 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:43.704 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018283, monitor_cnt:111, bc_elapsed:33, min:10, max:40
[2026-08-08 04:11:43.704 UTC] [V] 485DevCtl <C1:05> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:43.705 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:43.705 UTC] [V] 485ChCtl <C1> send request:omron04
[2026-08-08 04:11:43.707 UTC] [D] 485AcReq <C1:05> PutOStream [1][0800050300030014b441]
[2026-08-08 04:11:43.728 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:43.732 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[77] [02044801af022a00011719000001942dea00001a150014190d00261a0b00162d88000010c210bf10e9009f009e009fffffffffffffffffffffffff2cd900000687000003de0258267a8200a5cb]
[2026-08-08 04:11:43.733 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:43.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:43.740 UTC] [V] 485DevCtl <C2:02> [01][115202][431.000000][1][kWh]
[2026-08-08 04:11:43.740 UTC] [V] SummDat SetVrmValue dev_id:8 val:431.000000 sc:1
[2026-08-08 04:11:43.740 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:115202, value:431.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.745 UTC] [V] 485DevCtl <C2:02> [01][113202][66090.000000][0][kWh]
[2026-08-08 04:11:43.747 UTC] [V] SummDat SetVrmValue dev_id:8 val:66090.000000 sc:0
[2026-08-08 04:11:43.752 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:113202, value:66090.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:43.753 UTC] [V] 485DevCtl <C2:02> [01][121005][404.000000][1][℃]
[2026-08-08 04:11:43.753 UTC] [V] SummDat SetVrmValue dev_id:8 val:40400.000000 sc:3
[2026-08-08 04:11:43.762 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121005, value:404.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.771 UTC] [V] 485DevCtl <C2:02> [01][101100][6677.000000][1][V]
[2026-08-08 04:11:43.771 UTC] [V] SummDat SetVrmValue dev_id:8 val:667700.000000 sc:3
[2026-08-08 04:11:43.771 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101100, value:6677.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.778 UTC] [V] 485DevCtl <C2:02> [01][101101][20.000000][1][A]
[2026-08-08 04:11:43.779 UTC] [V] SummDat SetVrmValue dev_id:8 val:2000.000000 sc:3
[2026-08-08 04:11:43.782 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101101, value:20.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.785 UTC] [V] 485DevCtl <C2:02> [02][101100][6413.000000][1][V]
[2026-08-08 04:11:43.788 UTC] [V] SummDat SetVrmValue dev_id:8 val:641300.000000 sc:3
[2026-08-08 04:11:43.797 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101100, value:6413.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.801 UTC] [V] 485DevCtl <C2:02> [02][101101][38.000000][1][A]
[2026-08-08 04:11:43.805 UTC] [V] SummDat SetVrmValue dev_id:8 val:3800.000000 sc:3
[2026-08-08 04:11:43.811 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101101, value:38.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.812 UTC] [V] 485DevCtl <C2:02> [03][101100][6667.000000][1][V]
[2026-08-08 04:11:43.812 UTC] [V] SummDat SetVrmValue dev_id:8 val:666700.000000 sc:3
[2026-08-08 04:11:43.816 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101100, value:6667.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.817 UTC] [V] 485DevCtl <C2:02> [03][101101][22.000000][1][A]
[2026-08-08 04:11:43.817 UTC] [V] SummDat SetVrmValue dev_id:8 val:2200.000000 sc:3
[2026-08-08 04:11:43.818 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101101, value:22.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.822 UTC] [V] 485DevCtl <C2:02> [01][101102][11656.000000][0][W]
[2026-08-08 04:11:43.824 UTC] [V] SummDat SetVrmValue dev_id:8 val:11656000.000000 sc:3
[2026-08-08 04:11:43.828 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101102, value:11656.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:43.832 UTC] [V] 485DevCtl <C2:02> [01][111200][4290.000000][1][V]
[2026-08-08 04:11:43.834 UTC] [V] SummDat SetVrmValue dev_id:8 val:429000.000000 sc:3
[2026-08-08 04:11:43.838 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111200, value:4290.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.839 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:43.843 UTC] [V] 485DevCtl <C2:02> [02][111200][4287.000000][1][V]
[2026-08-08 04:11:43.844 UTC] [V] SummDat SetVrmValue dev_id:8 val:428700.000000 sc:3
[2026-08-08 04:11:43.848 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111200, value:4287.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.853 UTC] [V] 485DevCtl <C2:02> [03][111200][4329.000000][1][V]
[2026-08-08 04:11:43.854 UTC] [V] SummDat SetVrmValue dev_id:8 val:432900.000000 sc:3
[2026-08-08 04:11:43.858 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111200, value:4329.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.860 UTC] [V] 485DevCtl <C2:02> [01][111201][159.000000][1][A]
[2026-08-08 04:11:43.863 UTC] [V] SummDat SetVrmValue dev_id:8 val:15900.000000 sc:3
[2026-08-08 04:11:43.867 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111201, value:159.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.871 UTC] [V] 485DevCtl <C2:02> [02][111201][158.000000][1][A]
[2026-08-08 04:11:43.872 UTC] [V] SummDat SetVrmValue dev_id:8 val:15800.000000 sc:3
[2026-08-08 04:11:43.875 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111201, value:158.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.877 UTC] [V] 485DevCtl <C2:02> [03][111201][159.000000][1][A]
[2026-08-08 04:11:43.878 UTC] [V] SummDat SetVrmValue dev_id:8 val:15900.000000 sc:3
[2026-08-08 04:11:43.880 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111201, value:159.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.887 UTC] [V] 485DevCtl <C2:02> [01][111202][11481.000000][0][W]
[2026-08-08 04:11:43.887 UTC] [V] SummDat SetVrmValue dev_id:8 val:11481000.000000 sc:3
[2026-08-08 04:11:43.888 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111202, value:11481.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:43.888 UTC] [V] 485DevCtl <C2:02> [01][111203][1671.000000][0][var]
[2026-08-08 04:11:43.888 UTC] [V] SummDat SetVrmValue dev_id:8 val:1671000.000000 sc:3
[2026-08-08 04:11:43.888 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111203, value:1671.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:43.889 UTC] [V] 485DevCtl <C2:02> [01][121007][990.000000][3][]
[2026-08-08 04:11:43.889 UTC] [V] SummDat SetVrmValue dev_id:8 val:990.000000 sc:3
[2026-08-08 04:11:43.889 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121007, value:990.000000, scaleFactor:3, devId:8
[2026-08-08 04:11:43.889 UTC] [V] 485DevCtl <C2:02> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:43.889 UTC] [V] SummDat SetVrmValue dev_id:8 val:60000.000000 sc:3
[2026-08-08 04:11:43.890 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:43.890 UTC] [V] 485DevCtl <C2:02> [01][114202][66090.000000][0][kWh]
[2026-08-08 04:11:43.890 UTC] [V] SummDat SetVrmValue dev_id:8 val:66090000.000000 sc:3
[2026-08-08 04:11:43.890 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:114202, value:66090.000000, scaleFactor:0, devId:8
[2026-08-08 04:11:43.891 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:43.923 UTC] [V] 485DevCtl <C2:02> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:43.930 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:43.932 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:43.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:43.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:43.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:43.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5622.100000 = p_th_old_:5612.200000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:43.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15946.823673 = old:-15865.187173 +  kp:0.550000 * e:-159.150000 + ki:0.000000 * sume:9372013.850239 + kd:0.040000 * (e:-159.150000 - e1:-306.550000)
[2026-08-08 04:11:43.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15946.823673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:43.940 UTC] [V] OFSCtrl CHG 29 q:-160.000000, mod(round):1.000000
[2026-08-08 04:11:43.941 UTC] [D] OFSCtrl battery ctrl val:-31.900000
[2026-08-08 04:11:43.941 UTC] [V] 485ChCtl <C3> battery limit on [-159.000000,] request.
[2026-08-08 04:11:43.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:44.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.038 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:44.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-159] set rate[-31.800000] value100[500] value-100[-500]
[2026-08-08 04:11:44.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff61]
[2026-08-08 04:11:44.098 UTC] [V] 485DevCtl <C1:05> AnalyzeResponseData proc restart cnt:301816 UPRstat:0
[2026-08-08 04:11:44.098 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:44.099 UTC] [D] 485DevCtl <C1:05> RcvDat status[2] len[45] [0503280000fe30000105770000f8bb000000620000025800036aef000008bfffff4e9bfffffe3a001382bb7308]
[2026-08-08 04:11:44.100 UTC] [D] 485DevCtl <C1:05> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:44.100 UTC] [V] OFSCtrl Rcv set p_pv:22390.000000
[2026-08-08 04:11:44.101 UTC] [V] 485DevCtl <C1:05> [01][601259][2239.000000][2][kW]
[2026-08-08 04:11:44.101 UTC] [V] SummDat SetVrmValue dev_id:5 val:22390.000000 sc:3
[2026-08-08 04:11:44.118 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:601259, value:2239.000000, scaleFactor:2, devId:5
[2026-08-08 04:11:44.119 UTC] [V] 485DevCtl <C1:05> [01][603259][1278651.000000][1][kWh]
[2026-08-08 04:11:44.119 UTC] [V] SummDat SetVrmValue dev_id:5 val:1278651.000000 sc:1
[2026-08-08 04:11:44.119 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:603259, value:1278651.000000, scaleFactor:1, devId:5
[2026-08-08 04:11:44.119 UTC] [V] 485DevCtl <C1:05> device_type:PV-Meter
[2026-08-08 04:11:44.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.148 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:44.204 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018288, monitor_cnt:116, bc_elapsed:38, min:10, max:40
[2026-08-08 04:11:44.204 UTC] [V] 485DevCtl <C1:06> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:44.204 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:44.205 UTC] [V] 485ChCtl <C1> send request:omron06
[2026-08-08 04:11:44.206 UTC] [D] 485AcReq <C1:06> PutOStream [1][08000603000000144472]
[2026-08-08 04:11:44.208 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301823 UPRstat:0
[2026-08-08 04:11:44.210 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:44.212 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:44.212 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:44.212 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:44.213 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:44.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.538 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.595 UTC] [V] 485DevCtl <C1:06> AnalyzeResponseData proc restart cnt:301817 UPRstat:0
[2026-08-08 04:11:44.595 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:44.598 UTC] [D] 485DevCtl <C1:06> RcvDat status[2] len[45] [060328000007f400000806000008070000b08f0000b1520000b348ffffff9c00000258fffd8a22fffff9b4deb9]
[2026-08-08 04:11:44.598 UTC] [D] 485DevCtl <C1:06> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:44.599 UTC] [V] OFSCtrl Rcv set p_batt:-16120.000000
[2026-08-08 04:11:44.599 UTC] [V] 485DevCtl <C1:06> [01][601237][-1612.000000][2][kW]
[2026-08-08 04:11:44.599 UTC] [V] SummDat SetVrmValue dev_id:6 val:-16120.000000 sc:3
[2026-08-08 04:11:44.599 UTC] [V] OCMgr SetMeterValue PhId:0106, branchNo:01, valueId:601237, value:-1612.000000, scaleFactor:2, devId:6
[2026-08-08 04:11:44.612 UTC] [V] 485DevCtl <C1:06> device_type:Batt-Meter
[2026-08-08 04:11:44.613 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:44.622 UTC] [D] 485ChCtl <C1> monitoring dev All Send
[2026-08-08 04:11:44.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.638 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.641 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018292, monitor_cnt:50, bc_elapsed:3018292, min:10, max:40
[2026-08-08 04:11:44.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:44.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:44.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:44.643 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:44.643 UTC] [D] 485AcReq <C3:01> PutOStream [2][0c0000010000000601042751005e]
[2026-08-08 04:11:44.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:44.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.808 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301824 UPRstat:0
[2026-08-08 04:11:44.838 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[197] [0001000000bf0104bc0000ffffffffffff018700000000001000000000000000000000000000000000000000ae0032009a0000000100010001ffffffffffffffffffffffffffffffffffffffff000100000001000000010000ffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffff000101f40000ff62ffff0000000003e89ddc00009126000002230000001b0000]
[2026-08-08 04:11:44.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.839 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.838 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [2] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:44.862 UTC] [V] 485DevCtl <C3:01> [02][753049][0.000000][0][]
[2026-08-08 04:11:44.865 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:44.871 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:02, valueId:753049, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.871 UTC] [V] 485DevCtl <C3:01> [01][753040][16.000000][0][]
[2026-08-08 04:11:44.871 UTC] [V] SummDat SetVrmValue dev_id:9 val:16.000000 sc:0
[2026-08-08 04:11:44.887 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753040, value:16.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.892 UTC] [V] 485DevCtl <C3:01> [01][753053][0.000000][0][]
[2026-08-08 04:11:44.896 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:44.900 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.902 UTC] [V] 485DevCtl <C3:01> [02][753053][0.000000][0][]
[2026-08-08 04:11:44.903 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:44.907 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:02, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.916 UTC] [V] 485DevCtl <C3:01> [03][753053][0.000000][0][]
[2026-08-08 04:11:44.922 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:44.922 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:03, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.929 UTC] [V] 485DevCtl <C3:01> [04][753053][0.000000][0][]
[2026-08-08 04:11:44.929 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:44.930 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:04, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:44.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:44.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:44.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5632.000000 = p_th_old_:5622.100000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:44.940 UTC] [V] OFSCtrl CHG 21 batt_w:-16028.515173 = old:-15946.823673 +  kp:0.550000 * e:-149.250000 + ki:0.000000 * sume:9371864.600239 + kd:0.040000 * (e:-149.250000 - e1:-159.150000)
[2026-08-08 04:11:44.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16028.515173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:44.940 UTC] [V] OFSCtrl CHG 29 q:-161.000000, mod(round):1.000000
[2026-08-08 04:11:44.940 UTC] [D] OFSCtrl battery ctrl val:-32.100000
[2026-08-08 04:11:44.940 UTC] [V] 485ChCtl <C3> battery limit on [-160.000000,] request.
[2026-08-08 04:11:44.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:44.947 UTC] [V] 485DevCtl <C3:01> [01][716202][500.000000][1][kW]
[2026-08-08 04:11:44.947 UTC] [V] SummDat SetVrmValue dev_id:9 val:50000.000000 sc:3
[2026-08-08 04:11:44.948 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:716202, value:500.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:44.960 UTC] [V] 485DevCtl <C3:01> [01][711102][-158.000000][1][kW]
[2026-08-08 04:11:44.960 UTC] [V] SummDat SetVrmValue dev_id:9 val:-15800.000000 sc:3
[2026-08-08 04:11:44.960 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:711102, value:-158.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:44.961 UTC] [V] 485DevCtl <C3:01> [01][703102][40412.000000][0][kWh]
[2026-08-08 04:11:44.961 UTC] [V] SummDat SetVrmValue dev_id:9 val:40412.000000 sc:0
[2026-08-08 04:11:44.982 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:703102, value:40412.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:44.985 UTC] [V] 485DevCtl <C3:01> [01][713102][37158.000000][0][kWh]
[2026-08-08 04:11:44.987 UTC] [V] SummDat SetVrmValue dev_id:9 val:37158.000000 sc:0
[2026-08-08 04:11:44.988 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:713102, value:37158.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:45.007 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:45.013 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:45.020 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:45.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.038 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:45.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:45.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-160] set rate[-32.000000] value100[500] value-100[-500]
[2026-08-08 04:11:45.044 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff60]
[2026-08-08 04:11:45.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.138 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:45.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301824 UPRstat:0
[2026-08-08 04:11:45.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:45.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:45.202 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:45.202 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:45.202 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:45.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:45.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:45.387 UTC] [V] OC485DevMgr TargetPowerPolling 
[2026-08-08 04:11:45.387 UTC] [V] OC485DevMgr TargetPowerPolling Target power no ud current[20260808040000]now[20260808041145]next[20260808043000]
[2026-08-08 04:11:45.387 UTC] [V] OCMgr UpdateExtCurrentTarget call
[2026-08-08 04:11:45.387 UTC] [V] OCMgr UpdateExtSchedule call
[2026-08-08 04:11:45.388 UTC] [V] OCMgr UpdateExtSchedule file none. ext rate:-1, time:20200101000000
[2026-08-08 04:11:45.388 UTC] [V] OCMgr IsPvocdScheduleError 0
[2026-08-08 04:11:45.388 UTC] [V] OCMgr UpdateExtCurrentTarget check schedule:0, ext rate:-1
[2026-08-08 04:11:45.389 UTC] [V] OCMgr CalcOutputControlPower pow:99.000000, rate:100, cap:99.000000
[2026-08-08 04:11:45.389 UTC] [V] OCMgr IsPvocdScheduleError 0
[2026-08-08 04:11:45.389 UTC] [D] OCMgr UpdateExtCurrentTarget external none, in_pow:99.000000, 99.000000
[2026-08-08 04:11:45.389 UTC] [V] OCMgr CalcOutputControlRate rate:100, pow:99.000000, cap:99.000000, rate_out:99.000000
[2026-08-08 04:11:45.389 UTC] [V] OCMgr WriteExtSchedule dat:100,20260808133000
[2026-08-08 04:11:45.390 UTC] [V] FlUtil write csv file[/media/sdcard/solajithome/Log/modbus/ExecSchedulePath/ExecEmsSchedule.csv] result:1
[2026-08-08 04:11:45.391 UTC] [V] OCMgr now time:20260808040000, power_value:99.000000, rt:0
[2026-08-08 04:11:45.391 UTC] [V] OCMgr next time:20260808043000, power_value:99.000000, rt:0
[2026-08-08 04:11:45.391 UTC] [V] OCMgr GetCurrentTargetPower current target:99.000000
[2026-08-08 04:11:45.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:45.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:45.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:45.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:45.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:45.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:45.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:45.428 UTC] [V] OCMgr CalcOutputControlRate rate:100, pow:99.000000, cap:99.000000, rate_out:99.000000
[2026-08-08 04:11:45.428 UTC] [V] OCMgr IsPvocdCommunication 1
[2026-08-08 04:11:45.428 UTC] [V] OCMgr IsPvocdScheduleError 0
[2026-08-08 04:11:45.428 UTC] [V] OCMgr UpdateActiveMode mode:OFS conditions:output rate 100.
[2026-08-08 04:11:45.428 UTC] [V] LgMgr change mode OFS -> OFS
[2026-08-08 04:11:45.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:45.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:45.552 UTC] [I] Wdog command:/usr/bin/touch "/mnt/system/check/pvsl"
[2026-08-08 04:11:45.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:45.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:45.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:45.743 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301826 UPRstat:0
[2026-08-08 04:11:45.743 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:45.744 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040409100223b964]
[2026-08-08 04:11:45.744 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:45.745 UTC] [V] OFSCtrl Rcv set flux_of_solar:232.000000
[2026-08-08 04:11:45.745 UTC] [V] 485DevCtl <C1:01> [01][401006][2320.000000][1][W/m2]
[2026-08-08 04:11:45.745 UTC] [V] SummDat SetVrmValue dev_id:1 val:232000.000000 sc:3
[2026-08-08 04:11:45.746 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2320.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:45.746 UTC] [V] 485DevCtl <C1:01> [01][421005][297.000000][1][℃]
[2026-08-08 04:11:45.746 UTC] [V] SummDat SetVrmValue dev_id:1 val:29700.000000 sc:3
[2026-08-08 04:11:45.759 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:297.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:45.759 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:45.759 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:45.760 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:45.780 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:45.805 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:45.806 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:45.806 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:45.806 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:45.806 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:45.807 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:45.808 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:45.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.839 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:45.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:45.938 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:45.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:45.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5641.900000 = p_th_old_:5632.000000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:45.939 UTC] [V] OFSCtrl CHG 21 batt_w:-16023.636673 = old:-16028.515173 +  kp:0.550000 * e:-1.850000 + ki:0.000000 * sume:9371862.750239 + kd:0.040000 * (e:-1.850000 - e1:-149.250000)
[2026-08-08 04:11:45.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16023.636673 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:45.940 UTC] [V] OFSCtrl CHG 29 q:-161.000000, mod(round):1.000000
[2026-08-08 04:11:45.940 UTC] [D] OFSCtrl battery ctrl val:-32.000000
[2026-08-08 04:11:45.940 UTC] [V] 485ChCtl <C3> battery limit on [-160.000000,] request.
[2026-08-08 04:11:45.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:45.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:45.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-160] set rate[-32.000000] value100[500] value-100[-500]
[2026-08-08 04:11:45.944 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff60]
[2026-08-08 04:11:46.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.038 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:46.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301825 UPRstat:0
[2026-08-08 04:11:46.101 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:46.102 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:46.102 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:46.103 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:46.103 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:46.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.138 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:46.207 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301825 UPRstat:0
[2026-08-08 04:11:46.207 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:46.209 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [0403280000605e000060be000054d700000050000002580000f8630000027bffff4957fffffe2d0012168590e7]
[2026-08-08 04:11:46.209 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:46.209 UTC] [V] OFSCtrl Rcv set p_co:6350.000000, p_co_old:6340.000000
[2026-08-08 04:11:46.210 UTC] [V] 485DevCtl <C1:04> [01][601260][635.000000][2][kW]
[2026-08-08 04:11:46.210 UTC] [V] SummDat SetVrmValue dev_id:4 val:6350.000000 sc:3
[2026-08-08 04:11:46.210 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:635.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:46.210 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:46.211 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:46.211 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:46.211 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:46.211 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:46.211 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:46.211 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:46.212 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:46.212 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6350.000000
[2026-08-08 04:11:46.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.239 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:46.243 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:232.000000 < rad_th:80.000000
[2026-08-08 04:11:46.244 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301863:6350.000000
[2026-08-08 04:11:46.244 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:46.244 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:46.255 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:46.255 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:46.256 UTC] [D] OFSCtrl pv-pcs ctrl val:23.707506 old:23.207506
[2026-08-08 04:11:46.256 UTC] [V] OCHisDB set rate:24 t_rate:426 cnt:21
[2026-08-08 04:11:46.256 UTC] [V] 485ChCtl <C2> pv-pcs limit on [23.707506] request.
[2026-08-08 04:11:46.256 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:46.278 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:46.278 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:46.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:46.321 UTC] [D] VarInf update ofs_rate:23.707506
[2026-08-08 04:11:46.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:46.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:46.321 UTC] [D] VarInf update ofs_rate:23.707506
[2026-08-08 04:11:46.321 UTC] [D] VarInf Limit setRate[237.075058] rate[23.707506] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:46.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:23.707506 set_rate237
[2026-08-08 04:11:46.321 UTC] [D] VarInf Limit rt[2] int_set_rate[237] server_rate[23.707506] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:46.323 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00ed47e2]
[2026-08-08 04:11:46.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:46.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:46.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:46.615 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:46.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.639 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:46.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:46 val:6350.000000
[2026-08-08 04:11:46.693 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:46' , 6350.000000 , 0  )
[2026-08-08 04:11:46.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.738 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:46.777 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:46.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:46.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:46.938 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:46.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:46.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5651.800000 = p_th_old_:5641.900000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:46.939 UTC] [V] OFSCtrl CHG 21 batt_w:-16181.063173 = old:-16023.636673 +  kp:0.550000 * e:-266.950000 + ki:0.000000 * sume:9371595.800239 + kd:0.040000 * (e:-266.950000 - e1:-1.850000)
[2026-08-08 04:11:46.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16181.063173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:46.940 UTC] [V] OFSCtrl CHG 29 q:-162.000000, mod(round):0.000000
[2026-08-08 04:11:46.940 UTC] [D] OFSCtrl battery ctrl val:-32.400000
[2026-08-08 04:11:46.940 UTC] [V] 485ChCtl <C3> battery limit on [-162.000000,] request.
[2026-08-08 04:11:46.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:46.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:46.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-162] set rate[-32.400000] value100[500] value-100[-500]
[2026-08-08 04:11:46.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff5e]
[2026-08-08 04:11:47.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:47.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301826 UPRstat:0
[2026-08-08 04:11:47.101 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:47.102 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:47.102 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:47.102 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:47.102 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:47.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.139 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:47.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.239 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:11:47.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.339 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:47.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.438 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:47.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.538 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:47.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.639 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:47.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:47.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.739 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:47.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.839 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:47.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:47.939 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:47.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:47.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5661.700000 = p_th_old_:5651.800000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:47.939 UTC] [V] OFSCtrl CHG 21 batt_w:-16362.607173 = old:-16181.063173 +  kp:0.550000 * e:-325.800000 + ki:0.000000 * sume:9371270.000239 + kd:0.040000 * (e:-325.800000 - e1:-266.950000)
[2026-08-08 04:11:47.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16362.607173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:47.940 UTC] [V] OFSCtrl CHG 29 q:-164.000000, mod(round):0.000000
[2026-08-08 04:11:47.940 UTC] [D] OFSCtrl battery ctrl val:-32.700000
[2026-08-08 04:11:47.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:47.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-164] set rate[-32.800000] value100[500] value-100[-500]
[2026-08-08 04:11:47.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff5c]
[2026-08-08 04:11:47.940 UTC] [V] 485ChCtl <C3> battery limit on [-164.000000,] request.
[2026-08-08 04:11:47.946 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:48.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.039 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:48.098 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301827 UPRstat:0
[2026-08-08 04:11:48.100 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:48.100 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:48.100 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:48.100 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:48.101 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:48.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.138 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:48.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.238 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:11:48.320 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018329, monitor_cnt:50, bc_elapsed:3018329, min:10, max:40
[2026-08-08 04:11:48.321 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:48.321 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:48.322 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:48.323 UTC] [D] 485AcReq <C2:01> PutOStream [2][0800010413d80002f574]
[2026-08-08 04:11:48.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:48.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:48.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:48.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:48.644 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[9] [010404100000027e85]
[2026-08-08 04:11:48.645 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [2] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:48.645 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:48.646 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounter value0
[2026-08-08 04:11:48.646 UTC] [V] 485DevCtl <C2:01> ExecuteAction set start cnt:0
[2026-08-08 04:11:48.646 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:11:48.647 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:48.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:48.721 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018333, monitor_cnt:54, bc_elapsed:3018333, min:10, max:40
[2026-08-08 04:11:48.721 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:11:48.722 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:48.722 UTC] [D] 485AcReq <C2:02> PutOStream [2][0800020413d80002f547]
[2026-08-08 04:11:48.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.738 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:48.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:48.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:48.939 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:48.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:48.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5671.600000 = p_th_old_:5661.700000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:48.940 UTC] [V] OFSCtrl CHG 21 batt_w:-16373.706173 = old:-16362.607173 +  kp:0.550000 * e:-40.900000 + ki:0.000000 * sume:9371229.100239 + kd:0.040000 * (e:-40.900000 - e1:-325.800000)
[2026-08-08 04:11:48.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16373.706173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:48.940 UTC] [V] OFSCtrl CHG 29 q:-164.000000, mod(round):0.000000
[2026-08-08 04:11:48.940 UTC] [D] OFSCtrl battery ctrl val:-32.700000
[2026-08-08 04:11:48.941 UTC] [V] 485ChCtl <C3> battery limit on [-164.000000,] request.
[2026-08-08 04:11:48.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:49.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.039 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:49.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:49.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-164] set rate[-32.800000] value100[500] value-100[-500]
[2026-08-08 04:11:49.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff5c]
[2026-08-08 04:11:49.049 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[9] [020404100000024d85]
[2026-08-08 04:11:49.049 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [2] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:49.049 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:49.050 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounter value0
[2026-08-08 04:11:49.050 UTC] [V] 485DevCtl <C2:02> ExecuteAction set start cnt:0
[2026-08-08 04:11:49.051 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:11:49.052 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:49.052 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:49.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.139 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:49.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301828 UPRstat:0
[2026-08-08 04:11:49.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:49.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:49.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:49.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:49.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:49.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.239 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:49.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.338 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:49.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.438 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:49.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1171->1171] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.539 UTC] [V] OFSCtrl angif value:1171 power_val_:5506.250000
[2026-08-08 04:11:49.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:49.640 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018342, monitor_cnt:50, bc_elapsed:3018342, min:10, max:40
[2026-08-08 04:11:49.640 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:49.640 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:49.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :3
[2026-08-08 04:11:49.641 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:49.642 UTC] [D] 485AcReq <C3:01> PutOStream [3][0c00000100000006010435260018]
[2026-08-08 04:11:49.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:49.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.739 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:49.758 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301829 UPRstat:0
[2026-08-08 04:11:49.760 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[57] [0001000000330104301f4500c1026203e81f45026200010001ffff8000ffff013b013bffff008c008c00640064ffff823281e201360122004f]
[2026-08-08 04:11:49.760 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [3] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:49.760 UTC] [V] 485DevCtl <C3:01> [01][721100][8005.000000][1][V]
[2026-08-08 04:11:49.761 UTC] [V] SummDat SetVrmValue dev_id:9 val:800500.000000 sc:3
[2026-08-08 04:11:49.761 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721100, value:8005.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:49.768 UTC] [V] 485DevCtl <C3:01> [01][721101][193.000000][1][A]
[2026-08-08 04:11:49.768 UTC] [V] SummDat SetVrmValue dev_id:9 val:19300.000000 sc:3
[2026-08-08 04:11:49.768 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721101, value:193.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:49.769 UTC] [V] OFSCtrl change set SOC(t):61.000000 drive cnt:1
[2026-08-08 04:11:49.769 UTC] [V] OFSCtrl Rcv set soc[0301]:61.000000
[2026-08-08 04:11:49.769 UTC] [V] 485DevCtl <C3:01> [01][721035][610.000000][1][%]
[2026-08-08 04:11:49.769 UTC] [V] SummDat SetVrmValue dev_id:9 val:61000.000000 sc:3
[2026-08-08 04:11:49.769 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721035, value:610.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:49.770 UTC] [V] 485DevCtl <C3:01> [01][721036][1000.000000][1][%]
[2026-08-08 04:11:49.770 UTC] [V] SummDat SetVrmValue dev_id:9 val:100000.000000 sc:3
[2026-08-08 04:11:49.770 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721036, value:1000.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:49.770 UTC] [V] 485DevCtl <C3:01> [01][721030][33330.000000][4][V]
[2026-08-08 04:11:49.770 UTC] [V] SummDat SetVrmValue dev_id:9 val:3333.000000 sc:3
[2026-08-08 04:11:49.771 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721030, value:33330.000000, scaleFactor:4, devId:9
[2026-08-08 04:11:49.771 UTC] [V] 485DevCtl <C3:01> [01][721031][33250.000000][4][V]
[2026-08-08 04:11:49.771 UTC] [V] SummDat SetVrmValue dev_id:9 val:3325.000000 sc:3
[2026-08-08 04:11:49.771 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721031, value:33250.000000, scaleFactor:4, devId:9
[2026-08-08 04:11:49.772 UTC] [V] 485DevCtl <C3:01> [01][721032][310.000000][1][℃]
[2026-08-08 04:11:49.772 UTC] [V] SummDat SetVrmValue dev_id:9 val:31000.000000 sc:3
[2026-08-08 04:11:49.772 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721032, value:310.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:49.802 UTC] [V] 485DevCtl <C3:01> [01][721033][290.000000][1][℃]
[2026-08-08 04:11:49.808 UTC] [V] SummDat SetVrmValue dev_id:9 val:29000.000000 sc:3
[2026-08-08 04:11:49.818 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:721033, value:290.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:49.819 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:49.820 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:49.832 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:49.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:49.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:49.938 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:49.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:49.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5681.500000 = p_th_old_:5671.600000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:49.939 UTC] [V] OFSCtrl CHG 21 batt_w:-16390.360173 = old:-16373.706173 +  kp:0.550000 * e:-31.000000 + ki:0.000000 * sume:9371198.100239 + kd:0.040000 * (e:-31.000000 - e1:-40.900000)
[2026-08-08 04:11:49.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16390.360173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:49.940 UTC] [V] OFSCtrl CHG 29 q:-164.000000, mod(round):0.000000
[2026-08-08 04:11:49.940 UTC] [D] OFSCtrl battery ctrl val:-32.800000
[2026-08-08 04:11:49.940 UTC] [V] 485ChCtl <C3> battery limit on [-164.000000,] request.
[2026-08-08 04:11:49.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:49.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:49.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-164] set rate[-32.800000] value100[500] value-100[-500]
[2026-08-08 04:11:49.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff5c]
[2026-08-08 04:11:50.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.039 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:50.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301829 UPRstat:0
[2026-08-08 04:11:50.091 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:50.091 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:50.091 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:50.091 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:50.092 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:50.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.139 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.239 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.338 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:50.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:50.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:50.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:50.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:50.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:50.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:50.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.438 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:50.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.639 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:50.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.739 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.742 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301831 UPRstat:0
[2026-08-08 04:11:50.743 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:50.743 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040408c00224f8a3]
[2026-08-08 04:11:50.743 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:50.744 UTC] [V] OFSCtrl Rcv set flux_of_solar:224.000000
[2026-08-08 04:11:50.744 UTC] [V] 485DevCtl <C1:01> [01][401006][2240.000000][1][W/m2]
[2026-08-08 04:11:50.744 UTC] [V] SummDat SetVrmValue dev_id:1 val:224000.000000 sc:3
[2026-08-08 04:11:50.744 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2240.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:50.745 UTC] [V] 485DevCtl <C1:01> [01][421005][298.000000][1][℃]
[2026-08-08 04:11:50.745 UTC] [V] SummDat SetVrmValue dev_id:1 val:29800.000000 sc:3
[2026-08-08 04:11:50.745 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:298.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:50.758 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:50.758 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:50.759 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:50.759 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:50.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:50.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:50.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:50.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:50.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:50.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:50.808 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:50.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:50.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:50.938 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:50.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:50.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5691.400000 = p_th_old_:5681.500000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:50.939 UTC] [V] OFSCtrl CHG 21 batt_w:-16401.569173 = old:-16390.360173 +  kp:0.550000 * e:-21.100000 + ki:0.000000 * sume:9371177.000239 + kd:0.040000 * (e:-21.100000 - e1:-31.000000)
[2026-08-08 04:11:50.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16401.569173 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:50.941 UTC] [V] OFSCtrl CHG 29 q:-165.000000, mod(round):1.000000
[2026-08-08 04:11:50.941 UTC] [D] OFSCtrl battery ctrl val:-32.800000
[2026-08-08 04:11:50.941 UTC] [V] 485ChCtl <C3> battery limit on [-164.000000,] request.
[2026-08-08 04:11:50.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:51.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.039 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:51.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:51.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-164] set rate[-32.800000] value100[500] value-100[-500]
[2026-08-08 04:11:51.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff5c]
[2026-08-08 04:11:51.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.139 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:51.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301830 UPRstat:0
[2026-08-08 04:11:51.189 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:51.192 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:51.193 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:51.193 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:51.196 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:51.206 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301830 UPRstat:0
[2026-08-08 04:11:51.206 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:51.208 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800006035000060ad000054ba00000050000002580000f85e0000027bffff49c1fffffe2e00121685666f]
[2026-08-08 04:11:51.208 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:51.208 UTC] [V] OFSCtrl Rcv set p_co:6350.000000, p_co_old:6340.000000
[2026-08-08 04:11:51.209 UTC] [V] 485DevCtl <C1:04> [01][601260][635.000000][2][kW]
[2026-08-08 04:11:51.209 UTC] [V] SummDat SetVrmValue dev_id:4 val:6350.000000 sc:3
[2026-08-08 04:11:51.209 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:635.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:51.209 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:51.210 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:51.210 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:51.210 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:51.210 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:51.210 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:51.210 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:51.211 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:51.211 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6350.000000
[2026-08-08 04:11:51.211 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:224.000000 < rad_th:80.000000
[2026-08-08 04:11:51.211 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301868:6350.000000
[2026-08-08 04:11:51.211 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:51.212 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:51.212 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:51.231 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:51.234 UTC] [D] OFSCtrl pv-pcs ctrl val:23.105455 old:23.707506
[2026-08-08 04:11:51.235 UTC] [V] OCHisDB set rate:23 t_rate:449 cnt:22
[2026-08-08 04:11:51.237 UTC] [V] 485ChCtl <C2> pv-pcs limit on [23.105455] request.
[2026-08-08 04:11:51.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.238 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:51.243 UTC] [V] OFSCtrl save reduction C[W]:256.293514 = total[W]:99000.000000* diff[]:0.602052 / 100.0 * Kc:0.430000
[2026-08-08 04:11:51.245 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:51.246 UTC] [V] OFSCtrl Nod calc proc start.
[2026-08-08 04:11:51.249 UTC] [V] OFSCtrl ProcNodCountCalculation cur:301868 >= next:301878 diff:-10
[2026-08-08 04:11:51.251 UTC] [V] OFSCtrl ProcNodCountCalculation time not reached:-10
[2026-08-08 04:11:51.253 UTC] [V] OFSCtrl update p_co_old:6350.000000
[2026-08-08 04:11:51.254 UTC] [V] OFSCtrl Nod calc proc:
[2026-08-08 04:11:51.261 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:51.262 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:51.321 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:51.321 UTC] [D] VarInf update ofs_rate:23.105455
[2026-08-08 04:11:51.322 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:51.322 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:51.322 UTC] [D] VarInf update ofs_rate:23.105455
[2026-08-08 04:11:51.322 UTC] [D] VarInf Limit setRate[231.054550] rate[23.105455] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:51.322 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:23.105455 set_rate231
[2026-08-08 04:11:51.322 UTC] [D] VarInf Limit rt[2] int_set_rate[231] server_rate[23.105455] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:51.325 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00e7c7e5]
[2026-08-08 04:11:51.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.338 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:51.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:51.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:51.614 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:51.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:51.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:51 val:6350.000000
[2026-08-08 04:11:51.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:51' , 6350.000000 , 0  )
[2026-08-08 04:11:51.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.738 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:51.810 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:51.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.839 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:51.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1169->1169] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:51.939 UTC] [V] OFSCtrl angif value:1169 power_val_:5368.750000
[2026-08-08 04:11:51.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:51.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5701.300000 = p_th_old_:5691.400000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:51.940 UTC] [V] OFSCtrl CHG 21 batt_w:-16204.520673 = old:-16401.569173 +  kp:0.550000 * e:332.550000 + ki:0.000000 * sume:9371509.550239 + kd:0.040000 * (e:332.550000 - e1:-21.100000)
[2026-08-08 04:11:51.940 UTC] [V] OFSCtrl CHG 21 update batt_w:-15948.227159 += C:256.293514
[2026-08-08 04:11:51.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15948.227159 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:51.941 UTC] [V] OFSCtrl CHG 29 q:-160.000000, mod(round):1.000000
[2026-08-08 04:11:51.941 UTC] [D] OFSCtrl battery ctrl val:-31.900000
[2026-08-08 04:11:51.942 UTC] [V] 485ChCtl <C3> battery limit on [-159.000000,] request.
[2026-08-08 04:11:51.943 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:52.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1169->1169] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.038 UTC] [V] OFSCtrl angif value:1169 power_val_:5368.750000
[2026-08-08 04:11:52.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:52.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-159] set rate[-31.800000] value100[500] value-100[-500]
[2026-08-08 04:11:52.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff61]
[2026-08-08 04:11:52.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1169->1169] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.139 UTC] [V] OFSCtrl angif value:1169 power_val_:5368.750000
[2026-08-08 04:11:52.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301831 UPRstat:0
[2026-08-08 04:11:52.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:52.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:52.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:52.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:52.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:52.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.239 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:52.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1169->1169] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.339 UTC] [V] OFSCtrl angif value:1169 power_val_:5368.750000
[2026-08-08 04:11:52.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.439 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:52.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.538 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:52.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.638 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:52.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:52.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.739 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:52.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.839 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:11:52.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:52.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:52.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:52.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5711.200000 = p_th_old_:5701.300000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:52.940 UTC] [V] OFSCtrl CHG 21 batt_w:-16002.858659 = old:-15948.227159 +  kp:0.550000 * e:-70.050000 + ki:0.000000 * sume:9371439.500239 + kd:0.040000 * (e:-70.050000 - e1:332.550000)
[2026-08-08 04:11:52.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:16002.858659 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:52.941 UTC] [V] OFSCtrl CHG 29 q:-161.000000, mod(round):1.000000
[2026-08-08 04:11:52.941 UTC] [D] OFSCtrl battery ctrl val:-32.000000
[2026-08-08 04:11:52.941 UTC] [V] 485ChCtl <C3> battery limit on [-160.000000,] request.
[2026-08-08 04:11:52.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:53.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.038 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:53.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:53.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-160] set rate[-32.000000] value100[500] value-100[-500]
[2026-08-08 04:11:53.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff60]
[2026-08-08 04:11:53.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.139 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:53.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301832 UPRstat:0
[2026-08-08 04:11:53.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:53.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:53.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:53.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:53.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:53.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.239 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:53.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.339 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:53.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:53.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:53.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.638 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:53.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:53.721 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018383, monitor_cnt:50, bc_elapsed:3018383, min:10, max:40
[2026-08-08 04:11:53.721 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:53.722 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :9
[2026-08-08 04:11:53.723 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:53.723 UTC] [D] 485AcReq <C2:01> PutOStream [9][0800010413fa001794b1]
[2026-08-08 04:11:53.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.738 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:53.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.839 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:53.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:53.939 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:53.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:53.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5721.100000 = p_th_old_:5711.200000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:53.942 UTC] [V] OFSCtrl CHG 21 batt_w:-15954.420159 = old:-16002.858659 +  kp:0.550000 * e:77.350000 + ki:0.000000 * sume:9371516.850239 + kd:0.040000 * (e:77.350000 - e1:-70.050000)
[2026-08-08 04:11:53.943 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15954.420159 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:53.944 UTC] [V] OFSCtrl CHG 29 q:-160.000000, mod(round):0.000000
[2026-08-08 04:11:53.944 UTC] [D] OFSCtrl battery ctrl val:-31.900000
[2026-08-08 04:11:53.945 UTC] [V] 485ChCtl <C3> battery limit on [-160.000000,] request.
[2026-08-08 04:11:53.946 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:54.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:54.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:54.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-160] set rate[-32.000000] value100[500] value-100[-500]
[2026-08-08 04:11:54.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff60]
[2026-08-08 04:11:54.094 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:54.095 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[51] [01042e19440021197a001e19ef0013ffffffffffffffff03e8ffffffff3fc00000ffffffffffffffffffffffffffffffff484d]
[2026-08-08 04:11:54.095 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [9] IsNormal[1] 
[2026-08-08 04:11:54.097 UTC] [V] 485DevCtl <C2:01> [04][101100][6468.000000][1][V]
[2026-08-08 04:11:54.098 UTC] [V] SummDat SetVrmValue dev_id:7 val:646800.000000 sc:3
[2026-08-08 04:11:54.104 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:04, valueId:101100, value:6468.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:54.111 UTC] [V] 485DevCtl <C2:01> [04][101101][33.000000][1][A]
[2026-08-08 04:11:54.112 UTC] [V] SummDat SetVrmValue dev_id:7 val:3300.000000 sc:3
[2026-08-08 04:11:54.112 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:04, valueId:101101, value:33.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:54.126 UTC] [V] 485DevCtl <C2:01> [05][101100][6522.000000][1][V]
[2026-08-08 04:11:54.127 UTC] [V] SummDat SetVrmValue dev_id:7 val:652200.000000 sc:3
[2026-08-08 04:11:54.127 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:05, valueId:101100, value:6522.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:54.127 UTC] [V] 485DevCtl <C2:01> [05][101101][30.000000][1][A]
[2026-08-08 04:11:54.128 UTC] [V] SummDat SetVrmValue dev_id:7 val:3000.000000 sc:3
[2026-08-08 04:11:54.128 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:05, valueId:101101, value:30.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:54.128 UTC] [V] 485DevCtl <C2:01> [06][101100][6639.000000][1][V]
[2026-08-08 04:11:54.128 UTC] [V] SummDat SetVrmValue dev_id:7 val:663900.000000 sc:3
[2026-08-08 04:11:54.128 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:06, valueId:101100, value:6639.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:54.129 UTC] [V] 485DevCtl <C2:01> [06][101101][19.000000][1][A]
[2026-08-08 04:11:54.129 UTC] [V] SummDat SetVrmValue dev_id:7 val:1900.000000 sc:3
[2026-08-08 04:11:54.129 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:06, valueId:101101, value:19.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:54.130 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:54.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.138 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:54.166 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:54.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301833 UPRstat:0
[2026-08-08 04:11:54.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:54.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:54.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:54.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:54.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:54.204 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018388, monitor_cnt:100, bc_elapsed:38, min:10, max:40
[2026-08-08 04:11:54.204 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:54.221 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018388, monitor_cnt:55, bc_elapsed:3018388, min:10, max:40
[2026-08-08 04:11:54.221 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :9
[2026-08-08 04:11:54.222 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:54.223 UTC] [D] 485AcReq <C2:02> PutOStream [9][0800020413fa00179482]
[2026-08-08 04:11:54.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.238 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:54.305 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018389, monitor_cnt:101, bc_elapsed:39, min:10, max:40
[2026-08-08 04:11:54.305 UTC] [V] 485DevCtl <C1:02> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:54.305 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:54.306 UTC] [V] 485ChCtl <C1> send request:IMT01
[2026-08-08 04:11:54.306 UTC] [D] 485AcReq <C1:02> PutOStream [1][08000204000200019039]
[2026-08-08 04:11:54.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.339 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:54.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:54.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:54.606 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:54.607 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[51] [02042e18900026190f002318d70022ffffffffffffffff03e8ffffffff40ca0000ffffffffffffffffffffffffffffffff2aa1]
[2026-08-08 04:11:54.608 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [9] IsNormal[1] 
[2026-08-08 04:11:54.608 UTC] [V] 485DevCtl <C2:02> [04][101100][6288.000000][1][V]
[2026-08-08 04:11:54.608 UTC] [V] SummDat SetVrmValue dev_id:8 val:628800.000000 sc:3
[2026-08-08 04:11:54.612 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:04, valueId:101100, value:6288.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:54.615 UTC] [V] 485DevCtl <C2:02> [04][101101][38.000000][1][A]
[2026-08-08 04:11:54.616 UTC] [V] SummDat SetVrmValue dev_id:8 val:3800.000000 sc:3
[2026-08-08 04:11:54.622 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:04, valueId:101101, value:38.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:54.625 UTC] [V] 485DevCtl <C2:02> [05][101100][6415.000000][1][V]
[2026-08-08 04:11:54.625 UTC] [V] SummDat SetVrmValue dev_id:8 val:641500.000000 sc:3
[2026-08-08 04:11:54.625 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:05, valueId:101100, value:6415.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:54.631 UTC] [V] 485DevCtl <C2:02> [05][101101][35.000000][1][A]
[2026-08-08 04:11:54.633 UTC] [V] SummDat SetVrmValue dev_id:8 val:3500.000000 sc:3
[2026-08-08 04:11:54.637 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:05, valueId:101101, value:35.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:54.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.638 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:54.640 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018392, monitor_cnt:50, bc_elapsed:3018392, min:10, max:40
[2026-08-08 04:11:54.640 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:54.640 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:54.640 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :4
[2026-08-08 04:11:54.641 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:54.642 UTC] [D] 485AcReq <C3:01> PutOStream [4][0c00000100000006010427f0002f]
[2026-08-08 04:11:54.648 UTC] [V] 485DevCtl <C1:02> AnalyzeResponseData proc restart cnt:301828 UPRstat:0
[2026-08-08 04:11:54.648 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:54.649 UTC] [D] 485DevCtl <C1:02> RcvDat status[2] len[7] [020402021cfd99]
[2026-08-08 04:11:54.649 UTC] [D] 485DevCtl <C1:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:54.650 UTC] [V] 485DevCtl <C1:02> [01][431005][290.000000][1][°C]
[2026-08-08 04:11:54.650 UTC] [V] SummDat SetVrmValue dev_id:2 val:29000.000000 sc:3
[2026-08-08 04:11:54.650 UTC] [V] OCMgr SetMeterValue PhId:0102, branchNo:01, valueId:431005, value:290.000000, scaleFactor:1, devId:2
[2026-08-08 04:11:54.651 UTC] [V] 485DevCtl <C1:02> device_type:
[2026-08-08 04:11:54.651 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:54.656 UTC] [V] 485DevCtl <C2:02> [06][101100][6359.000000][1][V]
[2026-08-08 04:11:54.657 UTC] [V] SummDat SetVrmValue dev_id:8 val:635900.000000 sc:3
[2026-08-08 04:11:54.657 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:06, valueId:101100, value:6359.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:54.657 UTC] [V] 485DevCtl <C2:02> [06][101101][34.000000][1][A]
[2026-08-08 04:11:54.657 UTC] [V] SummDat SetVrmValue dev_id:8 val:3400.000000 sc:3
[2026-08-08 04:11:54.658 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:06, valueId:101101, value:34.000000, scaleFactor:1, devId:8
[2026-08-08 04:11:54.658 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:11:54.659 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:54.667 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:11:54.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:54.704 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:54.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.739 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:54.798 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301834 UPRstat:0
[2026-08-08 04:11:54.801 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[103] [00010000006101045e1f20ff3eff640f870f860fb900e700e500e8ff61000000000000000000000000000000000223001b9ddc000091260000012c00000067030b301a00000001177403e701d4014f01bc00d6000019de00002f4b000100a002230000001b0000]
[2026-08-08 04:11:54.801 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [4] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:54.801 UTC] [V] 485DevCtl <C3:01> [05][753053][0.000000][0][]
[2026-08-08 04:11:54.801 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:54.802 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:05, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:54.802 UTC] [V] 485DevCtl <C3:01> [06][753053][0.000000][0][]
[2026-08-08 04:11:54.804 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:54.819 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:54.827 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:06, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:54.827 UTC] [V] 485DevCtl <C3:01> [07][753053][0.000000][0][]
[2026-08-08 04:11:54.827 UTC] [V] SummDat SetVrmValue dev_id:9 val:0.000000 sc:0
[2026-08-08 04:11:54.828 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:07, valueId:753053, value:0.000000, scaleFactor:0, devId:9
[2026-08-08 04:11:54.828 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:54.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.839 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:54.848 UTC] [V] 485DevCtl <C3:01> set2 StatusCode[020101]
[2026-08-08 04:11:54.848 UTC] [V] OFSCtrl Bat[0301] StCd[020101]->st[1].
[2026-08-08 04:11:54.855 UTC] [V] OFSCtrl set batt status:[0301]:Drive, All:[0301]:Drive, [DRIVE] 
[2026-08-08 04:11:54.863 UTC] [V] OFSCtrl change set SOC(t):61.000000 drive cnt:1
[2026-08-08 04:11:54.864 UTC] [V] 485DevCtl <C3:01> set2 StatusCode[020101] DeviceName[蓄電池1] DeviceNumber[1]
[2026-08-08 04:11:54.876 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:54.883 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:54.904 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:54.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:54.939 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:54.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:54.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5731.000000 = p_th_old_:5721.100000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:54.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15946.599159 = old:-15954.420159 +  kp:0.550000 * e:18.500000 + ki:0.000000 * sume:9371535.350239 + kd:0.040000 * (e:18.500000 - e1:77.350000)
[2026-08-08 04:11:54.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15946.599159 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:54.940 UTC] [V] OFSCtrl CHG 29 q:-160.000000, mod(round):1.000000
[2026-08-08 04:11:54.941 UTC] [D] OFSCtrl battery ctrl val:-31.900000
[2026-08-08 04:11:54.942 UTC] [V] 485ChCtl <C3> battery limit on [-159.000000,] request.
[2026-08-08 04:11:54.943 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:55.004 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:55.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:55.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-159] set rate[-31.800000] value100[500] value-100[-500]
[2026-08-08 04:11:55.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff61]
[2026-08-08 04:11:55.104 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:55.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.138 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301834 UPRstat:0
[2026-08-08 04:11:55.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:55.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:55.201 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:55.201 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:55.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:55.204 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:55.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.238 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.304 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:55.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.339 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:55.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:55.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:11:55.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:55.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:55.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:11:55.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:11:55.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.638 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:55.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:55.738 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301836 UPRstat:0
[2026-08-08 04:11:55.738 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:55.739 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [0104040887022448b6]
[2026-08-08 04:11:55.739 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:55.739 UTC] [V] OFSCtrl Rcv set flux_of_solar:218.300000
[2026-08-08 04:11:55.739 UTC] [V] 485DevCtl <C1:01> [01][401006][2183.000000][1][W/m2]
[2026-08-08 04:11:55.739 UTC] [V] SummDat SetVrmValue dev_id:1 val:218300.000000 sc:3
[2026-08-08 04:11:55.741 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.741 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:55.740 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2183.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:55.742 UTC] [V] 485DevCtl <C1:01> [01][421005][298.000000][1][℃]
[2026-08-08 04:11:55.743 UTC] [V] SummDat SetVrmValue dev_id:1 val:29800.000000 sc:3
[2026-08-08 04:11:55.746 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:298.000000, scaleFactor:1, devId:1
[2026-08-08 04:11:55.746 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:55.747 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:11:55.757 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:55.759 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:11:55.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:55.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:55.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:11:55.805 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:55.805 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:55.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:11:55.808 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:11:55.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.838 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:55.938 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:55.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:55.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5740.900000 = p_th_old_:5731.000000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:55.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15930.583159 = old:-15946.599159 +  kp:0.550000 * e:28.400000 + ki:0.000000 * sume:9371563.750239 + kd:0.040000 * (e:28.400000 - e1:18.500000)
[2026-08-08 04:11:55.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15930.583159 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:55.940 UTC] [V] OFSCtrl CHG 29 q:-160.000000, mod(round):1.000000
[2026-08-08 04:11:55.940 UTC] [D] OFSCtrl battery ctrl val:-31.900000
[2026-08-08 04:11:55.940 UTC] [V] 485ChCtl <C3> battery limit on [-159.000000,] request.
[2026-08-08 04:11:55.940 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:55.940 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:55.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-159] set rate[-31.800000] value100[500] value-100[-500]
[2026-08-08 04:11:55.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff61]
[2026-08-08 04:11:56.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.039 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:56.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301835 UPRstat:0
[2026-08-08 04:11:56.094 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:56.096 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:56.097 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:56.098 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:56.103 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:56.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.139 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:56.199 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301835 UPRstat:0
[2026-08-08 04:11:56.199 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:56.201 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800005fd0000060400000544900000050000002580000f69a00000277ffff49b2fffffe2e001216853a12]
[2026-08-08 04:11:56.201 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:56.201 UTC] [V] OFSCtrl Rcv set p_co:6310.000000, p_co_old:6350.000000
[2026-08-08 04:11:56.203 UTC] [V] 485DevCtl <C1:04> [01][601260][631.000000][2][kW]
[2026-08-08 04:11:56.203 UTC] [V] SummDat SetVrmValue dev_id:4 val:6310.000000 sc:3
[2026-08-08 04:11:56.203 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:631.000000, scaleFactor:2, devId:4
[2026-08-08 04:11:56.204 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:11:56.204 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:11:56.204 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:11:56.204 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:56.204 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:11:56.205 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:11:56.205 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:11:56.205 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:11:56.205 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6310.000000
[2026-08-08 04:11:56.205 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:218.300000 < rad_th:80.000000
[2026-08-08 04:11:56.205 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301873:6310.000000
[2026-08-08 04:11:56.206 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:11:56.206 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:11:56.237 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:11:56.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.238 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:56.248 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:11:56.249 UTC] [D] OFSCtrl pv-pcs ctrl val:22.517503 old:23.105455
[2026-08-08 04:11:56.249 UTC] [V] OCHisDB set rate:23 t_rate:472 cnt:23
[2026-08-08 04:11:56.249 UTC] [V] 485ChCtl <C2> pv-pcs limit on [22.517503] request.
[2026-08-08 04:11:56.249 UTC] [V] OFSCtrl save reduction C[W]:250.290868 = total[W]:99000.000000* diff[]:0.587951 / 100.0 * Kc:0.430000
[2026-08-08 04:11:56.249 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:11:56.250 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:56.267 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:11:56.304 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:56.321 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:11:56.321 UTC] [D] VarInf update ofs_rate:22.517504
[2026-08-08 04:11:56.322 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:11:56.322 UTC] [D] VarInf output_mode:8
[2026-08-08 04:11:56.322 UTC] [D] VarInf update ofs_rate:22.517504
[2026-08-08 04:11:56.322 UTC] [D] VarInf Limit setRate[225.175034] rate[22.517504] value100[1000.000000] value0[0.000000]
[2026-08-08 04:11:56.322 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:22.517504 set_rate225
[2026-08-08 04:11:56.322 UTC] [D] VarInf Limit rt[2] int_set_rate[225] server_rate[22.517504] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:11:56.325 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00e147e7]
[2026-08-08 04:11:56.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.338 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:56.404 UTC] [V] 485ChCtl <C1> monitor no transmission period.
[2026-08-08 04:11:56.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:56.504 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018411, monitor_cnt:123, bc_elapsed:11, min:10, max:40
[2026-08-08 04:11:56.504 UTC] [V] 485DevCtl <C1:03> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:56.505 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:56.505 UTC] [V] 485ChCtl <C1> send request:omron03
[2026-08-08 04:11:56.506 UTC] [D] 485AcReq <C1:03> PutOStream [1][08000303000000144427]
[2026-08-08 04:11:56.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.539 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:56.612 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:56.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.639 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:56.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:11:56 val:6310.000000
[2026-08-08 04:11:56.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:11:56' , 6310.000000 , 0  )
[2026-08-08 04:11:56.712 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:56.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1170->1170] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.738 UTC] [V] OFSCtrl angif value:1170 power_val_:5437.500000
[2026-08-08 04:11:56.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1166->1166] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.838 UTC] [V] OFSCtrl angif value:1166 power_val_:5162.500000
[2026-08-08 04:11:56.900 UTC] [V] 485DevCtl <C1:03> AnalyzeResponseData proc restart cnt:301830 UPRstat:0
[2026-08-08 04:11:56.900 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:56.901 UTC] [D] 485DevCtl <C1:03> RcvDat status[2] len[45] [0303280000fc040000ff1b0000fe3d0000223e0000271d00002e730000005e00000258001069bb00002a040b69]
[2026-08-08 04:11:56.902 UTC] [D] 485DevCtl <C1:03> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:56.902 UTC] [V] 485DevCtl <C1:03> [01][301200][64516.000000][1][V]
[2026-08-08 04:11:56.902 UTC] [V] SummDat SetVrmValue dev_id:3 val:6451600.000000 sc:3
[2026-08-08 04:11:56.903 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301200, value:64516.000000, scaleFactor:1, devId:3
[2026-08-08 04:11:56.903 UTC] [V] 485DevCtl <C1:03> [01][301201][8766.000000][3][A]
[2026-08-08 04:11:56.903 UTC] [V] SummDat SetVrmValue dev_id:3 val:8766.000000 sc:3
[2026-08-08 04:11:56.921 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:301201, value:8766.000000, scaleFactor:3, devId:3
[2026-08-08 04:11:56.928 UTC] [V] OFSCtrl Rcv set p_grid:107560.000000
[2026-08-08 04:11:56.929 UTC] [V] 485DevCtl <C1:03> [01][601202][10756.000000][2][kW]
[2026-08-08 04:11:56.929 UTC] [V] SummDat SetVrmValue dev_id:3 val:107560.000000 sc:3
[2026-08-08 04:11:56.930 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:601202, value:10756.000000, scaleFactor:2, devId:3
[2026-08-08 04:11:56.930 UTC] [V] 485DevCtl <C1:03> device_type:Grid-Meter
[2026-08-08 04:11:56.931 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:56.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1167->1167] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:56.939 UTC] [V] OFSCtrl angif value:1167 power_val_:5231.250000
[2026-08-08 04:11:56.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:56.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5750.800000 = p_th_old_:5740.900000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:56.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15625.184659 = old:-15930.583159 +  kp:0.550000 * e:519.550000 + ki:0.000000 * sume:9372083.300239 + kd:0.040000 * (e:519.550000 - e1:28.400000)
[2026-08-08 04:11:56.940 UTC] [V] OFSCtrl CHG 21 update batt_w:-15374.893791 += C:250.290868
[2026-08-08 04:11:56.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15374.893791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:56.940 UTC] [V] OFSCtrl CHG 29 q:-154.000000, mod(round):0.000000
[2026-08-08 04:11:56.941 UTC] [D] OFSCtrl battery ctrl val:-30.700000
[2026-08-08 04:11:56.941 UTC] [V] 485ChCtl <C3> battery limit on [-154.000000,] request.
[2026-08-08 04:11:56.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:57.004 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018416, monitor_cnt:128, bc_elapsed:16, min:10, max:40
[2026-08-08 04:11:57.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1167->1167] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.038 UTC] [V] OFSCtrl angif value:1167 power_val_:5231.250000
[2026-08-08 04:11:57.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:57.040 UTC] [D] VarInf Limit_Bat rt[2]set val[-154] set rate[-30.800000] value100[500] value-100[-500]
[2026-08-08 04:11:57.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff66]
[2026-08-08 04:11:57.104 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018417, monitor_cnt:129, bc_elapsed:17, min:10, max:40
[2026-08-08 04:11:57.104 UTC] [V] 485DevCtl <C1:05> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:57.104 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:57.105 UTC] [V] 485ChCtl <C1> send request:omron04
[2026-08-08 04:11:57.106 UTC] [D] 485AcReq <C1:05> PutOStream [1][0800050300030014b441]
[2026-08-08 04:11:57.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1167->1167] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.138 UTC] [V] OFSCtrl angif value:1167 power_val_:5231.250000
[2026-08-08 04:11:57.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301836 UPRstat:0
[2026-08-08 04:11:57.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:57.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:57.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:57.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:57.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:57.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1167->1167] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.239 UTC] [V] OFSCtrl angif value:1167 power_val_:5231.250000
[2026-08-08 04:11:57.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1167->1167] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.339 UTC] [V] OFSCtrl angif value:1167 power_val_:5231.250000
[2026-08-08 04:11:57.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1167->1167] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.439 UTC] [V] OFSCtrl angif value:1167 power_val_:5231.250000
[2026-08-08 04:11:57.501 UTC] [V] 485DevCtl <C1:05> AnalyzeResponseData proc restart cnt:301829 UPRstat:0
[2026-08-08 04:11:57.501 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:57.504 UTC] [D] 485DevCtl <C1:05> RcvDat status[2] len[45] [0503280000fb0b000102ad0000f5d8000000610000025700036010000008a4ffff4eaffffffe3b001382bc5392]
[2026-08-08 04:11:57.505 UTC] [D] 485DevCtl <C1:05> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:57.507 UTC] [V] OFSCtrl Rcv set p_pv:22120.000000
[2026-08-08 04:11:57.509 UTC] [V] 485DevCtl <C1:05> [01][601259][2212.000000][2][kW]
[2026-08-08 04:11:57.511 UTC] [V] SummDat SetVrmValue dev_id:5 val:22120.000000 sc:3
[2026-08-08 04:11:57.516 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:601259, value:2212.000000, scaleFactor:2, devId:5
[2026-08-08 04:11:57.521 UTC] [V] 485DevCtl <C1:05> [01][603259][1278652.000000][1][kWh]
[2026-08-08 04:11:57.522 UTC] [V] SummDat SetVrmValue dev_id:5 val:1278652.000000 sc:1
[2026-08-08 04:11:57.527 UTC] [V] OCMgr SetMeterValue PhId:0105, branchNo:01, valueId:603259, value:1278652.000000, scaleFactor:1, devId:5
[2026-08-08 04:11:57.531 UTC] [V] 485DevCtl <C1:05> device_type:PV-Meter
[2026-08-08 04:11:57.536 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:57.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1171->1171] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.539 UTC] [V] OFSCtrl angif value:1171 power_val_:5506.250000
[2026-08-08 04:11:57.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018422, monitor_cnt:134, bc_elapsed:22, min:10, max:40
[2026-08-08 04:11:57.605 UTC] [V] 485DevCtl <C1:06> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:57.605 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:57.605 UTC] [V] 485ChCtl <C1> send request:omron06
[2026-08-08 04:11:57.607 UTC] [D] 485AcReq <C1:06> PutOStream [1][08000603000000144472]
[2026-08-08 04:11:57.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:57.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:57.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.739 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:57.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.838 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:57.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:57.939 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:57.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:57.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5760.700000 = p_th_old_:5750.800000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:57.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15448.362791 = old:-15374.893791 +  kp:0.550000 * e:-89.300000 + ki:0.000000 * sume:9371994.000239 + kd:0.040000 * (e:-89.300000 - e1:519.550000)
[2026-08-08 04:11:57.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15448.362791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:57.940 UTC] [V] OFSCtrl CHG 29 q:-155.000000, mod(round):1.000000
[2026-08-08 04:11:57.941 UTC] [D] OFSCtrl battery ctrl val:-30.900000
[2026-08-08 04:11:57.941 UTC] [V] 485ChCtl <C3> battery limit on [-154.000000,] request.
[2026-08-08 04:11:57.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:57.994 UTC] [V] 485DevCtl <C1:06> AnalyzeResponseData proc restart cnt:301830 UPRstat:0
[2026-08-08 04:11:57.994 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:57.995 UTC] [D] 485DevCtl <C1:06> RcvDat status[2] len[45] [060328000007f200000806000008060000aeb20000af770000b187ffffff9c00000259fffd90effffff9c565ee]
[2026-08-08 04:11:57.995 UTC] [D] 485DevCtl <C1:06> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:57.996 UTC] [V] OFSCtrl Rcv set p_batt:-15950.000000
[2026-08-08 04:11:57.996 UTC] [V] 485DevCtl <C1:06> [01][601237][-1595.000000][2][kW]
[2026-08-08 04:11:57.997 UTC] [V] SummDat SetVrmValue dev_id:6 val:-15950.000000 sc:3
[2026-08-08 04:11:58.004 UTC] [V] OCMgr SetMeterValue PhId:0106, branchNo:01, valueId:601237, value:-1595.000000, scaleFactor:2, devId:6
[2026-08-08 04:11:58.004 UTC] [V] 485DevCtl <C1:06> device_type:Batt-Meter
[2026-08-08 04:11:58.005 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:11:58.005 UTC] [D] 485ChCtl <C1> monitoring dev All Send
[2026-08-08 04:11:58.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.039 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:58.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:58.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-154] set rate[-30.800000] value100[500] value-100[-500]
[2026-08-08 04:11:58.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff66]
[2026-08-08 04:11:58.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.139 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301837 UPRstat:0
[2026-08-08 04:11:58.192 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:58.194 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:58.194 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:58.196 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:58.199 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:58.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.238 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:11:58.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.339 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.439 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.539 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:58.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.738 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:11:58.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.838 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:58.938 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:58.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:58.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5770.600000 = p_th_old_:5760.700000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:58.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15491.636791 = old:-15448.362791 +  kp:0.550000 * e:-79.400000 + ki:0.000000 * sume:9371914.600239 + kd:0.040000 * (e:-79.400000 - e1:-89.300000)
[2026-08-08 04:11:58.939 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15491.636791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:58.941 UTC] [V] OFSCtrl CHG 29 q:-155.000000, mod(round):0.000000
[2026-08-08 04:11:58.942 UTC] [D] OFSCtrl battery ctrl val:-31.000000
[2026-08-08 04:11:58.942 UTC] [V] 485ChCtl <C3> battery limit on [-155.000000,] request.
[2026-08-08 04:11:58.943 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:11:59.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:59.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:11:59.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-155] set rate[-31.000000] value100[500] value-100[-500]
[2026-08-08 04:11:59.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff65]
[2026-08-08 04:11:59.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.139 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:59.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301838 UPRstat:0
[2026-08-08 04:11:59.190 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:11:59.190 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:11:59.190 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:11:59.191 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:59.191 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:59.220 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018438, monitor_cnt:50, bc_elapsed:3018438, min:10, max:40
[2026-08-08 04:11:59.220 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:59.221 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:59.221 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:59.222 UTC] [D] 485AcReq <C2:01> PutOStream [1][08000104138a0024d57f]
[2026-08-08 04:11:59.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.238 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:11:59.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.338 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:59.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.439 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:59.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:11:59.623 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:11:59.625 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[77] [01044801b3fc9f00001726000001982be500001997001d1979001d199d001b2bd0000010ba10bd10db009800980099ffffffffffffffffffffffff2b280000067c000003dd0258267a8200877d]
[2026-08-08 04:11:59.625 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:11:59.630 UTC] [V] 485DevCtl <C2:01> [01][115202][435.000000][1][kWh]
[2026-08-08 04:11:59.630 UTC] [V] SummDat SetVrmValue dev_id:7 val:435.000000 sc:1
[2026-08-08 04:11:59.630 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:115202, value:435.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.631 UTC] [V] 485DevCtl <C2:01> [01][113202][64671.000000][0][kWh]
[2026-08-08 04:11:59.631 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671.000000 sc:0
[2026-08-08 04:11:59.631 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:113202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:59.631 UTC] [V] 485DevCtl <C2:01> [01][121005][408.000000][1][℃]
[2026-08-08 04:11:59.631 UTC] [V] SummDat SetVrmValue dev_id:7 val:40800.000000 sc:3
[2026-08-08 04:11:59.632 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121005, value:408.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.632 UTC] [V] 485DevCtl <C2:01> [01][101100][6551.000000][1][V]
[2026-08-08 04:11:59.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.638 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:59.641 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018442, monitor_cnt:50, bc_elapsed:3018442, min:10, max:40
[2026-08-08 04:11:59.641 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:11:59.641 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:11:59.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :5
[2026-08-08 04:11:59.642 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:11:59.643 UTC] [D] 485AcReq <C3:01> PutOStream [5][0c00000100000006010469780001]
[2026-08-08 04:11:59.663 UTC] [V] SummDat SetVrmValue dev_id:7 val:655100.000000 sc:3
[2026-08-08 04:11:59.663 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101100, value:6551.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.664 UTC] [V] 485DevCtl <C2:01> [01][101101][29.000000][1][A]
[2026-08-08 04:11:59.664 UTC] [V] SummDat SetVrmValue dev_id:7 val:2900.000000 sc:3
[2026-08-08 04:11:59.664 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101101, value:29.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.664 UTC] [V] 485DevCtl <C2:01> [02][101100][6521.000000][1][V]
[2026-08-08 04:11:59.664 UTC] [V] SummDat SetVrmValue dev_id:7 val:652100.000000 sc:3
[2026-08-08 04:11:59.665 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101100, value:6521.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.665 UTC] [V] 485DevCtl <C2:01> [02][101101][29.000000][1][A]
[2026-08-08 04:11:59.665 UTC] [V] SummDat SetVrmValue dev_id:7 val:2900.000000 sc:3
[2026-08-08 04:11:59.665 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:101101, value:29.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.665 UTC] [V] 485DevCtl <C2:01> [03][101100][6557.000000][1][V]
[2026-08-08 04:11:59.666 UTC] [V] SummDat SetVrmValue dev_id:7 val:655700.000000 sc:3
[2026-08-08 04:11:59.666 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101100, value:6557.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:11:59.702 UTC] [V] 485DevCtl <C2:01> [03][101101][27.000000][1][A]
[2026-08-08 04:11:59.702 UTC] [V] SummDat SetVrmValue dev_id:7 val:2700.000000 sc:3
[2026-08-08 04:11:59.704 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:101101, value:27.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.720 UTC] [V] 485DevCtl <C2:01> [01][101102][11216.000000][0][W]
[2026-08-08 04:11:59.720 UTC] [V] SummDat SetVrmValue dev_id:7 val:11216000.000000 sc:3
[2026-08-08 04:11:59.721 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:101102, value:11216.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:59.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1173->1173] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.740 UTC] [V] OFSCtrl angif value:1173 power_val_:5643.750000
[2026-08-08 04:11:59.721 UTC] [V] 485DevCtl <C2:01> [01][111200][4282.000000][1][V]
[2026-08-08 04:11:59.741 UTC] [V] SummDat SetVrmValue dev_id:7 val:428200.000000 sc:3
[2026-08-08 04:11:59.741 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111200, value:4282.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.741 UTC] [V] 485DevCtl <C2:01> [02][111200][4285.000000][1][V]
[2026-08-08 04:11:59.742 UTC] [V] SummDat SetVrmValue dev_id:7 val:428500.000000 sc:3
[2026-08-08 04:11:59.754 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111200, value:4285.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.754 UTC] [V] 485DevCtl <C2:01> [03][111200][4315.000000][1][V]
[2026-08-08 04:11:59.754 UTC] [V] SummDat SetVrmValue dev_id:7 val:431500.000000 sc:3
[2026-08-08 04:11:59.755 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111200, value:4315.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.755 UTC] [V] 485DevCtl <C2:01> [01][111201][152.000000][1][A]
[2026-08-08 04:11:59.755 UTC] [V] SummDat SetVrmValue dev_id:7 val:15200.000000 sc:3
[2026-08-08 04:11:59.755 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111201, value:152.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.756 UTC] [V] 485DevCtl <C2:01> [02][111201][152.000000][1][A]
[2026-08-08 04:11:59.756 UTC] [V] SummDat SetVrmValue dev_id:7 val:15200.000000 sc:3
[2026-08-08 04:11:59.756 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:02, valueId:111201, value:152.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.768 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301839 UPRstat:0
[2026-08-08 04:11:59.769 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[11] [000100000005010402012b]
[2026-08-08 04:11:59.769 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [5] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:11:59.784 UTC] [V] 485DevCtl <C3:01> [01][121005][299.000000][1][℃]
[2026-08-08 04:11:59.784 UTC] [V] SummDat SetVrmValue dev_id:9 val:29900.000000 sc:3
[2026-08-08 04:11:59.784 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:01, valueId:121005, value:299.000000, scaleFactor:1, devId:9
[2026-08-08 04:11:59.785 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:11:59.786 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:11:59.786 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:11:59.788 UTC] [V] 485DevCtl <C2:01> [03][111201][153.000000][1][A]
[2026-08-08 04:11:59.789 UTC] [V] SummDat SetVrmValue dev_id:7 val:15300.000000 sc:3
[2026-08-08 04:11:59.789 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:03, valueId:111201, value:153.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.798 UTC] [V] 485DevCtl <C2:01> [01][111202][11048.000000][0][W]
[2026-08-08 04:11:59.799 UTC] [V] SummDat SetVrmValue dev_id:7 val:11048000.000000 sc:3
[2026-08-08 04:11:59.802 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111202, value:11048.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:59.808 UTC] [V] 485DevCtl <C2:01> [01][111203][1660.000000][0][var]
[2026-08-08 04:11:59.809 UTC] [V] SummDat SetVrmValue dev_id:7 val:1660000.000000 sc:3
[2026-08-08 04:11:59.815 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:111203, value:1660.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:59.820 UTC] [V] 485DevCtl <C2:01> [01][121007][989.000000][3][]
[2026-08-08 04:11:59.836 UTC] [V] SummDat SetVrmValue dev_id:7 val:989.000000 sc:3
[2026-08-08 04:11:59.837 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:121007, value:989.000000, scaleFactor:3, devId:7
[2026-08-08 04:11:59.837 UTC] [V] 485DevCtl <C2:01> [01][131006][600.000000][1][Hz]
[2026-08-08 04:11:59.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1168->1168] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.838 UTC] [V] OFSCtrl angif value:1168 power_val_:5300.000000
[2026-08-08 04:11:59.837 UTC] [V] SummDat SetVrmValue dev_id:7 val:60000.000000 sc:3
[2026-08-08 04:11:59.848 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:7
[2026-08-08 04:11:59.848 UTC] [V] 485DevCtl <C2:01> [01][114202][64671.000000][0][kWh]
[2026-08-08 04:11:59.848 UTC] [V] SummDat SetVrmValue dev_id:7 val:64671000.000000 sc:3
[2026-08-08 04:11:59.858 UTC] [V] OCMgr SetMeterValue PhId:0201, branchNo:01, valueId:114202, value:64671.000000, scaleFactor:0, devId:7
[2026-08-08 04:11:59.862 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:11:59.870 UTC] [V] 485DevCtl <C2:01> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:11:59.875 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:11:59.920 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018445, monitor_cnt:57, bc_elapsed:3018445, min:10, max:40
[2026-08-08 04:11:59.921 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:11:59.921 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:11:59.923 UTC] [D] 485AcReq <C2:02> PutOStream [1][08000204138a0024d54c]
[2026-08-08 04:11:59.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:11:59.939 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:11:59.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:11:59.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5780.500000 = p_th_old_:5770.600000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:11:59.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15367.215791 = old:-15491.636791 +  kp:0.550000 * e:205.500000 + ki:0.000000 * sume:9372120.100239 + kd:0.040000 * (e:205.500000 - e1:-79.400000)
[2026-08-08 04:11:59.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15367.215791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:11:59.940 UTC] [V] OFSCtrl CHG 29 q:-154.000000, mod(round):0.000000
[2026-08-08 04:11:59.940 UTC] [D] OFSCtrl battery ctrl val:-30.700000
[2026-08-08 04:11:59.941 UTC] [V] 485ChCtl <C3> battery limit on [-154.000000,] request.
[2026-08-08 04:11:59.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:00.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.038 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:00.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-154] set rate[-30.800000] value100[500] value-100[-500]
[2026-08-08 04:12:00.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff66]
[2026-08-08 04:12:00.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.138 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301839 UPRstat:0
[2026-08-08 04:12:00.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:00.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:00.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:00.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:00.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:00.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.239 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.326 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:00.328 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[77] [02044801b0022a00011719000001942d0600001a230010186100281a1900122cab000010c010c010e8009c009b009cffffffffffffffffffffffff2bff0000067a000003de0258267a82008cd8]
[2026-08-08 04:12:00.329 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:12:00.329 UTC] [V] 485DevCtl <C2:02> [01][115202][432.000000][1][kWh]
[2026-08-08 04:12:00.329 UTC] [V] SummDat SetVrmValue dev_id:8 val:432.000000 sc:1
[2026-08-08 04:12:00.329 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:115202, value:432.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.330 UTC] [V] 485DevCtl <C2:02> [01][113202][66090.000000][0][kWh]
[2026-08-08 04:12:00.330 UTC] [V] SummDat SetVrmValue dev_id:8 val:66090.000000 sc:0
[2026-08-08 04:12:00.330 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:113202, value:66090.000000, scaleFactor:0, devId:8
[2026-08-08 04:12:00.330 UTC] [V] 485DevCtl <C2:02> [01][121005][404.000000][1][℃]
[2026-08-08 04:12:00.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.339 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.345 UTC] [V] SummDat SetVrmValue dev_id:8 val:40400.000000 sc:3
[2026-08-08 04:12:00.352 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121005, value:404.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.360 UTC] [V] 485DevCtl <C2:02> [01][101100][6691.000000][1][V]
[2026-08-08 04:12:00.362 UTC] [V] SummDat SetVrmValue dev_id:8 val:669100.000000 sc:3
[2026-08-08 04:12:00.365 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101100, value:6691.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.372 UTC] [V] 485DevCtl <C2:02> [01][101101][16.000000][1][A]
[2026-08-08 04:12:00.374 UTC] [V] SummDat SetVrmValue dev_id:8 val:1600.000000 sc:3
[2026-08-08 04:12:00.377 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101101, value:16.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.382 UTC] [V] 485DevCtl <C2:02> [02][101100][6241.000000][1][V]
[2026-08-08 04:12:00.383 UTC] [V] SummDat SetVrmValue dev_id:8 val:624100.000000 sc:3
[2026-08-08 04:12:00.383 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101100, value:6241.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.383 UTC] [V] 485DevCtl <C2:02> [02][101101][40.000000][1][A]
[2026-08-08 04:12:00.383 UTC] [V] SummDat SetVrmValue dev_id:8 val:4000.000000 sc:3
[2026-08-08 04:12:00.384 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:101101, value:40.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.384 UTC] [V] 485DevCtl <C2:02> [03][101100][6681.000000][1][V]
[2026-08-08 04:12:00.384 UTC] [V] SummDat SetVrmValue dev_id:8 val:668100.000000 sc:3
[2026-08-08 04:12:00.384 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101100, value:6681.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.385 UTC] [V] 485DevCtl <C2:02> [03][101101][18.000000][1][A]
[2026-08-08 04:12:00.385 UTC] [V] SummDat SetVrmValue dev_id:8 val:1800.000000 sc:3
[2026-08-08 04:12:00.385 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:101101, value:18.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.385 UTC] [V] 485DevCtl <C2:02> [01][101102][11435.000000][0][W]
[2026-08-08 04:12:00.385 UTC] [V] SummDat SetVrmValue dev_id:8 val:11435000.000000 sc:3
[2026-08-08 04:12:00.386 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:101102, value:11435.000000, scaleFactor:0, devId:8
[2026-08-08 04:12:00.386 UTC] [V] 485DevCtl <C2:02> [01][111200][4288.000000][1][V]
[2026-08-08 04:12:00.386 UTC] [V] SummDat SetVrmValue dev_id:8 val:428800.000000 sc:3
[2026-08-08 04:12:00.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:00.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:00.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:12:00.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:00.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:12:00.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:12:00.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:12:00.386 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111200, value:4288.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.432 UTC] [V] 485DevCtl <C2:02> [02][111200][4288.000000][1][V]
[2026-08-08 04:12:00.435 UTC] [V] SummDat SetVrmValue dev_id:8 val:428800.000000 sc:3
[2026-08-08 04:12:00.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.439 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.441 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111200, value:4288.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.445 UTC] [V] 485DevCtl <C2:02> [03][111200][4328.000000][1][V]
[2026-08-08 04:12:00.448 UTC] [V] SummDat SetVrmValue dev_id:8 val:432800.000000 sc:3
[2026-08-08 04:12:00.449 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111200, value:4328.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.449 UTC] [V] 485DevCtl <C2:02> [01][111201][156.000000][1][A]
[2026-08-08 04:12:00.469 UTC] [V] SummDat SetVrmValue dev_id:8 val:15600.000000 sc:3
[2026-08-08 04:12:00.471 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111201, value:156.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.472 UTC] [V] 485DevCtl <C2:02> [02][111201][155.000000][1][A]
[2026-08-08 04:12:00.483 UTC] [V] SummDat SetVrmValue dev_id:8 val:15500.000000 sc:3
[2026-08-08 04:12:00.484 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:02, valueId:111201, value:155.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.484 UTC] [V] 485DevCtl <C2:02> [03][111201][156.000000][1][A]
[2026-08-08 04:12:00.484 UTC] [V] SummDat SetVrmValue dev_id:8 val:15600.000000 sc:3
[2026-08-08 04:12:00.485 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:03, valueId:111201, value:156.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.485 UTC] [V] 485DevCtl <C2:02> [01][111202][11263.000000][0][W]
[2026-08-08 04:12:00.485 UTC] [V] SummDat SetVrmValue dev_id:8 val:11263000.000000 sc:3
[2026-08-08 04:12:00.485 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111202, value:11263.000000, scaleFactor:0, devId:8
[2026-08-08 04:12:00.485 UTC] [V] 485DevCtl <C2:02> [01][111203][1658.000000][0][var]
[2026-08-08 04:12:00.486 UTC] [V] SummDat SetVrmValue dev_id:8 val:1658000.000000 sc:3
[2026-08-08 04:12:00.486 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:111203, value:1658.000000, scaleFactor:0, devId:8
[2026-08-08 04:12:00.486 UTC] [V] 485DevCtl <C2:02> [01][121007][990.000000][3][]
[2026-08-08 04:12:00.486 UTC] [V] SummDat SetVrmValue dev_id:8 val:990.000000 sc:3
[2026-08-08 04:12:00.517 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:121007, value:990.000000, scaleFactor:3, devId:8
[2026-08-08 04:12:00.517 UTC] [V] 485DevCtl <C2:02> [01][131006][600.000000][1][Hz]
[2026-08-08 04:12:00.517 UTC] [V] SummDat SetVrmValue dev_id:8 val:60000.000000 sc:3
[2026-08-08 04:12:00.518 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:131006, value:600.000000, scaleFactor:1, devId:8
[2026-08-08 04:12:00.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.538 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.541 UTC] [V] 485DevCtl <C2:02> [01][114202][66090.000000][0][kWh]
[2026-08-08 04:12:00.541 UTC] [V] SummDat SetVrmValue dev_id:8 val:66090000.000000 sc:3
[2026-08-08 04:12:00.541 UTC] [V] OCMgr SetMeterValue PhId:0202, branchNo:01, valueId:114202, value:66090.000000, scaleFactor:0, devId:8
[2026-08-08 04:12:00.542 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:12:00.557 UTC] [V] 485DevCtl <C2:02> set2 StatusCode[010101] DeviceName[] DeviceNumber[]
[2026-08-08 04:12:00.557 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:12:00.558 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:12:00.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.638 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:00.739 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301841 UPRstat:0
[2026-08-08 04:12:00.739 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:00.739 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [010404087902242946]
[2026-08-08 04:12:00.740 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:12:00.740 UTC] [V] OFSCtrl Rcv set flux_of_solar:216.900000
[2026-08-08 04:12:00.740 UTC] [V] 485DevCtl <C1:01> [01][401006][2169.000000][1][W/m2]
[2026-08-08 04:12:00.740 UTC] [V] SummDat SetVrmValue dev_id:1 val:216900.000000 sc:3
[2026-08-08 04:12:00.741 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.741 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.742 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2169.000000, scaleFactor:1, devId:1
[2026-08-08 04:12:00.743 UTC] [V] 485DevCtl <C1:01> [01][421005][298.000000][1][℃]
[2026-08-08 04:12:00.743 UTC] [V] SummDat SetVrmValue dev_id:1 val:29800.000000 sc:3
[2026-08-08 04:12:00.744 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:298.000000, scaleFactor:1, devId:1
[2026-08-08 04:12:00.744 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:00.744 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:12:00.744 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:12:00.747 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:00.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:00.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:00.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:12:00.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:00.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:12:00.805 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:12:00.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:12:00.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.838 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:00.939 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:00.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:00.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5790.400000 = p_th_old_:5780.500000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:00.941 UTC] [V] OFSCtrl CHG 21 batt_w:-15248.349791 = old:-15367.215791 +  kp:0.550000 * e:215.400000 + ki:0.000000 * sume:9372335.500239 + kd:0.040000 * (e:215.400000 - e1:205.500000)
[2026-08-08 04:12:00.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15248.349791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:00.941 UTC] [V] OFSCtrl CHG 29 q:-153.000000, mod(round):1.000000
[2026-08-08 04:12:00.941 UTC] [D] OFSCtrl battery ctrl val:-30.500000
[2026-08-08 04:12:00.942 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:00.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:01.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.038 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:01.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:01.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:01.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:01.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.138 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:01.188 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301840 UPRstat:0
[2026-08-08 04:12:01.189 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:01.190 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:01.190 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:01.190 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:01.192 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:01.204 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301840 UPRstat:0
[2026-08-08 04:12:01.204 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:01.207 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800005f7c00005fdf000053f700000050000002580000f50000000273ffff49d8fffffe2e00121685b0e5]
[2026-08-08 04:12:01.207 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:12:01.209 UTC] [V] OFSCtrl Rcv set p_co:6270.000000, p_co_old:6350.000000
[2026-08-08 04:12:01.209 UTC] [V] 485DevCtl <C1:04> [01][601260][627.000000][2][kW]
[2026-08-08 04:12:01.209 UTC] [V] SummDat SetVrmValue dev_id:4 val:6270.000000 sc:3
[2026-08-08 04:12:01.209 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:627.000000, scaleFactor:2, devId:4
[2026-08-08 04:12:01.210 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:12:01.210 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:12:01.210 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:12:01.210 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:01.215 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:12:01.231 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:12:01.232 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:12:01.233 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:12:01.235 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6270.000000
[2026-08-08 04:12:01.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.238 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:01.242 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:216.900000 < rad_th:80.000000
[2026-08-08 04:12:01.244 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301878:6270.000000
[2026-08-08 04:12:01.244 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:12:01.244 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:12:01.244 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:12:01.245 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:12:01.245 UTC] [D] OFSCtrl pv-pcs ctrl val:22.373094 old:22.517503
[2026-08-08 04:12:01.245 UTC] [V] OCHisDB set rate:22 t_rate:494 cnt:24
[2026-08-08 04:12:01.245 UTC] [V] 485ChCtl <C2> pv-pcs limit on [22.373094] request.
[2026-08-08 04:12:01.262 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:12:01.266 UTC] [V] OFSCtrl Nod calc proc start.
[2026-08-08 04:12:01.266 UTC] [V] OFSCtrl ProcNodCountCalculation cur:301878 >= next:301878 diff:0
[2026-08-08 04:12:01.320 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:12:01.321 UTC] [D] VarInf update ofs_rate:22.373095
[2026-08-08 04:12:01.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:12:01.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:12:01.321 UTC] [D] VarInf update ofs_rate:22.373095
[2026-08-08 04:12:01.321 UTC] [D] VarInf Limit setRate[223.730942] rate[22.373095] value100[1000.000000] value0[0.000000]
[2026-08-08 04:12:01.321 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:22.373095 set_rate224
[2026-08-08 04:12:01.322 UTC] [D] VarInf Limit rt[2] int_set_rate[224] server_rate[22.373095] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:12:01.323 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00e08627]
[2026-08-08 04:12:01.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.339 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:01.359 UTC] [V] OFSCtrl GetMinMaxPCo min:[301278:3980.000000], max:[301688:7360.000000], diff:410, data[3980.000000,4050.000000,4090.000000,4130.000000,4170.000000,4280.000000,4370.000000,4470.000000,4520.000000,4590.000000,4650.000000,4720.000000,4750.000000,4730.000000,4760.000000,4770.000000,4840.000000,4890.000000,4880.000000,4960.000000,5000.000000,4960.000000,4930.000000,5010.000000,5120.000000,5230.000000,5290.000000,5290.000000,5320.000000,5370.000000,5380.000000,5480.000000,5540.000000,5600.000000,5630.000000,5670.000000,5740.000000,5790.000000,5870.000000,5900.000000,5950.000000,6020.000000,6080.000000,6130.000000,6180.000000,6180.000000,6200.000000,6230.000000,6240.000000,6250.000000,6270.000000,6270.000000,6300.000000,6360.000000,6450.000000,6570.000000,6630.000000,6700.000000,6690.000000,6670.000000,6610.000000,6710.000000,6700.000000,6730.000000,6760.000000,6790.000000,6840.000000,6860.000000,6930.000000,6970.000000,7000.000000,7040.000000,7070.000000,7050.000000,7050.000000,7080.000000,7170.000000,7240.000000,7250.000000,7260.000000,7270.000000,7270.000000,7360.000000,7350.000000,7320.000000,7260.000000,7220.000000,7220.000000,7220.000000,7240.000000,7230.000000,7210.000000,7180.000000,7150.000000,7100.000000,7070.000000,7000.000000,6950.000000,6850.000000,6860.000000,6790.000000,6740.000000,6730.000000,6710.000000,6740.000000,6730.000000,6680.000000,6680.000000,6660.000000,6620.000000,6580.000000,6540.000000,6490.000000,6370.000000,6380.000000,6350.000000,6340.000000,6350.000000,6350.000000,6310.000000,6270.000000,]
[2026-08-08 04:12:01.359 UTC] [V] OFSCtrl ProcNodCountCalculation update next:301938
[2026-08-08 04:12:01.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1172->1172] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.439 UTC] [V] OFSCtrl angif value:1172 power_val_:5575.000000
[2026-08-08 04:12:01.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.539 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:12:01.614 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:12:01.634 UTC] [V] OFSCtrl DeleteOldPCo 301338, old:[301278,3980.000000] [301283,4050.000000] [301288,4090.000000] [301293,4130.000000] [301298,4170.000000] [301303,4280.000000] [301308,4370.000000] [301313,4470.000000] [301318,4520.000000] [301323,4590.000000] [301328,4650.000000] [301333,4720.000000] [301338,4750.000000] [301343,4730.000000] [301348,4760.000000] [301353,4770.000000] [301358,4840.000000] [301363,4890.000000] [301368,4880.000000] [301373,4960.000000] [301378,5000.000000] [301383,4960.000000] [301388,4930.000000] [301393,5010.000000] [301398,5120.000000] [301403,5230.000000] [301408,5290.000000] [301413,5290.000000] [301418,5320.000000] [301423,5370.000000] [301428,5380.000000] [301433,5480.000000] [301438,5540.000000] [301443,5600.000000] [301448,5630.000000] [301453,5670.000000] [301458,5740.000000] [301463,5790.000000] [301468,5870.000000] [301473,5900.000000] [301478,5950.000000] [301483,6020.000000] [301488,6080.000000] [301493,6130.000000] [301498,6180.000000] [301503,6180.000000] [301508,6200.000000] [301513,6230.000000] [301518,6240.000000] [301523,6250.000000] [301528,6270.000000] [301533,6270.000000] [301538,6300.000000] [301543,6360.000000] [301548,6450.000000] [301553,6570.000000] [301558,6630.000000] [301563,6700.000000] [301568,6690.000000] [301573,6670.000000] [301578,6610.000000] [301583,6710.000000] [301588,6700.000000] [301593,6730.000000] [301598,6760.000000] [301603,6790.000000] [301608,6840.000000] [301613,6860.000000] [301618,6930.000000] [301623,6970.000000] [301628,7000.000000] [301633,7040.000000] [301638,7070.000000] [301643,7050.000000] [301648,7050.000000] [301653,7080.000000] [301658,7170.000000] [301663,7240.000000] [301668,7250.000000] [301673,7260.000000] [301678,7270.000000] [301683,7270.000000] [301688,7360.000000] [301693,7350.000000] [301698,7320.000000] [301703,7260.000000] [301708,7220.000000] [301713,7220.000000] [301718,7220.000000] [301723,7240.000000] [301728,7230.000000] [301733,7210.000000] [301738,7180.000000] [301743,7150.000000] [301748,7100.000000] [301753,7070.000000] [301758,7000.000000] [301763,6950.000000] [301768,6850.000000] [301773,6860.000000] [301778,6790.000000] [301783,6740.000000] [301788,6730.000000] [301793,6710.000000] [301798,6740.000000] [301803,6730.000000] [301808,6680.000000] [301813,6680.000000] [301818,6660.000000] [301823,6620.000000] [301828,6580.000000] [301833,6540.000000] [301838,6490.000000] [301843,6370.000000] [301848,6380.000000] [301853,6350.000000] [301858,6340.000000] [301863,6350.000000] [301868,6350.000000] [301873,6310.000000] [301878,6270.000000]  -> new:[301338,4750.000000] [301343,4730.000000] [301348,4760.000000] [301353,4770.000000] [301358,4840.000000] [301363,4890.000000] [301368,4880.000000] [301373,4960.000000] [301378,5000.000000] [301383,4960.000000] [301388,4930.000000] [301393,5010.000000] [301398,5120.000000] [301403,5230.000000] [301408,5290.000000] [301413,5290.000000] [301418,5320.000000] [301423,5370.000000] [301428,5380.000000] [301433,5480.000000] [301438,5540.000000] [301443,5600.000000] [301448,5630.000000] [301453,5670.000000] [301458,5740.000000] [301463,5790.000000] [301468,5870.000000] [301473,5900.000000] [301478,5950.000000] [301483,6020.000000] [301488,6080.000000] [301493,6130.000000] [301498,6180.000000] [301503,6180.000000] [301508,6200.000000] [301513,6230.000000] [301518,6240.000000] [301523,6250.000000] [301528,6270.000000] [301533,6270.000000] [301538,6300.000000] [301543,6360.000000] [301548,6450.000000] [301553,6570.000000] [301558,6630.000000] [301563,6700.000000] [301568,6690.000000] [301573,6670.000000] [301578,6610.000000] [301583,6710.000000] [301588,6700.000000] [301593,6730.000000] [301598,6760.000000] [301603,6790.000000] [301608,6840.000000] [301613,6860.000000] [301618,6930.000000] [301623,6970.000000] [301628,7000.000000] [301633,7040.000000] [301638,7070.000000] [301643,7050.000000] [301648,7050.000000] [301653,7080.000000] [301658,7170.000000] [301663,7240.000000] [301668,7250.000000] [301673,7260.000000] [301678,7270.000000] [301683,7270.000000] [301688,7360.000000] [301693,7350.000000] [301698,7320.000000] [301703,7260.000000] [301708,7220.000000] [301713,7220.000000] [301718,7220.000000] [301723,7240.000000] [301728,7230.000000] [301733,7210.000000] [301738,7180.000000] [301743,7150.000000] [301748,7100.000000] [301753,7070.000000] [301758,7000.000000] [301763,6950.000000] [301768,6850.000000] [301773,6860.000000] [301778,6790.000000] [301783,6740.000000] [301788,6730.000000] [301793,6710.000000] [301798,6740.000000] [301803,6730.000000] [301808,6680.000000] [301813,6680.000000] [301818,6660.000000] [301823,6620.000000] [301828,6580.000000] [301833,6540.000000] [301838,6490.000000] [301843,6370.000000] [301848,6380.000000] [301853,6350.000000] [301858,6340.000000] [301863,6350.000000] [301868,6350.000000] [301873,6310.000000] [301878,6270.000000] 
[2026-08-08 04:12:01.635 UTC] [V] OFSCtrl Nod No2 -2.000000 < 0.499630((max:7360.000000-min:3980.000000)/99000.000000*60/diff:410*100) < 2.000000
[2026-08-08 04:12:01.635 UTC] [V] OFSCtrl update p_co_old:6270.000000
[2026-08-08 04:12:01.635 UTC] [V] OFSCtrl Nod calc proc:0102
[2026-08-08 04:12:01.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.638 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:12:01.635 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:12:01.667 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:01.690 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:12:01 val:6270.000000
[2026-08-08 04:12:01.691 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:12:01' , 6270.000000 , 0  )
[2026-08-08 04:12:01.712 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:01.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.738 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:01.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.839 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:01.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1174->1174] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:01.939 UTC] [V] OFSCtrl angif value:1174 power_val_:5712.500000
[2026-08-08 04:12:01.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:01.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5800.300000 = p_th_old_:5790.400000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:01.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15205.163791 = old:-15248.349791 +  kp:0.550000 * e:87.800000 + ki:0.000000 * sume:9372423.300239 + kd:0.040000 * (e:87.800000 - e1:215.400000)
[2026-08-08 04:12:01.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15205.163791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:01.942 UTC] [V] OFSCtrl CHG 29 q:-153.000000, mod(round):1.000000
[2026-08-08 04:12:01.943 UTC] [D] OFSCtrl battery ctrl val:-30.400000
[2026-08-08 04:12:01.943 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:01.944 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:02.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:02.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:02.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:02.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:02.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301841 UPRstat:0
[2026-08-08 04:12:02.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:02.201 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:02.202 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:02.202 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:02.202 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:02.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.238 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.339 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.439 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:02.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:02.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.638 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:02.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.738 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.839 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:02.939 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:02.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:02.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5810.200000 = p_th_old_:5800.300000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:02.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15232.157791 = old:-15205.163791 +  kp:0.550000 * e:-39.800000 + ki:0.000000 * sume:9372383.500239 + kd:0.040000 * (e:-39.800000 - e1:87.800000)
[2026-08-08 04:12:02.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15232.157791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:02.940 UTC] [V] OFSCtrl CHG 29 q:-153.000000, mod(round):1.000000
[2026-08-08 04:12:02.941 UTC] [D] OFSCtrl battery ctrl val:-30.500000
[2026-08-08 04:12:02.941 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:02.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:03.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.039 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:12:03.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:03.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:03.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:03.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.138 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301842 UPRstat:0
[2026-08-08 04:12:03.200 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:03.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:03.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:03.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:03.201 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:03.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.238 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.339 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.439 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.539 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:03.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.738 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:03.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.838 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:03.939 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:03.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:03.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5820.100000 = p_th_old_:5810.200000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:03.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15248.206791 = old:-15232.157791 +  kp:0.550000 * e:-29.900000 + ki:0.000000 * sume:9372353.600239 + kd:0.040000 * (e:-29.900000 - e1:-39.800000)
[2026-08-08 04:12:03.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15248.206791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:03.940 UTC] [V] OFSCtrl CHG 29 q:-153.000000, mod(round):1.000000
[2026-08-08 04:12:03.940 UTC] [D] OFSCtrl battery ctrl val:-30.500000
[2026-08-08 04:12:03.941 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:03.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:03.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:03.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:03.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:04.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.038 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:04.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301843 UPRstat:0
[2026-08-08 04:12:04.089 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:04.090 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:04.090 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:04.090 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:04.090 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:04.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.138 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:04.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.238 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:04.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.339 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:04.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.439 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:04.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:04.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.638 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:04.640 UTC] [V] 485ChCtl <C3> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018492, monitor_cnt:50, bc_elapsed:3018492, min:10, max:40
[2026-08-08 04:12:04.640 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:12:04.640 UTC] [V] 485DevCtl <C3:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:04.641 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :12
[2026-08-08 04:12:04.641 UTC] [V] 485ChCtl <C3> send request:Sungrow11
[2026-08-08 04:12:04.642 UTC] [D] 485AcReq <C3:01> PutOStream [12][0c00000100000006010427580001]
[2026-08-08 04:12:04.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:04.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.738 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:04.768 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301844 UPRstat:0
[2026-08-08 04:12:04.769 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[11] [0001000000050104020010]
[2026-08-08 04:12:04.769 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [12] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:12:04.769 UTC] [V] 485DevCtl <C3:01> [02][753040][1.000000][0][]
[2026-08-08 04:12:04.769 UTC] [V] SummDat SetVrmValue dev_id:9 val:1.000000 sc:0
[2026-08-08 04:12:04.770 UTC] [V] OCMgr SetMeterValue PhId:0301, branchNo:02, valueId:753040, value:1.000000, scaleFactor:0, devId:9
[2026-08-08 04:12:04.770 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:04.778 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:04.781 UTC] [D] 485ChCtl <C3> monitoring dev All Send
[2026-08-08 04:12:04.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.838 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:04.920 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018495, monitor_cnt:50, bc_elapsed:3018495, min:10, max:40
[2026-08-08 04:12:04.920 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:12:04.921 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :10
[2026-08-08 04:12:04.921 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:12:04.922 UTC] [D] 485AcReq <C2:01> PutOStream [10][0800010413d80002f574]
[2026-08-08 04:12:04.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:04.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:04.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:04.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5830.000000 = p_th_old_:5820.100000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:04.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15218.248291 = old:-15248.206791 +  kp:0.550000 * e:48.750000 + ki:0.000000 * sume:9372402.350239 + kd:0.040000 * (e:48.750000 - e1:-29.900000)
[2026-08-08 04:12:04.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15218.248291 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:04.940 UTC] [V] OFSCtrl CHG 29 q:-153.000000, mod(round):1.000000
[2026-08-08 04:12:04.942 UTC] [D] OFSCtrl battery ctrl val:-30.400000
[2026-08-08 04:12:04.942 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:04.942 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:05.038 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.038 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:05.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:05.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:05.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:05.049 UTC] [V] CIStDb UpdateStatusData. [SELECT no, on_time, off_time FROM contact_input_status WHERE no BETWEEN '1' AND '9' ORDER BY no ASC ]
[2026-08-08 04:12:05.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.208 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301844 UPRstat:0
[2026-08-08 04:12:05.212 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:05.214 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:05.215 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:05.216 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:05.220 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:05.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.239 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:05.253 UTC] [D] 485DevCtl <C2:01> RcvDat status[2] len[9] [010404100000027e85]
[2026-08-08 04:12:05.253 UTC] [D] 485DevCtl <C2:01> ResCnd OperationId [10] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:12:05.254 UTC] [V] 485DevCtl <C2:01> device_type:PV-PCS
[2026-08-08 04:12:05.256 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounter value0
[2026-08-08 04:12:05.257 UTC] [V] 485DevCtl <C2:01> ExecuteAction set start cnt:0
[2026-08-08 04:12:05.257 UTC] [V] 485DevCtl <C2:01> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:12:05.260 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:12:05.321 UTC] [V] 485ChCtl <C2> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018499, monitor_cnt:54, bc_elapsed:3018499, min:10, max:40
[2026-08-08 04:12:05.321 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :10
[2026-08-08 04:12:05.323 UTC] [V] 485ChCtl <C2> send request:Sungrow08
[2026-08-08 04:12:05.324 UTC] [D] 485AcReq <C2:02> PutOStream [10][0800020413d80002f547]
[2026-08-08 04:12:05.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.338 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:05.404 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:05.404 UTC] [V] 485ChCtl <C1> fixed cycle Irr-Meter
[2026-08-08 04:12:05.404 UTC] [V] 485DevCtl <C1:01> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:05.404 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:12:05.405 UTC] [V] 485ChCtl <C1> send request:Irr01
[2026-08-08 04:12:05.406 UTC] [D] 485AcReq <C1:01> PutOStream [1][080001040000000271cb]
[2026-08-08 04:12:05.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.438 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.639 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:05.656 UTC] [D] 485DevCtl <C2:02> RcvDat status[2] len[9] [020404100000024d85]
[2026-08-08 04:12:05.656 UTC] [D] 485DevCtl <C2:02> ResCnd OperationId [10] IsNormal[1]  ConditionType [lggrdev:Normal] Action[-1]
[2026-08-08 04:12:05.657 UTC] [V] 485DevCtl <C2:02> device_type:PV-PCS
[2026-08-08 04:12:05.657 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounter value0
[2026-08-08 04:12:05.657 UTC] [V] 485DevCtl <C2:02> ExecuteAction set start cnt:0
[2026-08-08 04:12:05.657 UTC] [V] 485DevCtl <C2:02> ExecuteAction name:RestartCounterStat value0
[2026-08-08 04:12:05.658 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:12:05.659 UTC] [D] 485ChCtl <C2> monitoring dev All Send
[2026-08-08 04:12:05.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:05.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.739 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.742 UTC] [V] 485DevCtl <C1:01> AnalyzeResponseData proc restart cnt:301846 UPRstat:0
[2026-08-08 04:12:05.743 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:05.743 UTC] [D] 485DevCtl <C1:01> RcvDat status[2] len[9] [01040408a10224a97d]
[2026-08-08 04:12:05.744 UTC] [D] 485DevCtl <C1:01> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:12:05.744 UTC] [V] OFSCtrl Rcv set flux_of_solar:220.900000
[2026-08-08 04:12:05.744 UTC] [V] 485DevCtl <C1:01> [01][401006][2209.000000][1][W/m2]
[2026-08-08 04:12:05.745 UTC] [V] SummDat SetVrmValue dev_id:1 val:220900.000000 sc:3
[2026-08-08 04:12:05.745 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:401006, value:2209.000000, scaleFactor:1, devId:1
[2026-08-08 04:12:05.745 UTC] [V] 485DevCtl <C1:01> [01][421005][298.000000][1][℃]
[2026-08-08 04:12:05.745 UTC] [V] SummDat SetVrmValue dev_id:1 val:29800.000000 sc:3
[2026-08-08 04:12:05.746 UTC] [V] OCMgr SetMeterValue PhId:0101, branchNo:01, valueId:421005, value:298.000000, scaleFactor:1, devId:1
[2026-08-08 04:12:05.746 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:05.746 UTC] [V] OFSCtrl Irr-Meter received.
[2026-08-08 04:12:05.758 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:12:05.759 UTC] [V] 485DevCtl <C1:01> device_type:Irr-Meter
[2026-08-08 04:12:05.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:05.804 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:05.804 UTC] [V] 485ChCtl <C1> fixed cycle CO-Meter
[2026-08-08 04:12:05.804 UTC] [V] 485DevCtl <C1:04> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:05.804 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:12:05.806 UTC] [V] 485ChCtl <C1> send request:omron05
[2026-08-08 04:12:05.807 UTC] [D] 485AcReq <C1:04> PutOStream [1][0800040300030014b590]
[2026-08-08 04:12:05.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.838 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.939 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:05.939 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:05.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:05.940 UTC] [V] OFSCtrl CHG 20 p_th(t):5839.900000 = p_th_old_:5830.000000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:05.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15185.594791 = old:-15218.248291 +  kp:0.550000 * e:58.650000 + ki:0.000000 * sume:9372461.000239 + kd:0.040000 * (e:58.650000 - e1:48.750000)
[2026-08-08 04:12:05.941 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15185.594791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:05.942 UTC] [V] OFSCtrl CHG 29 q:-152.000000, mod(round):0.000000
[2026-08-08 04:12:05.942 UTC] [D] OFSCtrl battery ctrl val:-30.400000
[2026-08-08 04:12:05.944 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:05.945 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:06.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.039 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:06.040 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:06.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:06.042 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:06.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.139 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:06.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301845 UPRstat:0
[2026-08-08 04:12:06.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:06.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:06.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:06.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:06.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:06.219 UTC] [V] 485DevCtl <C1:04> AnalyzeResponseData proc restart cnt:301845 UPRstat:0
[2026-08-08 04:12:06.219 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:06.220 UTC] [D] 485DevCtl <C1:04> RcvDat status[2] len[45] [04032800005fd50000603d0000545800000050000002580000f67c00000277ffff49e6fffffe2e0012168508d9]
[2026-08-08 04:12:06.221 UTC] [D] 485DevCtl <C1:04> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:12:06.222 UTC] [V] OFSCtrl Rcv set p_co:6310.000000, p_co_old:6270.000000
[2026-08-08 04:12:06.222 UTC] [V] 485DevCtl <C1:04> [01][601260][631.000000][2][kW]
[2026-08-08 04:12:06.225 UTC] [V] SummDat SetVrmValue dev_id:4 val:6310.000000 sc:3
[2026-08-08 04:12:06.228 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:601260, value:631.000000, scaleFactor:2, devId:4
[2026-08-08 04:12:06.229 UTC] [V] 485DevCtl <C1:04> [01][603260][1185413.000000][1][kWh]
[2026-08-08 04:12:06.229 UTC] [V] SummDat SetVrmValue dev_id:4 val:1185413.000000 sc:1
[2026-08-08 04:12:06.229 UTC] [V] OCMgr SetMeterValue PhId:0104, branchNo:01, valueId:603260, value:1185413.000000, scaleFactor:1, devId:4
[2026-08-08 04:12:06.229 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:06.229 UTC] [V] OFSCtrl km50 received.
[2026-08-08 04:12:06.230 UTC] [V] OFSCtrl omron05_local_date :2026/08/08 ? 2026/08/08
[2026-08-08 04:12:06.230 UTC] [V] OFSCtrl omron05_local_time :2026/08/08 13 ? 2026/08/08 13
[2026-08-08 04:12:06.230 UTC] [V] OFSCtrl within control time.
[2026-08-08 04:12:06.230 UTC] [V] OFSCtrl UpdateCombinedPowerDb is_low_solar_pco:1, value:6310.000000
[2026-08-08 04:12:06.230 UTC] [V] OFSCtrl UpdateCombinedPowerDb flux_of_solar:220.900000 < rad_th:80.000000
[2026-08-08 04:12:06.230 UTC] [D] OFSCtrl UpdateCombinedPowerDb save value:301883:6310.000000
[2026-08-08 04:12:06.231 UTC] [V] OFSCtrl Control pv-pcs proc start.
[2026-08-08 04:12:06.231 UTC] [V] OFSCtrl NOD_month:-1270.000000 = (NOD_month:306 - ((nod_max_/30):23.333333 * (cnt-1):24) * (30/cnt):5.000000 
[2026-08-08 04:12:06.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.239 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:06.257 UTC] [V] OFSCtrl PCS ratio_month:194.135338 = -k_inhibition_ratio_month:-0.097744 * NOD_month:-1270.000000 + inhibition_ratio_max:70
[2026-08-08 04:12:06.259 UTC] [V] OFSCtrl PCS 05 inhibition_ratio:63.035714 = max(ratio_min:5, min(ratio:70, ratio_hour:70.000000, ratio_day:63.035714, ratio_month:194.135338))
[2026-08-08 04:12:06.264 UTC] [D] OFSCtrl pv-pcs ctrl val:22.785692 old:22.373094
[2026-08-08 04:12:06.266 UTC] [V] OCHisDB set rate:23 t_rate:517 cnt:25
[2026-08-08 04:12:06.271 UTC] [V] 485ChCtl <C2> pv-pcs limit on [22.785692] request.
[2026-08-08 04:12:06.272 UTC] [V] OFSCtrl Control pv-pcs proc:BATT_CHK->01->02->03->04->05->06->07->09->09->10->11->12
[2026-08-08 04:12:06.275 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:12:06.276 UTC] [V] 485DevCtl <C1:04> device_type:CO-Meter
[2026-08-08 04:12:06.321 UTC] [V] 485ChCtl <C2> pv-pcs send request.
[2026-08-08 04:12:06.321 UTC] [D] VarInf update ofs_rate:22.785692
[2026-08-08 04:12:06.321 UTC] [V] VarInf LimitSet rt[2] val[170] key[ValueOn]
[2026-08-08 04:12:06.321 UTC] [D] VarInf output_mode:8
[2026-08-08 04:12:06.321 UTC] [D] VarInf update ofs_rate:22.785692
[2026-08-08 04:12:06.322 UTC] [D] VarInf Limit setRate[227.856918] rate[22.785692] value100[1000.000000] value0[0.000000]
[2026-08-08 04:12:06.322 UTC] [V] 485DevCtl <C2:01> ChangeOutputRateToDevice rate:22.785692 set_rate228
[2026-08-08 04:12:06.322 UTC] [D] VarInf Limit rt[2] int_set_rate[228] server_rate[22.785692] rated_output[100.000000] solar_battery_power[100.000000]
[2026-08-08 04:12:06.324 UTC] [D] 485AcReq <C2:01> PutOStreamForBc [3][0d000010138e00020400aa00e487e4]
[2026-08-08 04:12:06.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.338 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:06.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.438 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:06.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.539 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:06.619 UTC] [V] 485ChCtl <C2> set rt:0
[2026-08-08 04:12:06.639 UTC] [V] OFSCtrl limit chk 400 < 800 < [1175->1175] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.639 UTC] [V] OFSCtrl angif value:1175 power_val_:5781.250000
[2026-08-08 04:12:06.689 UTC] [V] CPHisDb InsertHistory time:2026-08-08 04:12:06 val:6310.000000
[2026-08-08 04:12:06.690 UTC] [V] CPHisDb query:INSERT INTO combined_power_history  (  time , value , sent  ) VALUES (  '2026-08-08 04:12:06' , 6310.000000 , 0  )
[2026-08-08 04:12:06.715 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:06.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.739 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:06.838 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.838 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:06.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1176->1176] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:06.938 UTC] [V] OFSCtrl angif value:1176 power_val_:5850.000000
[2026-08-08 04:12:06.938 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:06.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5849.800000 = p_th_old_:5839.900000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:06.940 UTC] [V] OFSCtrl CHG 21 batt_w:-15188.058791 = old:-15185.594791 +  kp:0.550000 * e:-0.200000 + ki:0.000000 * sume:9372460.800239 + kd:0.040000 * (e:-0.200000 - e1:58.650000)
[2026-08-08 04:12:06.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15188.058791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:06.940 UTC] [V] OFSCtrl CHG 29 q:-152.000000, mod(round):0.000000
[2026-08-08 04:12:06.940 UTC] [D] OFSCtrl battery ctrl val:-30.400000
[2026-08-08 04:12:06.941 UTC] [V] 485ChCtl <C3> battery limit on [-152.000000,] request.
[2026-08-08 04:12:06.941 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:07.039 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.039 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:07.041 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:07.041 UTC] [D] VarInf Limit_Bat rt[2]set val[-152] set rate[-30.400000] value100[500] value-100[-500]
[2026-08-08 04:12:07.043 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff68]
[2026-08-08 04:12:07.139 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.139 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:12:07.198 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301846 UPRstat:0
[2026-08-08 04:12:07.199 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:07.200 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:07.200 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:07.200 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:07.200 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:07.239 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.239 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:07.339 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.339 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:12:07.438 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.439 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:12:07.538 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.538 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:12:07.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018522, monitor_cnt:100, bc_elapsed:22, min:10, max:40
[2026-08-08 04:12:07.604 UTC] [V] OFSCtrl /var/local/solajithome/function/output_fluctuation_suppression/state is exist:0
[2026-08-08 04:12:07.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.638 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:07.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:07.704 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018523, monitor_cnt:101, bc_elapsed:23, min:10, max:40
[2026-08-08 04:12:07.704 UTC] [V] 485DevCtl <C1:02> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:07.704 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:12:07.705 UTC] [V] 485ChCtl <C1> send request:IMT01
[2026-08-08 04:12:07.705 UTC] [D] 485AcReq <C1:02> PutOStream [1][08000204000200019039]
[2026-08-08 04:12:07.739 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.739 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:12:07.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.839 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:07.938 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:07.939 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:07.939 UTC] [V] OFSCtrl Control charge discharge proc start.
[2026-08-08 04:12:07.939 UTC] [V] OFSCtrl CHG 20 p_th(t):5859.700000 = p_th_old_:5849.800000 + lev_cd_:0.300000 * (total_pcs_capacity_:99000.000000 * cof_spec_:2.000000 / 60 * (time_threshold_renew:10.000000 * 10)), min:-1100.000000, max:119300.000000
[2026-08-08 04:12:07.939 UTC] [V] OFSCtrl CHG 21 batt_w:-15344.577791 = old:-15188.058791 +  kp:0.550000 * e:-265.300000 + ki:0.000000 * sume:9372195.500239 + kd:0.040000 * (e:-265.300000 - e1:-0.200000)
[2026-08-08 04:12:07.940 UTC] [V] OFSCtrl CHG 21 battery threshold min:5000.000000 <= bat:15344.577791 <= max:50000.000000, adjust charge:-0.000000, discharge:0.000000
[2026-08-08 04:12:07.940 UTC] [V] OFSCtrl CHG 29 q:-154.000000, mod(round):1.000000
[2026-08-08 04:12:07.940 UTC] [D] OFSCtrl battery ctrl val:-30.700000
[2026-08-08 04:12:07.941 UTC] [V] 485ChCtl <C3> battery send request.1
[2026-08-08 04:12:07.941 UTC] [D] VarInf Limit_Bat rt[2]set val[-153] set rate[-30.600000] value100[500] value-100[-500]
[2026-08-08 04:12:07.943 UTC] [D] 485AcReq <C3:01> PutOStream [6][0f000001000000090110278e000102ff67]
[2026-08-08 04:12:07.947 UTC] [V] 485ChCtl <C3> battery limit on [-153.000000,] request.
[2026-08-08 04:12:07.948 UTC] [V] OFSCtrl Control charge discharge proc:01->02->BATT_CHK->03->04->20->21->22->23->24->26->27->28->29->30->31->32->33->34
[2026-08-08 04:12:08.037 UTC] [V] 485DevCtl <C1:02> AnalyzeResponseData proc restart cnt:301841 UPRstat:0
[2026-08-08 04:12:08.038 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:08.038 UTC] [D] 485DevCtl <C1:02> RcvDat status[2] len[7] [020402021cfd99]
[2026-08-08 04:12:08.038 UTC] [D] 485DevCtl <C1:02> ResCnd OperationId [1] IsNormal[1] 
[2026-08-08 04:12:08.039 UTC] [V] 485DevCtl <C1:02> [01][431005][290.000000][1][°C]
[2026-08-08 04:12:08.039 UTC] [V] SummDat SetVrmValue dev_id:2 val:29000.000000 sc:3
[2026-08-08 04:12:08.039 UTC] [V] OCMgr SetMeterValue PhId:0102, branchNo:01, valueId:431005, value:290.000000, scaleFactor:1, devId:2
[2026-08-08 04:12:08.039 UTC] [V] 485DevCtl <C1:02> device_type:
[2026-08-08 04:12:08.040 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:12:08.041 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.041 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:08.088 UTC] [V] 485DevCtl <C3:01> AnalyzeResponseData proc restart cnt:301847 UPRstat:0
[2026-08-08 04:12:08.091 UTC] [V] Query CheckPresetMultipleResisterRequest check data:0c000001000000090110278e0001 - 0110278e0001
[2026-08-08 04:12:08.092 UTC] [D] 485DevCtl <C3:01> RcvDat status[0] len[12] [0001000000060110278e0001]
[2026-08-08 04:12:08.092 UTC] [D] 485DevCtl <C3:01> ResCnd OperationId [6] IsNormal[1] 
[2026-08-08 04:12:08.092 UTC] [V] 485DevCtl <C3:01> device_type:Battery
[2026-08-08 04:12:08.093 UTC] [V] 485ChCtl <C3> set rt:0
[2026-08-08 04:12:08.104 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018527, monitor_cnt:105, bc_elapsed:27, min:10, max:40
[2026-08-08 04:12:08.104 UTC] [V] 485DevCtl <C1:03> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:08.104 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :2
[2026-08-08 04:12:08.104 UTC] [V] 485ChCtl <C1> send request:omron03
[2026-08-08 04:12:08.105 UTC] [D] 485AcReq <C1:03> PutOStream [2][08000303002000084424]
[2026-08-08 04:12:08.138 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.138 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:08.238 UTC] [V] OFSCtrl limit chk 400 < 800 < [1180->1180] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.238 UTC] [V] OFSCtrl angif value:1180 power_val_:6125.000000
[2026-08-08 04:12:08.338 UTC] [V] OFSCtrl limit chk 400 < 800 < [1179->1179] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.338 UTC] [V] OFSCtrl angif value:1179 power_val_:6056.250000
[2026-08-08 04:12:08.439 UTC] [V] OFSCtrl limit chk 400 < 800 < [1177->1177] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.439 UTC] [V] OFSCtrl angif value:1177 power_val_:5918.750000
[2026-08-08 04:12:08.462 UTC] [V] 485DevCtl <C1:03> AnalyzeResponseData proc restart cnt:301841 UPRstat:0
[2026-08-08 04:12:08.463 UTC] [V] Res no response condition. set normal condition.
[2026-08-08 04:12:08.464 UTC] [D] 485DevCtl <C1:03> RcvDat status[2] len[21] [030310000000003822752a000000000006843bab8e]
[2026-08-08 04:12:08.464 UTC] [D] 485DevCtl <C1:03> ResCnd OperationId [2] IsNormal[1] 
[2026-08-08 04:12:08.465 UTC] [V] StructInfo Add 941782.314000 = 0.000000+941782.314000+0.000000
[2026-08-08 04:12:08.465 UTC] [V] 485DevCtl <C1:03> [01][603202][94178231.400000][2][kWh]
[2026-08-08 04:12:08.465 UTC] [V] SummDat SetVrmValue dev_id:3 val:94178231.400000 sc:2
[2026-08-08 04:12:08.470 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:603202, value:94178231.400000, scaleFactor:2, devId:3
[2026-08-08 04:12:08.471 UTC] [V] 485DevCtl <C1:03> [01][604202][94178231.400000][2][kWh]
[2026-08-08 04:12:08.471 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:604202, value:94178231.400000, scaleFactor:2, devId:3
[2026-08-08 04:12:08.472 UTC] [V] StructInfo Add 427.067000 = 0.000000+427.067000+0.000000
[2026-08-08 04:12:08.472 UTC] [V] 485DevCtl <C1:03> [01][613202][42706.700000][2][kWh]
[2026-08-08 04:12:08.482 UTC] [V] SummDat SetVrmValue dev_id:3 val:42706.700000 sc:2
[2026-08-08 04:12:08.486 UTC] [V] OCMgr SetMeterValue PhId:0103, branchNo:01, valueId:613202, value:42706.700000, scaleFactor:2, devId:3
[2026-08-08 04:12:08.491 UTC] [V] 485DevCtl <C1:03> device_type:Grid-Meter
[2026-08-08 04:12:08.499 UTC] [V] 485ChCtl <C1> set rt:0
[2026-08-08 04:12:08.504 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018531, monitor_cnt:109, bc_elapsed:31, min:10, max:40
[2026-08-08 04:12:08.539 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.539 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:12:08.604 UTC] [V] 485ChCtl <C1> StartDeviceCommunicationForOutputFluctuationSuppressionControlBroadcast 4 cnt:3018532, monitor_cnt:110, bc_elapsed:32, min:10, max:40
[2026-08-08 04:12:08.604 UTC] [V] 485DevCtl <C1:05> Dev not PCS IsNeedToChangeOControlState
[2026-08-08 04:12:08.604 UTC] [V] SCCtl  GetRegistryPurchaseMeterOperationId :1
[2026-08-08 04:12:08.605 UTC] [V] 485ChCtl <C1> send request:omron04
[2026-08-08 04:12:08.606 UTC] [D] 485AcReq <C1:05> PutOStream [1][0800050300030014b441]
[2026-08-08 04:12:08.638 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.638 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:12:08.690 UTC] [V] OFSCtrl [/var/local/solajithome/function/output_fluctuation_suppression/batt_data] write success.
[2026-08-08 04:12:08.738 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.738 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000
[2026-08-08 04:12:08.839 UTC] [V] OFSCtrl limit chk 400 < 800 < [1178->1178] < 4000 < 4000 , cnt:0:0:601 
[2026-08-08 04:12:08.839 UTC] [V] OFSCtrl angif value:1178 power_val_:5987.500000